manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. WaterLogic
  6. •
  7. Water Dispenser
  8. •
  9. WaterLogic WL250 Operating instructions

WaterLogic WL250 Operating instructions

WL250Manual Page55‐Revision:12‐12‐2018
DISPENSINGTROUBLESHOOTINGINDEX

1. Dispensingwon'tstopwhennotholdingtheDispensingButton

2. Waterdoesnotdispensefromunit

3. SteadyDripoutofFaucet

4. Irregular/IntermittentDispensing

5. Smallamountofwaterperiodicallydispensesfromfaucetautomatically

6. LowFlowofWater–RatedServiceFlowis1.89Liters(0.5gallons)per
Minute

7. HotWaterIntermittentlyForcedThroughtheFaucet,oraDualStreamOut
oftheFaucet

8. HotWatercomingoutofboththeFaucetandtheVentHole

9. HotWaterDripoutofFaucet

10. DispensesHotandColdWateratthesametime

11. NoColdWaterAvailable

12. ColdWaterdispensesfromFaucetandVentOutletSimultaneously

13. DispenseButtonsstick

14. Run‐OnWatercontinuestodispenseoutoffaucetafterreleasingthe
dispensebutton

AlsoincludesrelatedinstructionforHotTankDescaling


WL250Manual Page56‐Revision:12‐12‐2018
1. DispensingWon’tStopwhenNotHoldingtheDispensingButton


PossibleReason Solution
Toomuchwaterpressure.
Recommend40‐60psiforthe
WL250WaterTreatment
Systemtooperateproperly.
Thecorrectinputwaterpressureiscriticaltotheperformanceof
theunittoallowsolenoidstoopen.

Checkwaterpressureattheinletbulkheadwithawaterpressure
gauge.

Additionalmethodofverificationistoturnoffwatertounitand
pressthedispensebutton.Doesthesolenoidopenwithoutwater
pressuretotheunit?Listenforsolenoidtoactivate,notbutton
“click”.

Adjustwaterpressureto40‐60psi.
BadDisplayPCB
ReplaceFrontPCB
HotandCold–P/NEN‐6085WLCPPN12‐8103
ColdOnly–P/NEN‐6086WLCPPN12‐8615
DebrisintheSolenoid InspectSolenoidfordebrisandcleanoutasneeded.
DispensingButtonStuck
DirtorForeignmaterialisfillingthegaparoundthepush‐buttons.
Inspectthepushbuttonsandcleansurroundingarea.Inspect
faucetassemblyinsidetheunitandcleanasnecessary.


WL250Manual Page57‐Revision:12‐12‐2018
2. WaterdoesnotdispensefromUnit


PossibleReason Solution
Toomuchwaterpressure.
Recommend40‐60psiforthe
WL250WaterTreatment
Systemtooperateproperly.
Thecorrectinputwaterpressureiscriticaltothe
performanceoftheunittoallowsolenoidstoopen.

Checkwaterpressureattheinletbulkheadwithawater
pressuregauge.

Additionalmethodofverificationistoturnoffwatertounit
andpressthedispensebutton.Doesthesolenoidopen
withoutwaterpressuretotheunit?Listenforsolenoidto
activate,notbutton“click”.

Adjustwaterpressureto40‐60psi.
Closedwatersupplyvalve Openthewatersupplyvalve.
Theunitisnotproperly
pluggedintoelectricaloutlet
Checkelectricaloutletconnection,orforblowncircuit
breaker.
RedHeaterandCompressor
Switchonunitisintheoff
position


TurnRedHeaterandCompressorswitchon.
I=ON


15AmpFuseBlown Replacethe15AmpFuseasneeded.
Waterispresentinthebottom
tray,causingtheleak
detectiontotrigger.

*LeakDetectionisonthe
CounterTopModelonly.
RemovetheTopCoverandFrontPanel.Tiptheunitslightly
todrain,drybottomtraycompletely.
HotandColdSolenoid
connectionsintotheDisplay
PCBareloose.
Turnpoweroff;unplugtheunitandvisuallyinspectsolenoid
connectionsintotheDisplayPCB.Verifythesolderingpoints
onconnectionsaresecureintotheboard.

RemovethePCBtoinspectthefrontoftheboard.
ExhaustedFilter Replacefiltersasneeded.


WL250Manual Page58‐Revision:12‐12‐2018

3. SteadyDripOutofFaucet

PossibleReason Solution
DebrisinSolenoid InspectSolenoidfordebrisandcleanoutasneeded.

4. Irregular/IntermittentDispensing

PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
WL250WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawaterpressure
gauge.

