manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. WaterLogic
  6. •
  7. Water Dispenser
  8. •
  9. WaterLogic WL380 Operating instructions

WaterLogic WL380 Operating instructions

WL380Manual Page42‐Revision:2‐5‐2018
DISPENSETROUBLESHOOTINGINDEX

1. Irregular / Intermittent Dispensing from One Side
2. Hot Water Intermittently Forced Out Through the Faucet, or a Dual Stream Out of the
Faucet
3. Dispensing won't stop when not holding the Dispensing Button
4. Steady Drip out of Faucet
5. Hot Water or Steam coming out of both the Faucet and the Vent Hole
6. Hot Water coming out of Faucet Vent Hole
7. Low Flow of Water
8. Hot Water Drip out of Faucet
9. Dispenses Hot and Cold Water at the same time
10. No cold water available
11. Water does not dispense from unit
12. No Water is Dispensing from One Side – Cold or Hot
13. Cold Water dispenses from Faucet and Vent Outlet Simultaneously
14. Small amount of water periodically dispenses from faucet automatically
15. Dispense Buttons Stick
16. Water Stream is at an Angle
17. Run-On - Water continues to dispense out of faucet after releasing the dispense button
 Also includes related instruction for Hot Tank Descaling 




WL380Manual Page43‐Revision:2‐5‐2018
1.Irregular/IntermittentDispensingfromOneSide


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
theWL380WaterTreatment
Systemtooperateproperly.

Checkwaterpressureattheinletbulkheadwithanaccurate
waterpressuregauge.

Additionalmethodofverificationistoturnoffwatertounitand
pressthedispensebutton.Doesthesolenoidopenwithout
waterpressuretotheunit?Listenforsolenoidtoactivate,not
button“click”.

REGULATEinputWaterPressureto40‐60psi.

Looseorbadconnectionon
theFrontDispensingPCBor
SolenoidConnector
Checkthattheyareconnectedproperlyandtightened.
Solenoid
IfboththeWaterPressureandPCBhavebeenruledout,thenitis
theSolenoid.

ReplaceSolenoid.
Dispensingbuttonisbrokenon
PCB
CheckPCBforlooseordamagedbutton.ReplacePCBas
necessary.


2.HotWaterIntermittentlyForcedOutThroughtheFaucet,oraDualStreamOutof
theFaucet

PossibleReason Solution
Mineraldepositsonthe
expansionslotinsidethehot
tankventchamberwhich
blocksthenormalpathof
watertoexpand.

DescaleHotTank

SeeHotTankDescalingInstructionsthatareincludedfurther
belowinthisTroubleshootingSection.









WL380Manual Page44‐Revision:2‐5‐2018

3.DispensingWon’tStopWhenNotHoldingtheDispensingButton


PossibleReason Solution
BadDisplayPCB ReplaceMainPCB
DebrisintheSolenoid InspectSolenoidfordebrisandcleanoutasneeded.
DamagedorFaultySolenoid ReplaceSolenoid.

4.SteadyDripOutofFaucet


PossibleReason Solution
DebrisinSolenoid InspectSolenoidfordebrisandcleanoutasneeded.



5.HotWaterorSteamComingoutofboththeFaucetandVentHole


PossibleReason Solution
Impropertubingattachment
fromtheHotTanktoFaucetor
viceversa.
CheckthatthetubingisconnectedfromHotTankOutletsto
correctFaucetattachments.Connecttubingtooutletsas
needed.



WL380Manual Page45‐Revision:2‐5‐2018
6.HotWaterComingoutofFaucetVentHole


PossibleReason Solution
Impropertubingattachmentfrom
thetanktofaucetorviceversa.
Verifytubingisconnectedproperlyfromtankoutletsto
correctfaucetattachments.
HotTankoutletholeisscaledover.
InspectandDescaleTankasneeded.

SeeHotTankDescalingInstructionsthatareincluded
furtherbelowinthisTroubleshootingSection.

SeeinstructionalvideoonthePartnerAreaofthe
Waterlogic.comwebsiteformoreinformation.
Expansionchamberisnotsealed
properly. ReplacetheHotTank.

