
Conformity and standards
1. The UPS complies with 2014/35/EU (LVD), 2014/30/EU (EMC), 2011/65/EU (Rohs) and the following product
standards for UPS:
IEC/EN 62040-1, General and safety requirements for UPS
IEC/EN 62040-2: Class C2 compliant
IEC/EN 62040-3: Performance requirements and test methods
2. Continued compliance requires installation in accordance with these instructions and the use of manufacturer
approved accessories only.
Warning
1. Before moving or rewiring the UPS, disconnect mains input power and the battery and make sure that the
UPS is completely shut down. Otherwise, the output terminal may carry live voltage, presenting an electric
shock hazard.
2. Liquid or other irrelevant external objects are prohibited inside the UPS.
3. In case of a fire, a dry chemical fire extinguisher is essential. Using a foam fire extinguisher will cause electric
shock.
4. To prevent the radio frequency of output cables from disturbing other electric equipment, it is recommended
to use the UPS output cable with the length less than 10m.
Warning: high earth leakage current
1. Earth connection is critical before connecting the input supply (including both mains supply and battery).
2. Earth leakage current is less than 2500mA.
3. Transient and steady state earth leakage currents, which may occur when the equipment is started, should be
taken into account in the selection of instantaneous RCCBs or RCD devices. RCCB which is sensitive to
unidirectional DC pulse (class A) and insensitive to transient state current pulse must be selected.
4. Note also that the earth leakage currents of the load will be carried by the RCCBs or RCDs.
5. The equipment must be earthed in accordance with the local electrical code of practice.
Warning: backfeeding protection
This UPS is fitted with a dry contact closure signal for use with an external automatic disconnect device
(supplied independently) to protect against backfeeding voltage into the incoming terminal through the rectifier
or bypass switch circuit. A label must be added at all external incoming primary supply disconnect device to
warn service personnel that the circuit is connected to a UPS. The text of the label has the following m eaning:
Risk of voltage backfeed! Isolate the UPS, then check for hazardous voltage between all terminals including the
protective earth before working on this circuit.