Additionalmethodofverificationistoturnoffwatertounitand
pressthedispensebutton.Doesthesolenoidopenwithoutwater
pressuretotheunit?Listenforsolenoidtoactivate,notbutton
“click”.

Adjustwaterpressureto40‐60psi.
Looseorbadconnectionon
theFrontDispensingPCBor
SolenoidConnector
Checkthattheyareconnectedproperlyandtightened.
Solenoid
IfboththeWaterPressureandPCBhavebeenruledout,thenitis
theSolenoid.

ReplaceSolenoid.
Dispensingbuttonisbrokenon
PCB
CheckPCBforlooseordamagedbutton.ReplacePCBas
necessary.

5. SmallAmountofWaterPeriodicallyDispensesfromFaucetAutomatically

PossibleReason Solution
ColdorHotWaterSolenoid
Valvemalfunction`
Inspectvalvecomponentsforproperfunction.Replaceas
necessary.
ObstructioninSolenoid
housingispreventingproper
sealingofcomponent
Pre‐determinewhetherwaterbeingdispensedisHot/Cold.
Isolatethewatersupply;pushtheDISPENSEbuttontoreleasethe
linepressure,andremovethecoilaffixedtotheSolenoidstem.

Removethestemfromthesolenoidhousingandallowwaterfrom
thetanktoflushoutthecontaminate(s).
WL250Manual Page59‐Revision:12‐12‐2018
6. LowFlowofWater–RatedServiceFlowis1.89Liters(0.5gallons)per
Minute


PossibleReason Solution
DetermineFlowofWater
RatedFlowRateis1.89Liters(0.5gallons)perMinute.

CheckFlowRatebydispensingintoacontainerforoneminute.
Measuretheamountofwaterthathasbeendispensed.
FeedLinestoosmall
Feedlinescanrestrictflowifrunlongdistancesfromthesupply.It
maybenecessarytoincreasethesupplyline(e.g.use3/8”feed
lineversus¼”).
Elbowsandturnsinthefeed
line Minimizeelbowsandturnsinthefeedline.
Filters
Filterswithhighpressuredropduetofoulingorjustbydesign.
Changefiltersmorefrequentlyorgotohighermicronsizefilterfor
localwaterconditions.
Restrictions
Flowpathtoensuretherearenoundiscoveredrestrictionsdueto
debrisormalfunctioningvalves,includingthesupplyvalveatthe
source.
BoosterPump Addaboosterpumptothesupplylineifthefeedisslowerthan
needed.


7. HotWaterIntermittentlyForcedOutthroughtheFaucet,oraDualStream
outoftheFaucet


PossibleReason Solution
Mineraldepositsonthe
expansionslotinsidetheHot
Tankventchamberwhich
blocksthenormalpathof
watertoexpand.
DescaletheTank.

SeeHotTankDescalingInstructionsthatareincludedfurther
belowwinthisTroubleshootSection.





WL250Manual Page60‐Revision:12‐12‐2018

8. HotWaterComingoutofFaucetVentHole


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
WL250WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawaterpressure
gauge.

Additionalmethodofverificationistoturnoffwatertounitand
pressthedispensebutton.Doesthesolenoidopenwithoutwater
pressuretotheunit?Listenforsolenoidtoactivate,notbutton
“click”.

Adjustwaterpressureto40‐60psi.
Impropertubingattachment
fromthetanktofaucetorvice
versa.
Verifytubingisconnectedproperlyfromtankoutletstocorrect
faucetattachments.
HotTankoutletholeisscaled
over.
InspectandDescaleTankasneeded.

SeeHotTankDescalingInstructionsthatareincludedfurther
belowinthisTroubleshootingSection.

SeeinstructionalvideoonthePartnerAreaoftheWaterlogic.com
websiteformoreinformation.
Expansionchamberisnot
sealedproperly. ReplacetheHotTank.


WL250Manual Page61‐Revision:12‐12‐2018
9. HotWaterDripoutofFaucet

PossibleReason Solution
SmallOutletVentHolesusceptibletoscale
buildup.
DescaleTank.

SeeHotTankDescalingInstructionsthatareincluded
furtherbelowinthisTroubleshootingSection.

SeeinstructionalvideoonthePartnerAreaofthe
Waterlogic.comwebsiteformoreinformation.

AllWaterlogicHotTankshaveabuiltinVentor
ExpansionChamberinthetopofthetankexceptfor
WL270(GF)units.

TheVentChamberallowsforexpansionofthewater
whenitisheated.

Thechambersareseparatedbyawelded‐intank
baffle.

Wateralwaysflowsintothebottomofthetankand
outthetoptothefaucet.