7.LowFlowofWater–RatedServiceFlowis1.89Liters(0.5gallons)perMinute


PossibleReason Solution
DetermineFlowofWater
RatedFlowRateis1.89Liters(0.5gallons)perminute.
Checkflowratebydispensingintoacontainertomeasure
foroneminute.Measuretheamountofwaterthathas
beendispensed.
FeedLinestooSmall
Feedlinescanrestrictflowifrunlongdistancesfromthe
supply.Itmaybenecessarytoincreasethesupplyline(e.g.,
use3/8”feedlinevs.¼”.
Elbowsandturnsinthefeedline Minimizeelbowsandturnsinthefeedline.
Filters
Filterswithhighpressuredropduetofoulingorjustby
design.Changefiltersmorefrequentlyorgotohigher
micronsizefilterforlocalwaterconditions.
Restrictions
Followflowpathtoensuretherearenoundiscovered
restrictionsduetodebrisormalfunctioningvalves,including
thesupplyvalveatthesource.
BoosterPump Addaboosterpumptothesupplylineifthefeedisslower
thanneeded.


WL380Manual Page46‐Revision:2‐5‐2018

9. HotWaterDripoutofFaucet

PossibleReason Solution
SmallOutletVentHolesusceptibletoscale
buildup.
DescaleTank.

SeeHotTankDescalingInstructionsthatareincluded
furtherbelowinthisTroubleshootingSection.

SeeinstructionalvideoonthePartnerAreaofthe
Waterlogic.comwebsiteformoreinformation.

AllWaterlogicHotTankshaveabuilt‐inVentor
ExpansionChamberinthetopofthetankexceptfor
WL270(GF)units.

TheVentChamberallowsforexpansionofthewater
whenitisheated.

Thechambersareseparatedbyawelded‐intank
baffle.

WateralwaysflowsintothebottomoftheHotTank
andoutthetoptotheFaucet.

TheHotTankOutletTubehasaRestrictorinitsbase.
Thisensuresthereservoirisalwaysfullbyallowing
morewaterinthanout.

ThereisasmallholeinthesideoftheHotTankOutlet
TubethatallowsairandwatertopassintotheVent
Chamberasitisheated.

WaterintheVentChamberissuctionedbackthrough
theOutletTubeventholewhenwaterisdispensed.

ExpansionofwaterasitisheatedintheReservoirwill
pushthewateroutthefaucetwhentheoutlettube
ventholebecomespluggedwithdebrisorscale.

ThesmallOutletVentHoleissusceptibletoscalebuild
upandisakeyindicatorthatdescalingisrequired.

ItiscriticaltodescaletheHotTankthroughthevent
lineandoutletlineonaregularbasistopreventthis
problem.

Descalingthroughtheinletand/oroutletlinesonly
willnotcleantheventchamberandoutletventhole
properly.
WL380Manual Page47‐Revision:2‐5‐2018

9.DispensesHotandColdWateratthesametime


PossibleReason Solution
HotorColdsolenoidisstuck
open.
RemoveTopCover.

CheckHotSolenoid:Dispensecoldwaterandvisuallyinspecttubing
forwaterflowfrombothtanks.

CheckColdSolenoid:DisconnectElbowfromoutletofCold
Solenoid.Selecthotwateranddispense(quicklyreleasing
DispensingButtontoavoidmuchwatercomingoutofColdSolenoid.

ReplaceSolenoidasnecessary.

10.NoColdWaterAvailable


PossibleReason Solution
ClosedWaterSupplyValve OpentheWaterSupplyValve
ColdWaterSolenoidValve
malfunction Inspectthevalvecomponentsforproperfunctionality.
GreenHeater&Compressor
Switchonunitisoff.


TurnGreenHeater&CompressorSwitchon.
I=ON


Looseconnection(s)onthe
DisplayPCB
Turnpoweroff;unplugtheWL380WaterTreatmentSystemand
visuallyinspectsolenoidconnectionsintotheDisplayPCB.Verify
thesolderingpointsonconnectionsaresecureintotheboard.

RemovethePCBtoinspectthefrontoftheboard.
ExhaustedFilter Replacefiltersasneeded.


WL380Manual Page48‐Revision:2‐5‐2018

11.WaterdoesnotdispensefromUnit


PossibleReason Solution
Closedwatersupplyvalve Openthewatersupplyvalve.

Theunitisnotproperly
pluggedintoelectricaloutlet

Checkelectricaloutletconnection,orforblowncircuitbreaker.
GreenHeater&Compressor
Switchbuttononunitisinthe
offposition


TurnGreenHeater&CompressorSwitchon.
I=ON


15AmpFuseBlown Replacethe15AmpFuseasneeded.
WaterispresentintheBottom
Tray,causingtheLeak
Detectiontotrigger
RemovetheTopCoverandFrontPanel.Tiptheunitslightlyto
drain,dryBottomTraycompletely.
HotandColdSolenoid
connectionsintotheDisplace
PCBareloose.
Turnpoweroff;unplugtheWL380WaterTreatmentSystemand
visuallyinspectSolenoidconnectionsintotheDisplayPCB.Verify
thesolderingpointsonconnectionsaresecureintotheboard.

