manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. WaterLogic
  6. •
  7. Water Dispenser
  8. •
  9. WaterLogic WL250 Operating instructions

WaterLogic WL250 Operating instructions

WL250Manual Page55‐Revision:12‐12‐2018
DISPENSINGTROUBLESHOOTINGINDEX

1. Dispensingwon'tstopwhennotholdingtheDispensingButton

2. Waterdoesnotdispensefromunit

3. SteadyDripoutofFaucet

4. Irregular/IntermittentDispensing

5. Smallamountofwaterperiodicallydispensesfromfaucetautomatically

6. LowFlowofWater–RatedServiceFlowis1.89Liters(0.5gallons)per
Minute

7. HotWaterIntermittentlyForcedThroughtheFaucet,oraDualStreamOut
oftheFaucet

8. HotWatercomingoutofboththeFaucetandtheVentHole

9. HotWaterDripoutofFaucet

10. DispensesHotandColdWateratthesametime

11. NoColdWaterAvailable

12. ColdWaterdispensesfromFaucetandVentOutletSimultaneously

13. DispenseButtonsstick

14. Run‐OnWatercontinuestodispenseoutoffaucetafterreleasingthe
dispensebutton

AlsoincludesrelatedinstructionforHotTankDescaling


WL250Manual Page56‐Revision:12‐12‐2018
1. DispensingWon’tStopwhenNotHoldingtheDispensingButton


PossibleReason Solution
Toomuchwaterpressure.
Recommend40‐60psiforthe
WL250WaterTreatment
Systemtooperateproperly.
Thecorrectinputwaterpressureiscriticaltotheperformanceof
theunittoallowsolenoidstoopen.

Checkwaterpressureattheinletbulkheadwithawaterpressure
gauge.

Additionalmethodofverificationistoturnoffwatertounitand
pressthedispensebutton.Doesthesolenoidopenwithoutwater
pressuretotheunit?Listenforsolenoidtoactivate,notbutton
“click”.

Adjustwaterpressureto40‐60psi.
BadDisplayPCB
ReplaceFrontPCB
HotandCold–P/NEN‐6085WLCPPN12‐8103
ColdOnly–P/NEN‐6086WLCPPN12‐8615
DebrisintheSolenoid InspectSolenoidfordebrisandcleanoutasneeded.
DispensingButtonStuck
DirtorForeignmaterialisfillingthegaparoundthepush‐buttons.
Inspectthepushbuttonsandcleansurroundingarea.Inspect
faucetassemblyinsidetheunitandcleanasnecessary.


WL250Manual Page57‐Revision:12‐12‐2018
2. WaterdoesnotdispensefromUnit


PossibleReason Solution
Toomuchwaterpressure.
Recommend40‐60psiforthe
WL250WaterTreatment
Systemtooperateproperly.
Thecorrectinputwaterpressureiscriticaltothe
performanceoftheunittoallowsolenoidstoopen.

Checkwaterpressureattheinletbulkheadwithawater
pressuregauge.

Additionalmethodofverificationistoturnoffwatertounit
andpressthedispensebutton.Doesthesolenoidopen
withoutwaterpressuretotheunit?Listenforsolenoidto
activate,notbutton“click”.

Adjustwaterpressureto40‐60psi.
Closedwatersupplyvalve Openthewatersupplyvalve.
Theunitisnotproperly
pluggedintoelectricaloutlet
Checkelectricaloutletconnection,orforblowncircuit
breaker.
RedHeaterandCompressor
Switchonunitisintheoff
position


TurnRedHeaterandCompressorswitchon.
I=ON


15AmpFuseBlown Replacethe15AmpFuseasneeded.
Waterispresentinthebottom
tray,causingtheleak
detectiontotrigger.

*LeakDetectionisonthe
CounterTopModelonly.
RemovetheTopCoverandFrontPanel.Tiptheunitslightly
todrain,drybottomtraycompletely.
HotandColdSolenoid
connectionsintotheDisplay
PCBareloose.
Turnpoweroff;unplugtheunitandvisuallyinspectsolenoid
connectionsintotheDisplayPCB.Verifythesolderingpoints
onconnectionsaresecureintotheboard.

RemovethePCBtoinspectthefrontoftheboard.
ExhaustedFilter Replacefiltersasneeded.


WL250Manual Page58‐Revision:12‐12‐2018

3. SteadyDripOutofFaucet

PossibleReason Solution
DebrisinSolenoid InspectSolenoidfordebrisandcleanoutasneeded.

4. Irregular/IntermittentDispensing

PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
WL250WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawaterpressure
gauge.