Thehottankoutlettubehasarestrictorinitsbase.
Thisensuresthereservoirisalwaysfullbyallowing
morewaterinthanout.

Thereisasmallholeinthesideofthetankoutlettube
thatallowsairandwatertopassintothevent
chamberasitisheated.

Waterintheventchamberissuctionedbackthrough
theoutlettubeventholewhenwaterisdispensed.

Expansionofwaterasitisheatedinthereservoirwill
pushthewateroutthefaucetwhentheoutlettube
ventholebecomespluggedwithdebrisorscale.

ThesmallOutletVentHoleissusceptibletoscalebuild
upandisakeyindicatorthatdescalingisrequired.

Itiscriticaltodescalethehottankthroughthevent
lineandoutletlineonaregularbasistopreventthis
problem.

Descalingthroughtheinletand/oroutletlinesonly
willnotcleantheventchamberandoutletventhole
properly.
WL250Manual Page62‐Revision:12‐12‐2018
10. DispensesHotandColdWaterattheSameTime


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
WL250WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawater
pressuregauge.

Additionalmethodofverificationistoturnoffwatertounit
andpressthedispensebutton.Doesthesolenoidopen
withoutwaterpressuretotheunit?Listenforsolenoidto
activate,notbutton“click”.

Adjustwaterpressureto40‐60psi.
HotorColdsolenoidisstuck
open.
RemoveTopcover.

CheckHotSolenoid:Dispensecoldwaterandvisuallyinspect
tubingforwaterflowfrombothtanks.

CheckColdSolenoid:Disconnectelbowfromoutletofcold
solenoid.Selecthotwateranddispense(quicklyreleasing
dispensingbuttontoavoidmuchwatercomingoutofcold
solenoid.

Replacesolenoidasnecessary.


WL250Manual Page63‐Revision:12‐12‐2018

11. NoColdWaterAvailable


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
WL250WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawater
pressuregauge.

Additionalmethodofverificationistoturnoffwatertounit
andpressthedispensebutton.Doesthesolenoidopen
withoutwaterpressuretotheunit?Listenforsolenoidto
activate,notbutton“click”.

Adjustwaterpressureto40‐60psi.
ClosedWaterSupplyValve OpentheWaterSupplyValve
ColdWaterSolenoidValve
malfunction Inspectthevalvecomponentsforproperfunctionality.
RedHeaterandCompressor
Switchonunitisoff.


TurnRedHeaterandCompressorSwitchon.
I=ON


Looseconnection(s)onthe
DisplayPCB
Turnpoweroff;unplugtheunitandvisuallyinspectsolenoid
connectionsintotheDisplayPCB.Verifythesolderingpoints
onconnectionsaresecureintotheboard.

RemovethePCBtoinspectthefrontoftheboard.
ExhaustedFilter Replacefiltersasneeded.

12. ColdWaterDispensesfromFaucetandVentOutletSimultaneously


PossibleReason Solution
Impropertubingattachment
fromthetanktofaucetorvice
versa
Verifytubingisconnectedproperlyfromtankoutletsto
correctfaucetattachments.
Scalehasformedinsidecold
tankoutlettube.
Removecoldwateroutlettubefromtanktofaucet.Pour
somescaleremoverintocoldtank.
ExpansionchamberinCold
Tankisnotsealedproperly. ReplaceColdTank.


WL250Manual Page64‐Revision:12‐12‐2018
13. DispenseButtonsStick


PossibleReason Solution
DirtorForeignmaterialis
fillingthegaparoundthe
push‐buttons.
Inspectthepushbuttonsandcleansurroundingarea.
Inspectfaucetassemblyinsidetheunitandcleanas
necessary.

14. RunOn–Watercontinuestodispenseoutoffaucetafterreleasingthe
dispensebutton

Reason
“RunOn”or“CarryOn”ispresentinallWaterlogicpressurefedunitswithoutoutlet
solenoids.

“RunOn”isdefinedistheamountofwaterthatcontinuestodispenseoutofthefaucetafter
releasingthedispensebutton.

RunOnexistsbecausethetankspressurizeaswaterisbeingdispensed.EveryWaterlogictank
hasanoutletrestrictortoensurethetanksremainfullofwaterandwateriscontrolledasitis
releasedtothefaucet.Theinletsolenoidcontrolsflowintothetanks.Thetankswill
“depressurize”oncethedispensebuttonisreleasedtheinletsolenoidcloses.Asmallamount
ofwaterwill“RunOn”throughthefaucetasthetankdepressurizestoatmospheric
conditions.

Typical“RunOn”is2‐3seconds.

“RunOn”canbereducedbyinstallingapressurelimitingdevice.

