Reliable HL22 User manual

Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bulletin 010 February 2020
Bulletin 010 February 2020
Model HL22 (SIN RA1011)
K22.4 (320 metric)
Early Suppression
Fast Response (ESFR) Sprinkler
Product Description
The Reliable Model HL22 is an Early Suppression Fast
Response (ESFR) Sprinkler with a nominal k-factor of
22.4 (320 metric). This sprinkler is designed to respond
quickly to growing fires with a high volume of water
discharge to “suppress” rather than “control” fires.
FM Global classifies the Model HL22 as a quick-
response sprinkler, storage and non-storage, when the
sprinkler is used in accordance with FM Global Property
Loss Prevention Data Sheets.
The Model HL22 sprinkler utilizes a levered fusible
alloy solder link in either 165°F (74°C) or 212°F (100°C)
temperature rating. The sprinkler has a nominal K Factor
of 22.4 (metric 320), and is available with 1” NPT or
ISO 7-R1 threads, or with the Victaulic® IGS™ Style V9
Sprinkler Coupling*.
Application and Installation
The HL22 ESFR sprinkler is intended for installation
in accordance with NFPA 13 and Factory Mutual (FM)
Loss Prevention Data Sheets 2-0 and 8-9, as well as
the requirements of any Authorities Having Jurisdiction.
See Table 1 for information on NFPA and FM Global
design criteria for the Model HL22 sprinkler.
In addition to design criteria permitted by NFPA
13, the Model HL22 also has the following Specific
Application Listing from UL, as documented in Table C:
• Sprinkler: Model HL22 in 212°F (100°C) only
• Maximum Ceiling Height: 48 ft. (14.6 m)
• Maximum Storage Height: 43 ft. (13.1 m)
• Minimum Aisle Width: 8 ft. (2.44 m)
• Permitted Commodities: Class I - IV commodities,
encapsulated or nonencapsulated, and Cartoned
Group A Unexpanded plastics. Permitted
Storage Arrangements: Single- and double-row
rack storage (no open top containers or solid
shelves) and palletized and solid pile storage
(no open top containers or solid shelves).
• Minimum System Operating
Pressure: 55 psi (3.79 bar).
• Installation and Obstruction Criteria: Same as
for K25.2 ESFR sprinklers, but with a maximum
deflector to ceiling distance of 14 in. (356 mm)
Follow installation criteria in NFPA 13 or FM Global
Property Loss Prevention Data Sheets. For installations
using the UL Listed Specific Application Criteria for
ceiling heights up to 48 ft. (14.6 m), also follow the
additional installation criteria contained in this bulletin.
Model HL22 Sprinkler
Listings and Approvals
1. Listed by Underwriters Laboratories, Inc.
and UL certified for Canada (cULus).
2. FM Approved as a quick-response, storage
and non-storage, sprinkler (FM).
3. VdS Schadenverhütung (VdS).
4. Loss Prevention Certification Board (LPCB).
5. CNBOP Technical Approval.
Sprinkler Guard or Water Shield Listings and
Approvals
HL22 ESFR
Pendent
Model S-5 Water Shield FM
Model 22 Guard FM
Optional Guards and Water Shields
Notes:
1. Guards and shields are approved for threaded sprinklers
only.
2. Water shield is listed for use only when the sprinkler is
installed within racks (IRAS) or under open grating (or similar)
areas as required by NFPA or FM standards.
3. Guard is listed for use only when the sprinkler is installed
within racks (IRAS).
*Note: Victaulic® and IGS™ are trademarks of Victaulic Company.
2.
ITEM DESCRIPTION
Sprinkler Identification Number (SIN) RA1011
K Factor US (Metric) 22.4 (320)