Additionalmethodofverificationistoturnoffwatertounitand
pressthedispensebutton.Doesthesolenoidopenwithoutwater
pressuretotheunit?Listenforsolenoidtoactivate,notbutton
“click”.

Adjustwaterpressureto40‐60psi.
Looseorbadconnectionon
theFrontDispensingPCBor
SolenoidConnector
Checkthattheyareconnectedproperlyandtightened.
Solenoid
IfboththeWaterPressureandPCBhavebeenruledout,thenitis
theSolenoid.

ReplaceSolenoid.
Dispensingbuttonisbrokenon
PCB
CheckPCBforlooseordamagedbutton.ReplacePCBas
necessary.

5. SmallAmountofWaterPeriodicallyDispensesfromFaucetAutomatically

PossibleReason Solution
ColdorHotWaterSolenoid
Valvemalfunction`
Inspectvalvecomponentsforproperfunction.Replaceas
necessary.
ObstructioninSolenoid
housingispreventingproper
sealingofcomponent
Pre‐determinewhetherwaterbeingdispensedisHot/Cold.
Isolatethewatersupply;pushtheDISPENSEbuttontoreleasethe
linepressure,andremovethecoilaffixedtotheSolenoidstem.

Removethestemfromthesolenoidhousingandallowwaterfrom
thetanktoflushoutthecontaminate(s).
WL250Manual Page59‐Revision:12‐12‐2018
6. LowFlowofWater–RatedServiceFlowis1.89Liters(0.5gallons)per
Minute


PossibleReason Solution
DetermineFlowofWater
RatedFlowRateis1.89Liters(0.5gallons)perMinute.

CheckFlowRatebydispensingintoacontainerforoneminute.
Measuretheamountofwaterthathasbeendispensed.
FeedLinestoosmall
Feedlinescanrestrictflowifrunlongdistancesfromthesupply.It
maybenecessarytoincreasethesupplyline(e.g.use3/8”feed
lineversus¼”).
Elbowsandturnsinthefeed
line Minimizeelbowsandturnsinthefeedline.
Filters
Filterswithhighpressuredropduetofoulingorjustbydesign.
Changefiltersmorefrequentlyorgotohighermicronsizefilterfor
localwaterconditions.
Restrictions
Flowpathtoensuretherearenoundiscoveredrestrictionsdueto
debrisormalfunctioningvalves,includingthesupplyvalveatthe
source.
BoosterPump Addaboosterpumptothesupplylineifthefeedisslowerthan
needed.


7. HotWaterIntermittentlyForcedOutthroughtheFaucet,oraDualStream
outoftheFaucet


PossibleReason Solution
Mineraldepositsonthe
expansionslotinsidetheHot
Tankventchamberwhich
blocksthenormalpathof
watertoexpand.
DescaletheTank.

SeeHotTankDescalingInstructionsthatareincludedfurther
belowwinthisTroubleshootSection.





WL250Manual Page60‐Revision:12‐12‐2018

8. HotWaterComingoutofFaucetVentHole


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
WL250WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawaterpressure
gauge.

Additionalmethodofverificationistoturnoffwatertounitand
pressthedispensebutton.Doesthesolenoidopenwithoutwater
pressuretotheunit?Listenforsolenoidtoactivate,notbutton
“click”.

Adjustwaterpressureto40‐60psi.
Impropertubingattachment
fromthetanktofaucetorvice
versa.
Verifytubingisconnectedproperlyfromtankoutletstocorrect
faucetattachments.
HotTankoutletholeisscaled
over.
InspectandDescaleTankasneeded.

SeeHotTankDescalingInstructionsthatareincludedfurther
belowinthisTroubleshootingSection.

SeeinstructionalvideoonthePartnerAreaoftheWaterlogic.com
websiteformoreinformation.
Expansionchamberisnot
sealedproperly. ReplacetheHotTank.


WL250Manual Page61‐Revision:12‐12‐2018
9. HotWaterDripoutofFaucet

PossibleReason Solution
SmallOutletVentHolesusceptibletoscale
buildup.
DescaleTank.

SeeHotTankDescalingInstructionsthatareincluded
furtherbelowinthisTroubleshootingSection.

SeeinstructionalvideoonthePartnerAreaofthe
Waterlogic.comwebsiteformoreinformation.

AllWaterlogicHotTankshaveabuiltinVentor
ExpansionChamberinthetopofthetankexceptfor
WL270(GF)units.

TheVentChamberallowsforexpansionofthewater
whenitisheated.

Thechambersareseparatedbyawelded‐intank
baffle.

Wateralwaysflowsintothebottomofthetankand
outthetoptothefaucet.