Theamountofinletorsupplypressuredirectlyimpactstheamountof“RunOn”asquantified
below.

WLCPLabTestingofRnOn7‐31‐2013
Pressure Pressure Time FlowRate RunOn
StaticPSI DynamicPSI 4Liters I/min Seconds
68 40 61 2.9508197 3
50 30 72 2.5 2.5
32 20 92 1.956217 2
Pressuremeasuredatinletlinetounit.Staticwithunitclosed.Dynamicwithunit
dispensingcoldwater.
Nofilterswereinstalledinunit.



WL250Manual Page65‐Revision:12‐12‐2018
HOTTANKDESCALINGINSTRUCTIONS

Thehottankrequiresremovalofmineraldeposits(descaling)onaregularbasis.Typically
descalingshouldtakeplaceevery6to12monthstopreservethelong‐termhealthofyour
unit.

Usenon‐toxiccleanersuchasScaleKleen,DEZCAL,20%CitricAcidSolution,orUndiluted
VinegarSolutiontoremovemineraldepositsasdirectedbythemanufacturerdepending
uponfiltrationandlocalwaterconditions.

Descalingisanimportantprocessthatremovescalciumdeposits,orscale,thatcanbuildup
insideatankovertime.Calciumandscaleisnon‐toxicbutleftunattendedwillhinderyour
unit’sperformance.


WARNING!PERSONALPROTECTIVEEQUIPMENTREQUIRED.Alwaysensureproper
ventilationanduserubberornitrileglovesandeyeprotectionwhenusingchemicals.
RefertoMaterialSafetyDataSheetforspecificrequirementsofeachproduct.

CAUTION!STAINLESSSTEELTANKDESCALING.
TheHotTankismadefromstainlesssteel.Ensuredescalingsolutioniscompatiblewith
stainlessandalwaysflushtheunitcompletely.Disposeinanenvironmentallysafe
manner.

MaterialsNeeded:
 PersonalProtectiveEquipment.RubberorNitrileSafetyGlovesandProtectiveEyewear
 PhillipsScrewdriver
 TemperatureGauge
 WaterPitcherorContainertocollectwaterfromthefaucet
 5‐galloncontainerordrainbasin
 CitricAcidBasedCleaner
 ¼”PlasticTubing,atleast4feetinlength,andassorted¼”quickconnectfittings
 SanitizingCartridge–anemptyWaterlogicFilterwithcartridgeremoved
 FoodColoring

1. BypassfiltersbeforestartingtheDescalingProcedure.

2. Putdescalerperdirectionsand3dropsoffoodcoloringintothedescalingcartridge.

3. Connectdescalingcartridgetotheinletwatersupplyandconnecttoinletbulkheadfitting
onthebackoftheunit.TurnonWaterSupply.

4. SelectHotWateranddepresstheMainDispensingButtonontheFrontControlPaneluntil
descalingsolution(coloredwater)comesoutofthefaucet.Containeranddrainbasicwill
berequiredtocatchwaterfromthefaucet.
WL250Manual Page66‐Revision:12‐12‐2018

5. Turnoffwatersupplyandremovesanitizingcartridgefrominletwatersupply.Reconnect
watersupplytoinletfitting.


6. AllowdescalingsolutiontoremainintheHotTankfor15minutes(lengthoftimemayvary
dependingonwaterconditions).

7. Placeapitcher,catchbasinorothercontainerunderthefaucetoftheWL250.

8. FlushtheHotTankuntilwaterrunsclear.

9. OnceclearWaterdispensesfromthefaucettheHotTankhasbeendescaled.Always
ensureunitisperformingtothecustomer’ssatisfaction.

10. ReplaceFilters.


WARNING!HOTWATER.TheWL250WaterTreatmentSystemproducesHotWaterup
to87°C(188°F).Waterabove52°C(125°F)cancausesevereburnsorscalding.Hot
watershouldbedispensedcarefullyintoinsulatedcontainertoavoidinjury.Alwaysuse
insulatedandchemicallycompatiblecontainersandletunitcooldownbeforedraining
theHotTanktoavoidinjury.

CAUTION!MUSTREPLACEHOTTANK3‐5YEARSDEPENDINGONUSAGE.TheHot
Tankanditscontrolsmustbereplacedaminimumofeverythreetofiveyearsdepending
onusagetoensureefficientanddependableoperation.


WARNING!REINSTALLALLPANELSANDCOVERS.Alwaysreinstallallpanels,protective
covers,andfastenersafterservicingequipment.Failuretodosocouldresultinsevere
personalinjuryandwillvoidthecertificationsandwarrantyoftheequipment.