End Connection 1" NPT or ISO7 R-1 threads, IGS™Style V9 Sprinkler Coupling
Sprinkler Orientation Pendent
Maximum Working Pressure, PSI (bar) 175 PSI (12 bar)
Model HL22 Technical Data Table A
Shown with optional Model 22 Guard (ordered separately)
*FM Approved Only
Installation
For threaded sprinklers, use only the Model W5
sprinkler wrench. Any other type of wrench may
damage the sprinkler. Sprinklers should be tightened
between 22 - 30 ft-lbs (30 - 41 Nm) torque. Sprinklers
not tightened to recommended torque or tightened past
recommended torque may cause leakage or impairment
of the sprinkler. Damaged sprinklers must be replaced
immediately.
For grooved sprinklers, push the IGS™ Style V9
Sprinkler Coupling onto the grooved outlet until contact
with the center leg of the gasket occurs. Align the
sprinkler frame arms and the pads of the coupling with
the sprinkler piping and tighten the coupling until the
pads of the coupling meet. For additional information,
please reference Victaulic technical bulletin I-V9.
Caution: When handling sprinklers, hold sprinklers only
by the frame arms and do not apply any force on the link
assembly.
Maintenance
The Model HL22 ESFR Sprinkler should be inspected
and the sprinkler system maintained in accordance with
NFPA 25. Do not clean sprinkler with soap and water,
ammonia or any other cleaning fluid. Remove any
sprinkler that has been painted (other than factory applied)
Model HL22 Temperature Ratings and Approvals
Temperature
Classification
Temperature
Rating Link
Color
Frame
Color
Maximum Ambient
Temperature Approvals
Sprinkler
Identification
Number
(SIN)
°F °C °F °C
Ordinary 165 74 Black Uncolored 100 38 cULus, FM, VdS, LPCB, CNBOP RA1011
Intermediate 212 100 White White 150 66 cULus & UL Spec App, FM, VdS,
LPCB, CNBOP RA1011
Installation Data
Sprinkler Type Nominal Orifice End Connection Nominal K-Factor Maximum Working
Pressure
US Metric
Pendent 0.87”
(22.1mm)
1” NPT
ISO 7-R1 (Optional)
22.4 320 175 psi
(12.1 bar)
1” NPT threaded ISO 7-R1 threaded
IGS™Style V9 Sprinkler Coupling
3.
or damaged in any way. A stock of spare sprinklers
should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons
and packaging until used, to minimize the potential
for damage to sprinklers that would cause improper
operation or non-operation.
Once operated, automatic sprinklers cannot be
reassembled and reused. New sprinklers of the same
size, type and temperature rating must be installed. A
cabinet of replacement sprinklers should be provided for
this purpose.
Ordering Information
Specify:
1. Sprinkler Model: HL22
2. Temperature Rating
- 165F (74C)
- 212F (100C)
3. End Connection
- 1” NPT thread
- ISO 7 R-1 thread
- Victaulic® IGS™ Style V9 Sprinkler Coupling
Fig. 1 - Model W5 Wrench (for threaded sprinklers only)
Note: 1” S/142 IGS™ grooved
welded outlets are also available
from Reliable.
Storage Type NFPA FM GLOBAL
Sprinkler Type ESFR Storage
Response Type ESFR Quick Response
System Type Wet Wet
Temperature Rating °F (°C) 165, 212 (74, 100) 165, 212 (74, 100)
Roof Construction See NFPA 13 See FM Global 2-0
Ceiling Slope See NFPA 13 See FM Global 2-0
Maximum Coverage Area See NFPA 13 See FM Global 2-0
Minimum Coverage Area See NFPA 13 See FM Global 2-0
Maximum Spacing See NFPA 13 See FM Global 2-0
Minimum Spacing See NFPA 13 See FM Global 2-0
Minimum Clearance to Commodity See NFPA 13 See FM Global 2-0
Sprinkler Distance to Ceiling See NFPA 13 See FM Global 2-0