Thehottankoutlettubehasarestrictorinitsbase.
Thisensuresthereservoirisalwaysfullbyallowing
morewaterinthanout.

Thereisasmallholeinthesideofthetankoutlettube
thatallowsairandwatertopassintothevent
chamberasitisheated.

Waterintheventchamberissuctionedbackthrough
theoutlettubeventholewhenwaterisdispensed.

Expansionofwaterasitisheatedinthereservoirwill
pushthewateroutthefaucetwhentheoutlettube
ventholebecomespluggedwithdebrisorscale.

ThesmallOutletVentHoleissusceptibletoscalebuild
upandisakeyindicatorthatdescalingisrequired.

Itiscriticaltodescalethehottankthroughthevent
lineandoutletlineonaregularbasistopreventthis
problem.

Descalingthroughtheinletand/oroutletlinesonly
willnotcleantheventchamberandoutletventhole
properly.
WL250Manual Page62‐Revision:12‐12‐2018
10. DispensesHotandColdWaterattheSameTime


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
WL250WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawater
pressuregauge.

Additionalmethodofverificationistoturnoffwatertounit
andpressthedispensebutton.Doesthesolenoidopen
withoutwaterpressuretotheunit?Listenforsolenoidto
activate,notbutton“click”.

Adjustwaterpressureto40‐60psi.
HotorColdsolenoidisstuck
open.
RemoveTopcover.

CheckHotSolenoid:Dispensecoldwaterandvisuallyinspect
tubingforwaterflowfrombothtanks.

CheckColdSolenoid:Disconnectelbowfromoutletofcold
solenoid.Selecthotwateranddispense(quicklyreleasing
dispensingbuttontoavoidmuchwatercomingoutofcold
solenoid.

Replacesolenoidasnecessary.


WL250Manual Page63‐Revision:12‐12‐2018

11. NoColdWaterAvailable


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
WL250WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawater
pressuregauge.

Additionalmethodofverificationistoturnoffwatertounit
andpressthedispensebutton.Doesthesolenoidopen
withoutwaterpressuretotheunit?Listenforsolenoidto
activate,notbutton“click”.

Adjustwaterpressureto40‐60psi.
ClosedWaterSupplyValve OpentheWaterSupplyValve
ColdWaterSolenoidValve
malfunction Inspectthevalvecomponentsforproperfunctionality.
RedHeaterandCompressor
Switchonunitisoff.


TurnRedHeaterandCompressorSwitchon.
I=ON


Looseconnection(s)onthe
DisplayPCB
Turnpoweroff;unplugtheunitandvisuallyinspectsolenoid
connectionsintotheDisplayPCB.Verifythesolderingpoints
onconnectionsaresecureintotheboard.

RemovethePCBtoinspectthefrontoftheboard.
ExhaustedFilter Replacefiltersasneeded.

12. ColdWaterDispensesfromFaucetandVentOutletSimultaneously


PossibleReason Solution
Impropertubingattachment
fromthetanktofaucetorvice
versa
Verifytubingisconnectedproperlyfromtankoutletsto
correctfaucetattachments.
Scalehasformedinsidecold
tankoutlettube.
Removecoldwateroutlettubefromtanktofaucet.Pour
somescaleremoverintocoldtank.
ExpansionchamberinCold
Tankisnotsealedproperly. ReplaceColdTank.


WL250Manual Page64‐Revision:12‐12‐2018
13. DispenseButtonsStick


PossibleReason Solution
DirtorForeignmaterialis
fillingthegaparoundthe
push‐buttons.
Inspectthepushbuttonsandcleansurroundingarea.
Inspectfaucetassemblyinsidetheunitandcleanas
necessary.

14. RunOn–Watercontinuestodispenseoutoffaucetafterreleasingthe
dispensebutton

Reason
“RunOn”or“CarryOn”ispresentinallWaterlogicpressurefedunitswithoutoutlet
solenoids.

“RunOn”isdefinedistheamountofwaterthatcontinuestodispenseoutofthefaucetafter
releasingthedispensebutton.

RunOnexistsbecausethetankspressurizeaswaterisbeingdispensed.EveryWaterlogictank
hasanoutletrestrictortoensurethetanksremainfullofwaterandwateriscontrolledasitis
releasedtothefaucet.Theinletsolenoidcontrolsflowintothetanks.Thetankswill
“depressurize”oncethedispensebuttonisreleasedtheinletsolenoidcloses.Asmallamount
ofwaterwill“RunOn”throughthefaucetasthetankdepressurizestoatmospheric
conditions.

Typical“RunOn”is2‐3seconds.