Other manuals for WL250

6

Other WaterLogic Water Dispenser manuals

WaterLogic WL100 User manual

WaterLogic

WaterLogic WL100 User manual

WaterLogic ARAMARK User manual

WaterLogic

WaterLogic ARAMARK User manual

WaterLogic WL800 User manual

WaterLogic

WaterLogic WL800 User manual

WaterLogic CUBE Reference guide

WaterLogic

WaterLogic CUBE Reference guide

WaterLogic WL500 - Sparkling Reference guide

WaterLogic

WaterLogic WL500 - Sparkling Reference guide

WaterLogic WL500 - Sparkling Operating instructions

WaterLogic

WaterLogic WL500 - Sparkling Operating instructions

WaterLogic WL380 Operating instructions

WaterLogic

WaterLogic WL380 Operating instructions

WaterLogic WL200 Operating instructions

WaterLogic

WaterLogic WL200 Operating instructions

WaterLogic WL800 - MAX II Manual

WaterLogic

WaterLogic WL800 - MAX II Manual

WaterLogic WL2 Firewall User manual

WaterLogic

WaterLogic WL2 Firewall User manual

WaterLogic WL900 User manual

WaterLogic

WaterLogic WL900 User manual

WaterLogic WL900 Operating instructions

WaterLogic

WaterLogic WL900 Operating instructions

WaterLogic WL200 Reference guide

WaterLogic

WaterLogic WL200 Reference guide

WaterLogic WL1000GF MAX User manual

WaterLogic

WaterLogic WL1000GF MAX User manual

WaterLogic CUBE Operating instructions

WaterLogic

WaterLogic CUBE Operating instructions

WaterLogic WL2FLT Operating instructions

WaterLogic

WaterLogic WL2FLT Operating instructions

WaterLogic WL290 User manual

WaterLogic

WaterLogic WL290 User manual

WaterLogic WL250 Operating instructions

WaterLogic

WaterLogic WL250 Operating instructions

WaterLogic ICE 900 User manual

WaterLogic

WaterLogic ICE 900 User manual

WaterLogic WL500 - Sparkling Manual

WaterLogic

WaterLogic WL500 - Sparkling Manual

WaterLogic CUBE User manual

WaterLogic

WaterLogic CUBE User manual

WaterLogic WL2FW FIREWALL Series User manual

WaterLogic

WaterLogic WL2FW FIREWALL Series User manual

WaterLogic WL2000IT User manual

WaterLogic

WaterLogic WL2000IT User manual

WaterLogic WL250 Operating instructions

WaterLogic

WaterLogic WL250 Operating instructions

Popular Water Dispenser manuals by other brands

Elkay HEW1JO 2F Series Installation, care & use manual

Elkay

Elkay HEW1JO 2F Series Installation, care & use manual

Follett Symphony Plus 25 series Operation and service manual

Follett

Follett Symphony Plus 25 series Operation and service manual

Frigidaire EFWC498-BLACK instruction manual

Frigidaire

Frigidaire EFWC498-BLACK instruction manual

EcoWater Timetronic 314 User/installer handbook

EcoWater

EcoWater Timetronic 314 User/installer handbook

Elkay EZS8WS 1G Series Installation & use manual

Elkay

Elkay EZS8WS 1G Series Installation & use manual

Canature WaterGroup 185HTO owner's manual

Canature WaterGroup

Canature WaterGroup 185HTO owner's manual

aQuatell Fleck 5600SXT instructions

aQuatell

aQuatell Fleck 5600SXT instructions

UNITED AF24 owner's manual

UNITED

UNITED AF24 owner's manual

Halsey Taylor WM8 Series owner's manual

Halsey Taylor

Halsey Taylor WM8 Series owner's manual

SODAX X1-X10 user guide

SODAX

SODAX X1-X10 user guide

Hatco ATMOSPHERIC AWD-12 Series Replacement parts list

Hatco

Hatco ATMOSPHERIC AWD-12 Series Replacement parts list

SPM K-Soft Operator's manual

SPM

SPM K-Soft Operator's manual

Kärcher WPD 100 Original instructions

Kärcher

Kärcher WPD 100 Original instructions

Rainfresh 30T Installation and operation manual

Rainfresh

Rainfresh 30T Installation and operation manual

Oasis 504818C user guide

Oasis

Oasis 504818C user guide

Clover B7A Service manual

Clover

Clover B7A Service manual

Taurus ALPATEC MG10 manual

Taurus

Taurus ALPATEC MG10 manual

Viqua PRO24-100 owner's manual

Viqua

Viqua PRO24-100 owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.