Open Frame, Single, Double, Multi-
ple Row, or Portable Rack Storage of
Class I - IV, Cartoned Unexp Plastics
See NFPA 13 See FM 2-0 & 8-9
Solid Pile or Palletized Stor-
age of Class I - IV and Car-
toned Unexp Plastics
See NFPA 13 See FM 2-0 & 8-9
Idle Pallet Storage See NFPA 13 See FM 2-0,8-9 & 8-24
Rubber Tire Storage See NFPA 13 See FM 2-0 & 8-3
Rolled Paper Storage See NFPA 13 See FM 8-21
Flammable Liquid Storage See NFPA 30 See FM 7-29
Aerosol Storage See NFPA 30B See FM 7-31
Auto Components in Portable Racks N/A N/A
Model HL22 Commodity Selection and Design Criteria Overview Table B
Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 02/20 P/N 9999970287
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years.
DESCRIPTION UL, Specific Application Criteria
Sprinkler Type ESFR
Temperature Rating °F (°C) 212 (100)
Response Type ESFR
System Type Wet
Maximum Area of Coverage See NFPA 13
Minimum Area of Coverage See NFPA 13
Maximum Slope Ceiling See NFPA 13
Maximum Spacing See NFPA 13
Minimum Spacing See NFPA 13
Deflector Distance from Walls See NFPA 13
Deflector to Top of Storage See NFPA 13
Deflector to Ceiling Distance 6"- 14" (150-350mm)
Maximum Ceiling Height 48ft (14.6m)
Maximum Storage Height 43ft (13.1m)
Storage Arrangement Single and double row rack storage, palletized and solid
pile storage. No open top containers or solid shelves.
Commodity Class I-IV commodities, encapsulated or nonencapsu-
lated, and Cartoned Group A Unexpanded plastics
Sprinkler System Design 55 PSI (3.8 bar) design pressure,12 sprinklers in remote area
Obstruction Criteria See NFPA 13
Minimum Aisle Width 8ft (2.4m)
Hose Stream Allowance and Duration See NFPA 13
Model HL22 Commodity Selection and Design Criteria Overview Specific Application Listing (UL) Table C
Model HL22 ESFR Sprinkler Specification
Sprinklers shall be Early Suppression Fast Response (ESFR)
pendent suppression mode sprinklers cULus Listed and FM,
VdS, and LPCB Approved for commodity storage applications.
Sprinkler frame and deflector to be of bronze construction
with deflector located inside of the frame arms. Sprinkler shall
have a maximum listed/approved ceiling-to-deflector distance
of 18”. [Sprinklers shall have a UL Listed Specific Application
criteria permitting single- and double-row rack storage (no
open top containers or solid shelves) and palletized and
solid pile storage (no open top containers or solid shelves)
of Class I-IV commodities encapsulated or nonencapsulated
and cartoned Group A unexpanded plastics stored up to 43 ft
(13.1m) under ceilings up to 48 ft (14.6m) high when installed
with 8 ft. aisles, a minimum operating pressure of 55 psi
(3.79 bar), a maximum deflector to ceiling distance of 14 in
(356mm), and a temperature rating of 212°F (100°C).]
Fusible alloy solder link assembly shall utilize the strut and
lever principle of operation with approved fast response
beryllium-nickel thermal element with protective [black painted
(165°F)] [white painted (212°F)] coating. Water seal shall
consist of a PTFE coated Belleville spring washer and brass
cap assembly containing no plastic parts. ESFR sprinklers
shall have a nominal K-factor of 22.4 with [1” NPT threaded]
[ISO7-1R1 threaded] [Victaulic®IGS™ Style V9 Coupling].
Sprinkler temperature rating shall be [Ordinary 165°F (74°C)]
[Intermediate 212°F (100°C)]. ESFR pendent sprinklers shall
be Reliable Model HL22, SIN RA1011 (Bulletin 010).