“RunOn”canbereducedbyinstallingapressurelimitingdevice.

Theamountofinletorsupplypressuredirectlyimpactstheamountof“RunOn”asquantified
below.

WLCPLabTestingofRnOn7‐31‐2013
Pressure Pressure Time FlowRate RunOn
StaticPSI DynamicPSI 4Liters I/min Seconds
68 40 61 2.9508197 3
50 30 72 2.5 2.5
32 20 92 1.956217 2
Pressuremeasuredatinletlinetounit.Staticwithunitclosed.Dynamicwithunit
dispensingcoldwater.
Nofilterswereinstalledinunit.



WL250Manual Page65‐Revision:12‐12‐2018
HOTTANKDESCALINGINSTRUCTIONS

Thehottankrequiresremovalofmineraldeposits(descaling)onaregularbasis.Typically
descalingshouldtakeplaceevery6to12monthstopreservethelong‐termhealthofyour
unit.

Usenon‐toxiccleanersuchasScaleKleen,DEZCAL,20%CitricAcidSolution,orUndiluted
VinegarSolutiontoremovemineraldepositsasdirectedbythemanufacturerdepending
uponfiltrationandlocalwaterconditions.

Descalingisanimportantprocessthatremovescalciumdeposits,orscale,thatcanbuildup
insideatankovertime.Calciumandscaleisnon‐toxicbutleftunattendedwillhinderyour
unit’sperformance.


WARNING!PERSONALPROTECTIVEEQUIPMENTREQUIRED.Alwaysensureproper
ventilationanduserubberornitrileglovesandeyeprotectionwhenusingchemicals.
RefertoMaterialSafetyDataSheetforspecificrequirementsofeachproduct.

CAUTION!STAINLESSSTEELTANKDESCALING.
TheHotTankismadefromstainlesssteel.Ensuredescalingsolutioniscompatiblewith
stainlessandalwaysflushtheunitcompletely.Disposeinanenvironmentallysafe
manner.

MaterialsNeeded:
 PersonalProtectiveEquipment.RubberorNitrileSafetyGlovesandProtectiveEyewear
 PhillipsScrewdriver
 TemperatureGauge
 WaterPitcherorContainertocollectwaterfromthefaucet
 5‐galloncontainerordrainbasin
 CitricAcidBasedCleaner
 ¼”PlasticTubing,atleast4feetinlength,andassorted¼”quickconnectfittings
 SanitizingCartridge–anemptyWaterlogicFilterwithcartridgeremoved
 FoodColoring

1. BypassfiltersbeforestartingtheDescalingProcedure.

2. Putdescalerperdirectionsand3dropsoffoodcoloringintothedescalingcartridge.

3. Connectdescalingcartridgetotheinletwatersupplyandconnecttoinletbulkheadfitting
onthebackoftheunit.TurnonWaterSupply.

4. SelectHotWateranddepresstheMainDispensingButtonontheFrontControlPaneluntil
descalingsolution(coloredwater)comesoutofthefaucet.Containeranddrainbasicwill
berequiredtocatchwaterfromthefaucet.
WL250Manual Page66‐Revision:12‐12‐2018

5. Turnoffwatersupplyandremovesanitizingcartridgefrominletwatersupply.Reconnect
watersupplytoinletfitting.


6. AllowdescalingsolutiontoremainintheHotTankfor15minutes(lengthoftimemayvary
dependingonwaterconditions).

7. Placeapitcher,catchbasinorothercontainerunderthefaucetoftheWL250.

8. FlushtheHotTankuntilwaterrunsclear.

9. OnceclearWaterdispensesfromthefaucettheHotTankhasbeendescaled.Always
ensureunitisperformingtothecustomer’ssatisfaction.

10. ReplaceFilters.


WARNING!HOTWATER.TheWL250WaterTreatmentSystemproducesHotWaterup
to87°C(188°F).Waterabove52°C(125°F)cancausesevereburnsorscalding.Hot
watershouldbedispensedcarefullyintoinsulatedcontainertoavoidinjury.Alwaysuse
insulatedandchemicallycompatiblecontainersandletunitcooldownbeforedraining
theHotTanktoavoidinjury.

CAUTION!MUSTREPLACEHOTTANK3‐5YEARSDEPENDINGONUSAGE.TheHot
Tankanditscontrolsmustbereplacedaminimumofeverythreetofiveyearsdepending
onusagetoensureefficientanddependableoperation.


WARNING!REINSTALLALLPANELSANDCOVERS.Alwaysreinstallallpanels,protective
covers,andfastenersafterservicingequipment.Failuretodosocouldresultinsevere
personalinjuryandwillvoidthecertificationsandwarrantyoftheequipment.