RemovethePCBtoinspectthefrontoftheboard.
ExhaustedFilter Replacefiltersasneeded.


WL380Manual Page49‐Revision:2‐5‐2018
12.NoWaterisDispensingfromOneSide–ColdorHot


PossibleReason Solution
Toomuchwaterpressure.

Recommend40to60psifor
theWL380WaterTreatment
Systemtooperateproperly.
VerifywaterpressureattheInletBulkheadwithaPressure
Regulator.

Additionalmethodofverificationistoturnoffwatertounitand
presstheDispenseButton.DoestheSolenoidopenwithoutwater
pressuretotheunit?Listenforsolenoidtoactivate,notthe
DispenseButton“click”.

Adjustwaterpressureto40‐60psi.
PCB
SwitchthehotandcoldwiresonPCB(redandblueconnections).

Ifwaternowdispensesfromtheoppositeside,thisisanindication
thatthereisaPCBproblem.

ReplacePCB
Solenoid
IfboththeWaterPressureandPCBhavebeenruledout,thenitis
theSolenoid.

ReplaceSolenoid.
See“GreenFlashingLight”
FaultCodeSectionofthis
Manual
IndicatestheFirewallUVsystemisnotdetectingadequatedoseof
UVtoensuresafewater.


13.ColdWaterDispensesfromFaucetandVentOutletSimultaneously


PossibleReason Solution
Impropertubingattachment
fromtheColdTanktoFaucet
orviceversa
VerifytubingisconnectedproperlyfromColdTankOutletsto
correctFaucetattachments.
ScalehasformedinsideCold
Tankoutlettube.
RemoveColdWaterOutletTubefromColdTanktoFaucet.Pour
somescaleremoverintoColdTank.
ExpansionchamberinCold
Tankisnotsealedproperly. ReplaceColdTank.




WL380Manual Page50‐Revision:2‐5‐2018
14.SmallAmountofWaterPeriodicallyDispensesfromFaucetAutomatically


PossibleReason Solution
ColdorHotWatersolenoid
valvemalfunction
Inspectvalvecomponentsforproperfunction.Replaceas
necessary.
Obstructioninsolenoid
housingispreventingproper
sealingofcomponent.
Pre‐determinewhetherwaterbeingdispensedishotorcold.

Isolatethewatersupply;pushtheDISPENSEbuttontoreleasethe
linepressure,andremovethecoilaffixedtothesolenoidstem.

Removethestemfromthesolenoidhousingandallowwaterfrom
thetanktoflushoutthecontaminant(s).


15.DispenseButtonsStick


PossibleReason Solution
DirtorForeignmaterialis
fillingthegaparoundthe
DispenseButtons.
InspecttheDispenseButtonsandcleansurroundingarea.Inspect
FaucetAssemblyinsidetheWL380WaterTreatmentSystemand
cleanasnecessary.


16.WaterStreamsatanAngle


Solution

RotatetheBung(BlueSilicone)andtheJGfittingsafewdegrees.

WaterFeedPressure VerifytheIncomingFeedwithaPressureRegulator.Shouldbe40‐
60psi(275‐414kPa)–UsePressureRegulator
OutgoingFlowRate
VerifytheoutgoingFlowRate.Shouldbe1.89Litersperminute(0.5
gallonsperminute)‐FirewallPurification.

Dispensewaterforoneminute–shouldmeasure1.89Liters(0.5
gallons)perminute

ChangeFlowRestrictorifneeded.
WL380Manual Page51‐Revision:2‐5‐2018
17.RunOn–Watercontinuestodispenseoutoffaucetafterreleasingthedispense
button

Reason
“RunOn”or“CarryOn”ispresentinallWaterlogicpressurefedunitswithoutoutletsolenoids.

“RunOn”isdefinedistheamountofwaterthatcontinuestodispenseoutofthefaucetafter
releasingthedispensebutton.

RunOnexistsbecausethetankspressurizeaswaterisbeingdispensed.EveryWaterlogictankhasan
outletrestrictortoensurethetanksremainfullofwaterandwateriscontrolledasitisreleasedtothe
faucet.Theinletsolenoidcontrolsflowintothetanks.Thetankswill“depressurize”oncethe
dispensebuttonisreleasedtheinletsolenoidcloses.Asmallamountofwaterwill“RunOn”through
thefaucetasthetankdepressurizestoatmosphericconditions.

Typical“RunOn”is2‐3seconds.