This manual suits for next models

2

Other Reliable Irrigation System manuals

Reliable Pantman F1 User manual

Reliable

Reliable Pantman F1 User manual

Reliable F1FR56 Manual

Reliable

Reliable F1FR56 Manual

Reliable RFS42 Manual

Reliable

Reliable RFS42 Manual

Reliable F156 Series User manual

Reliable

Reliable F156 Series User manual

Reliable F4FR User manual

Reliable

Reliable F4FR User manual

Reliable RFC43 User manual

Reliable

Reliable RFC43 User manual

Reliable N25 User manual

Reliable

Reliable N25 User manual

Reliable XL Manual

Reliable

Reliable XL Manual

Reliable F1 Series Manual

Reliable

Reliable F1 Series Manual

Reliable F1FR-FS LO Manual

Reliable

Reliable F1FR-FS LO Manual

Reliable RFC56 User manual

Reliable

Reliable RFC56 User manual

Reliable Concealer G4A User manual

Reliable

Reliable Concealer G4A User manual

Reliable F3QR56 Dry Manual

Reliable

Reliable F3QR56 Dry Manual

Reliable F1S5 Series User manual

Reliable

Reliable F1S5 Series User manual

Reliable F1FR80VdS Series Manual

Reliable

Reliable F1FR80VdS Series Manual

Reliable G4 User manual

Reliable

Reliable G4 User manual

Reliable F1-SS Series User manual

Reliable

Reliable F1-SS Series User manual

Reliable F1-28 Series User manual

Reliable

Reliable F1-28 Series User manual

Reliable JL-14 User manual

Reliable

Reliable JL-14 User manual

Reliable GFR User manual

Reliable

Reliable GFR User manual

Reliable G6-80 Manual

Reliable

Reliable G6-80 Manual

Reliable F1FR-SS Series User manual

Reliable

Reliable F1FR-SS Series User manual

Reliable DH80 Dry User manual

Reliable

Reliable DH80 Dry User manual

Reliable F1FR56 Manual

Reliable

Reliable F1FR56 Manual

Popular Irrigation System manuals by other brands

Victaulic VicFlex AH1 manual

Victaulic

Victaulic VicFlex AH1 manual

Perrot Hydra M VAC operating manual

Perrot

Perrot Hydra M VAC operating manual

IrriGreen 2 Quick install guide

IrriGreen

IrriGreen 2 Quick install guide

Viking VK1021 Technical data

Viking

Viking VK1021 Technical data

Viking HORIZON H-3 Technical data

Viking

Viking HORIZON H-3 Technical data

Rain Bird 7005 Operation guide

Rain Bird

Rain Bird 7005 Operation guide

Rain Bird 3500 Series instructions

Rain Bird

Rain Bird 3500 Series instructions

Tyco DS-2 Series manual

Tyco

Tyco DS-2 Series manual

Seametrics EX90 quick start guide

Seametrics

Seametrics EX90 quick start guide

Senninger i-Wob UP3 Recommended installation

Senninger

Senninger i-Wob UP3 Recommended installation

Tyco Fire Product Star Mizar S210 instruction manual

Tyco Fire Product

Tyco Fire Product Star Mizar S210 instruction manual

Tyco 16.8 K-factor manual

Tyco

Tyco 16.8 K-factor manual

Tyco ELO-231B Series manual

Tyco

Tyco ELO-231B Series manual

Johnson Controls tyco DSB-2 manual

Johnson Controls

Johnson Controls tyco DSB-2 manual

Johnson Controls tyco RAPID RESPONSE LFII Series manual

Johnson Controls

Johnson Controls tyco RAPID RESPONSE LFII Series manual

Rain Bird Falcon 6504 Installation and operating guide

Rain Bird

Rain Bird Falcon 6504 Installation and operating guide

CENTRAL GBR manual

CENTRAL

CENTRAL GBR manual

Underhill Mirage M-160-FP-9 Operating and maintenance instructions

Underhill

Underhill Mirage M-160-FP-9 Operating and maintenance instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.