PROFIsafe Safety Modules
753-661/000-002 4FDI 24V PROFIsafe V2.0
753-662/000-002 8FDI 24V PROFIsafe V2.0
753-667/000-002 4FDI/4FDO 24V 2A PROFIsafe V2.0
1
Important Notes
NOTICE:
Please observe the guidelines in the corresponding manuals before startup!
Download: http://www.wago.com
NOTICE:
The PROFIsafe safety modules from the WAGO-I/O-SYSTEM 750 shall only be installed and started up by competent personnel who are familiar with the corresponding
manuals and the applicable regulations on work safety and accident prevention. VDE and local regulations shall be observed.
NOTICE:
The WAGO-I/O-SYSTEM 750 PROFIsafe safety modules shall be installed in switch cabinets with at least IP54.
NOTICE:
To prevent dirt accumulation and scratches, the safety modules shall not be placed on the gold spring contacts.
ESD (Electrostatic Discharge)
The modules are equipped with electronic components that may be destroyed by electrostatic discharge. When handling the modules, please ensure that environmental
factors (personnel, work space and packaging) are well grounded. Do not touch components that conduct electricity; e.g., gold spring contacts.
Use in Compliance with Underlying Provisions
The WAGO-I/O-SYSTEM 750 PROFIsafe safety modules are intended for use in EMERGENCY-STOP equipment and safety circuits. Modifying the safety modules or using
them improperly invalidates the warranty claim made to WAGO Kontakttechnik GmbH & Co. KG.
WAGO Kontakttechnik GmbH & Co. KG
Hansastr. 27
D-32423 Minden
www.wago.com
9970-0966/0753-0661 · 24.06.2009
Subject to design changes
E
Operating and Assembly Instructions
Please keep!
LED Designation Description Function
A, B, C, D I1 … I4 Status input 1 ... 4 off = “0“, green = “1“, red = error
I, K, L, M I 5 … I 8 Status input 5 ... 8 off = “0“, green = “1“, red = error (753-662...)
I, K, L, M O1 ... O4 Status output 1 ... 4 off = “0“, green = “1“, red = error (753-667...)
E Group error off = no error,
red = group error,
red 2 Hz = internal error
F Internal data bus communication green = internal data bus communication active,
red = internal data bus communication error
G PROFIsafe status off = no PROFIsafe data communication,
green = PROFIsafe data communication active,
green 1 Hz = confirmation required,
red = F parameters missing,
red 1 Hz = watchdog time exceeded,
red 2 Hz = PROFIsafe F address invalid
H Configuration off = configuration OK,
red = module selected by WAGO-I/O-CHECK,
red 1 Hz = I parameters missing,
red 2 Hz = configuration running
4 x Emergency Stop, Single-Channel
Safety Operation SIL2 / Cat. 2 / PL d
2 x Emergency Stop, Two-Channel
Safety Operation SIL3 / Cat. 4 / PL e
4 x (2 x) Interlock Monitoring, Antivalence
Safety Operation SIL3 / Cat. 4 / PL e
753-662/000-002
8 x Emergency Stop, Single-Channel, Safety Operation SIL2 / Cat. 2 / PL d (see example 753-661/000-002: Connecting Emergency Stop 5 ... 8 to Contacts T1/I5 ... T2/I8)
4 x Emergency Stop, Two-Channel, Safety Operation SIL3 / Cat. 4 / PL e (see example 753-661/000-002: Connecting Emergency Stop 3 + 4 to Contacts T1/I5/T2/I6 + T1/I7/T2/I8)
2 x Interlock Monitoring, Antivalence, Safety Operation SIL3 / Cat. 4 / PL e (see example 753-661/000-002: Connecting Safety Door 2 to Contacts T1/I5 ... T2/I8)
753-667/000-002
2 x Emergency Stop, Single-Channel, Safety Operation SIL2 / Cat. 2 / PL d (see example 753-661/000-002)
1 x Emergency Stop, Two-Channel, Safety Operation SIL3 / Cat. 4 / PL e (see example 753-661/000-002)
1 x Interlock Monitoring, Antivalence, Safety Operation SIL3 / Cat. 4 / PL e (see example 753-661/000-002)
4 x Motor, Single-Channel with Feedback (1 Switch per Motor),
Safety Operation SIL2 / Cat. 2 / PL d
2 x Motor, Two-Channel with Feedback (2 Switches per Motor),
Safety Operation SIL3 / Cat. 4 / PL e
4 x DC Motor
Safety Operation SIL3 / Cat. 4 / PL e
Connections and Indicators
Simplified diagrams
Connection examples
753-661/000-002
753-661/000-002 753-662/000-002 753-667/000-002
753-661/000-002 753-662/000-002 753-667/000-002