“RunOn”canbereducedbyinstallingapressurelimitingdevice.

Theamountofinletorsupplypressuredirectlyimpactstheamountof“RunOn”asquantifiedbelow.

WLCPLabTestingofRunon7‐31‐2013
Pressure Pressure Time FlowRate RunOn
StaticPSI DynamicPSI 4Liters I/min Seconds
68 40 61 2.9508197 3
50 30 72 2.5 2.5
32 20 92 1.956217 2
Pressuremeasuredatinletlinetounit.Staticwithunitclosed.Dynamicwithunit
dispensingcoldwater.
Nofilterswereinstalledinunit.






WL380Manual Page52‐Revision:2‐5‐2018
HOTTANKDESCALINGINSTRUCTIONS

TheHotTankrequiresremovalofmineraldeposits(descaling)onaregularbasis.Typicallydescaling
shouldtakeplaceevery6to12monthstopreservethelong‐termhealthofyourunit.

Usenon‐toxiccleanersuchasScaleKleen,DEZCAL,20%CitricAcidSolution,orUndilutedVinegar
Solutiontoremovemineraldepositsasdirectedbythemanufacturerdependinguponfiltrationand
localwaterconditions.

Descalingisanimportantprocessthatremovescalciumdeposits,orscale,thatcanbuildupinsidea
tankovertime.Calciumandscaleisnon‐toxicbutleftunattendedwillhinderyourunit’s
performance.

WARNING!PERSONALPROTECTIVEEQUIPMENTREQUIRED.Alwaysensureproperventilation
anduserubberornitrileglovesandeyeprotectionwhenusingchemicals.RefertoMaterial
SafetyDataSheetforspecificrequirementsofeachproduct.

CAUTION!STAINLESSSTEELTANKDESCALING.
TheHotTankismadefromstainlesssteel.Ensuredescalingsolutioniscompatiblewithstainless
andalwaysflushtheunitcompletely.Disposeinanenvironmentallysafemanner.

MaterialsNeeded:
 PersonalProtectiveEquipment.RubberorNitrileSafetyGlovesandProtectiveEyewear
 PhillipsScrewdriver
 TemperatureGauge
 WaterPitcherorContainertocollectwaterfromthefaucet
 19Liter(5gallon)containerordrainbasin
 CitricAcidBasedCleaner
 ¼”PlasticTubing,atleast4feetinlength,andassorted¼”quickconnectfittings
 SanitizingCartridge
 FoodColoring

1. Putdescalerperdirectionsand3dropsoffoodcoloringintothedescalingcartridge.

2. ConnectdescalingcartridgetotheinletwatersupplyandconnecttoInletBulkheadFittingonthe
backoftheWL380WaterTreatmentSystem.TurnonWaterSupply.

3. SelectHotWateranddepresstheMainDispensingButtonontheFrontControlPaneluntildescaling
solution(coloredwater)comesoutofthefaucet.Containeranddrainbasicwillberequiredto
catchwaterfromthefaucet.

4. Turnoffwatersupplyandremovesanitizingcartridgefrominletwatersupply.Reconnectwater
supplytoinletfitting.


WL380Manual Page53‐Revision:2‐5‐2018
5. AllowdescalingsolutiontoremainintheHotTankfor15minutes(lengthoftimemayvary
dependingonwaterconditions).

6. Placeapitcher,catchbasinorothercontainerunderthefaucetoftheWL380WaterTreatment
System.

7. FlushtheHotTankuntilwaterrunsclear.

8. OnceclearWaterdispensesfromthefaucettheHotTankhasbeendescaled.Alwaysensurethe
WL380WaterTreatmentSystemisperformingtothecustomer’ssatisfaction.


WARNING!HOTWATER.HOTWATER.UnitproducesHotWaterinexcessof80
o
C(175
o
F).
Waterabove52
o
C(125
o
F)cancausesevereburnsorscalding.Keepunauthorizedpeopleand
childrenawayfromtheunittoavoidaccidentaldispensingofhotwater.

CAUTION!MUSTREPLACEHOTTANK3‐5YEARSDEPENDINGONUSAGE.TheHotTankandits
controlsmustbereplacedaminimumofeverythreetofiveyearstoensureefficientand
dependableoperation.


WARNING!REINSTALLALLPANELSANDCOVERS.AlwaysreinstallallPanels,ProtectiveCovers,
andFastenersafterservicingequipment.Failuretodosocouldresultinseverepersonalinjury
andwillvoidthecertificationsandwarrantyoftheequipment.