Other manuals for WL250

6

Other WaterLogic Water Dispenser manuals

WaterLogic CUBE Reference guide

WaterLogic

WaterLogic CUBE Reference guide

WaterLogic WL270 Operating instructions

WaterLogic

WaterLogic WL270 Operating instructions

WaterLogic WL250 Operating instructions

WaterLogic

WaterLogic WL250 Operating instructions

WaterLogic WL2FW FIREWALL Series User manual

WaterLogic

WaterLogic WL2FW FIREWALL Series User manual

WaterLogic WL3000 User manual

WaterLogic

WaterLogic WL3000 User manual

WaterLogic WL500 - Sparkling User manual

WaterLogic

WaterLogic WL500 - Sparkling User manual

WaterLogic WL Cube Manual

WaterLogic

WaterLogic WL Cube Manual

WaterLogic WL2 Firewall User manual

WaterLogic

WaterLogic WL2 Firewall User manual

WaterLogic WL350 Operating instructions

WaterLogic

WaterLogic WL350 Operating instructions

WaterLogic WL500 - Sparkling Operating instructions

WaterLogic

WaterLogic WL500 - Sparkling Operating instructions

WaterLogic WL3 Firewall User manual

WaterLogic

WaterLogic WL3 Firewall User manual

WaterLogic WL100 User manual

WaterLogic

WaterLogic WL100 User manual

WaterLogic WL200 User manual

WaterLogic

WaterLogic WL200 User manual

WaterLogic WL350 Operating instructions

WaterLogic

WaterLogic WL350 Operating instructions

WaterLogic WL250 Manual

WaterLogic

WaterLogic WL250 Manual

WaterLogic WL7 User manual

WaterLogic

WaterLogic WL7 User manual

WaterLogic CUBE User manual

WaterLogic

WaterLogic CUBE User manual

WaterLogic WL900 User manual

WaterLogic

WaterLogic WL900 User manual

WaterLogic P2 Classe User manual

WaterLogic

WaterLogic P2 Classe User manual

WaterLogic WL350 Manual

WaterLogic

WaterLogic WL350 Manual

WaterLogic WL500 - Sparkling Manual

WaterLogic

WaterLogic WL500 - Sparkling Manual

WaterLogic WL380 Operating instructions

WaterLogic

WaterLogic WL380 Operating instructions

WaterLogic WL4 Firewall User manual

WaterLogic

WaterLogic WL4 Firewall User manual

WaterLogic WL Max User manual

WaterLogic

WaterLogic WL Max User manual

Popular Water Dispenser manuals by other brands

MOA HWD23B instruction manual

MOA

MOA HWD23B instruction manual

GE GXCF03EWWR owner's manual

GE

GE GXCF03EWWR owner's manual

Haws 2000S installation guide

Haws

Haws 2000S installation guide

Emerson InSinkErator involve Series owner's manual

Emerson

Emerson InSinkErator involve Series owner's manual

Oasis VERSAFILLER  P EBF Series installation instructions

Oasis

Oasis VERSAFILLER P EBF Series installation instructions

3M 3MWTS Series Installation and operating instructions

3M

3M 3MWTS Series Installation and operating instructions

National NC-30HN operating instructions

National

National NC-30HN operating instructions

Pentair PRF34K installation instructions

Pentair

Pentair PRF34K installation instructions

Zojirushi CD-EPC22 operating instructions

Zojirushi

Zojirushi CD-EPC22 operating instructions

SENTRY II 959TA14 Series Operation and maintenance manual

SENTRY II

SENTRY II 959TA14 Series Operation and maintenance manual

Aquverse B17A Troubleshooting instructions supplement

Aquverse

Aquverse B17A Troubleshooting instructions supplement

Pentair Riva Viridion user guide

Pentair

Pentair Riva Viridion user guide

Columbia soda TOP CS 18 Installation, operation and maintenance manual

Columbia

Columbia soda TOP CS 18 Installation, operation and maintenance manual

Nikken PIMAG WATERFALL operating manual

Nikken

Nikken PIMAG WATERFALL operating manual

Eau de Vie EDV-TT-BP Installation and operation handbook

Eau de Vie

Eau de Vie EDV-TT-BP Installation and operation handbook

Toshiba RWF-W1669BF(W) instruction manual

Toshiba

Toshiba RWF-W1669BF(W) instruction manual

Carel ROC025500N user manual

Carel

Carel ROC025500N user manual

Oasis BAEB1SHSK user guide

Oasis

Oasis BAEB1SHSK user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.