Foradditionalinformationandupdatesvisithttp://techportal.waterlogic.com

ContactWaterlogicforassistanceorhelpfindinganauthorizedservicerepresentative.



Other manuals for WL380

3

Other WaterLogic Water Dispenser manuals

WaterLogic WL2000IT User manual

WaterLogic

WaterLogic WL2000IT User manual

WaterLogic WL350 Operating instructions

WaterLogic

WaterLogic WL350 Operating instructions

WaterLogic WL800 User manual

WaterLogic

WaterLogic WL800 User manual

WaterLogic WL100 Manual

WaterLogic

WaterLogic WL100 Manual

WaterLogic WL250 Manual

WaterLogic

WaterLogic WL250 Manual

WaterLogic WL100 User manual

WaterLogic

WaterLogic WL100 User manual

WaterLogic WL200 User manual

WaterLogic

WaterLogic WL200 User manual

WaterLogic WL900 User manual

WaterLogic

WaterLogic WL900 User manual

WaterLogic WL Cube Firewall User manual

WaterLogic

WaterLogic WL Cube Firewall User manual

WaterLogic WL350 Reference guide

WaterLogic

WaterLogic WL350 Reference guide

WaterLogic WL100 User manual

WaterLogic

WaterLogic WL100 User manual

WaterLogic WL Max User manual

WaterLogic

WaterLogic WL Max User manual

WaterLogic WL250 Operating instructions

WaterLogic

WaterLogic WL250 Operating instructions

WaterLogic WL400 Series Reference guide

WaterLogic

WaterLogic WL400 Series Reference guide

WaterLogic NIAGARA IB User manual

WaterLogic

WaterLogic NIAGARA IB User manual

WaterLogic WL290 User manual

WaterLogic

WaterLogic WL290 User manual

WaterLogic WL2FLT Operating instructions

WaterLogic

WaterLogic WL2FLT Operating instructions

WaterLogic WL290 Operating instructions

WaterLogic

WaterLogic WL290 Operating instructions

WaterLogic WL250 Operating instructions

WaterLogic

WaterLogic WL250 Operating instructions

WaterLogic WL900 User manual

WaterLogic

WaterLogic WL900 User manual

WaterLogic WL500 - Sparkling User manual

WaterLogic

WaterLogic WL500 - Sparkling User manual

WaterLogic WL Cube Manual

WaterLogic

WaterLogic WL Cube Manual

WaterLogic WL500 - Sparkling User manual

WaterLogic

WaterLogic WL500 - Sparkling User manual

WaterLogic WL 1000 GF User manual

WaterLogic

WaterLogic WL 1000 GF User manual

Popular Water Dispenser manuals by other brands

Pure H2O QUATREAU SmartTap user guide

Pure H2O

Pure H2O QUATREAU SmartTap user guide

Halsey Taylor HTV4Q-1C: HTV8Q-1C owner's manual

Halsey Taylor

Halsey Taylor HTV4Q-1C: HTV8Q-1C owner's manual

Global 761012 user manual

Global

Global 761012 user manual

Braun AquaExpress 5 manual

Braun

Braun AquaExpress 5 manual

Enviro WD60 instruction manual

Enviro

Enviro WD60 instruction manual

Watts HC-300 manual

Watts

Watts HC-300 manual

Primo Water 900139 user manual

Primo Water

Primo Water 900139 user manual

Grundfos AQtap Installation and operating instructions

Grundfos

Grundfos AQtap Installation and operating instructions

Winterhalter Gastronom RoMatik 150 operating instructions

Winterhalter Gastronom

Winterhalter Gastronom RoMatik 150 operating instructions

KineticoPRO Compact Commercial Series owner's manual

KineticoPRO

KineticoPRO Compact Commercial Series owner's manual

Kenmore 625.383760 owner's manual

Kenmore

Kenmore 625.383760 owner's manual

Halsey Taylor SCWT14WQ1K Series owner's manual

Halsey Taylor

Halsey Taylor SCWT14WQ1K Series owner's manual

Angel Water A3000 Series manual

Angel Water

Angel Water A3000 Series manual

Crystal Mountain Summit user manual

Crystal Mountain

Crystal Mountain Summit user manual

Fleck 7000SE Installer manual

Fleck

Fleck 7000SE Installer manual

Elkay EWTLA8 1C Series Installation, care & use manual

Elkay

Elkay EWTLA8 1C Series Installation, care & use manual

Pure-Pro CW-698P user manual

Pure-Pro

Pure-Pro CW-698P user manual

Clear Water M-15/O2 Installation & maintenance manual

Clear Water

Clear Water M-15/O2 Installation & maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.