Watts LFC500-FS Series Operating instructions

Series C400-FS, C500-FS, and LFC500-FS are each equipped
with an integrated flood sensor that detects excessive relief valve
discharges and triggers notification of potential flood events.
NOTICE
An add-on connection kit is required to activate the integrated
flood sensor. Without the connection kit, the flood sensor is a
passive component and will not communicate with any other de-
vice. (A retrofit sensor connection kit is also available for existing
installations. See “Add-on and Retrofit Sensor Connection Kits,”
for ordering details.)
RP/IS-A-C400/C500-FS
C400-OSY-FS
Installation, Maintenance, and Repair Manual
Colt™ Series C400-FS, C500-FS, LFC500-FS
Reduced Pressure Zone Assemblies
Reduced Pressure Detector Assemblies
21⁄2" – 10"
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information
can result in death, serious personal injury, property
damage, or damage to the equipment.
Keep this Manual for future reference.
Local building or plumbing codes may require modifications
to the information provided. You are required to consult
the local building and plumbing codes prior to instal-
lation. If the information provided here is not consistent
with local building or plumbing codes, the local codes
should be followed. This product must be installed by
a licensed contractor in accordance with local codes
and ordinances.
WARNING
!
Need for Periodic Inspection/Maintenance: This product
must be tested periodically in compliance with local codes,
but at least once per year or more as service conditions war-
rant. All products must be retested once maintenance has
been performed. Corrosive water conditions and/or unauthorized
adjustments or repair could render the product ineffective
for the service intended. Regular checking and cleaning of
the product’s internal and external components helps assure
maximum life and proper product function.
WARNING
!
This device must be tested periodically in compliance with
local codes, but at least once per year or more as service
conditions warrant. If installed on a fire sprinkler system, all
mechanical checks, such as alarm checks and backflow
preventers, should be flow tested and inspected internally in
accordance with NFPA 13 and NFPA 25.
WARNING
!
NOTICE
For Australia and New Zealand, line strainers should be installed
between the upstream shutoff valve and the inlet of the backflow
preventer.
Testing
For field testing procedure, refer to Ames installation sheets
IS-A-ATG-1 at www.amesfirewater.com.
For technical assistance, contact your local Ames representative.
NOTICE
The information contained herein is not intended to replace the
full product installation and safety information available or the
experience of a trained product installer. You are required to
thoroughly read all installation instructions and product safety
information before beginning the installation of this product.
Inquire with governing authorities for local installation
requirements.
NOTICE
Use of the integrated flood sensor does not replicate the need to
comply with all required instructions, codes, and regulations re-
lated to installation, operation, and maintenance of this product,
including the need to provide proper drainage in the event of a
discharge.
Watts®is not responsible for the failure of alerts due to
connectivity or power issues.

2
• Most field problems occur because dirt and debris are present
in the system at the time of installation and becomes trapped
in check #1. The system should be flushed before the back-
flow valve is installed. If the system is not flushed until after the
backflow valve is installed, remove both check modules from
the valve and open the inlet shutoff to allow water to flow for
a sufficient time to flush debris from the water line. If debris in
the water system continues to cause fouling, a strainer can be
installed upstream of the backflow assembly.
•
Series C400-FS, C500-FS, and LFC500-FS can be installed
in either horizontal, “N” pattern, or “Z” pattern position as long
as the backflow assembly is installed in accordance with the
direction of the flow arrow on the assembly and the local water
authority approves the installation.
•The assembly should be installed with adequate clearance
around the valve to allow for inspection, testing, and servicing. A
minimum clearance of 12" should be between the lower portion
of the assembly and the floor or grade. The valve should be
protected from freezing.
• Installing a backflow preventer in a pit or vault is not
recommended.
• Normal discharge and nuisance spitting are accommodated by
the use of an Ames air gap fitting and a fabricated indirect waste
line. Floor drains of the same size must be provided in case of
excessive discharge.
• Series C400, C500, and LFC500 backflow preventers should be
tested by a certified tester at the time of installation.
NOTICE
Assembly body should not be painted.
Installation Guidelines
Relief Valve Discharge Rates 21⁄2" – 10"
lpm gpm
1330 350
1140 300
950 250
760 200
570 150
380 100
190 50
0 0
0 20 40 60 80 psi
0 138 276 413 551 kPa
Rate of Flow
Pressure
Horizontal Installation
N Pattern Z Pattern

3
WARNING
!
Before servicing any Ames valve, it is mandatory to shut down
the water system by closing both the inlet and outlet shutoff
valves. After the shutoff valves are closed, open test cocks
No. 2, No. 3, and No. 4 to relieve pressure within the backflow
assembly.
1. After test cock No. 3 has been opened to relieve pressure,
remove the test cock from the housing. (See Figure A.)
2.
Insert a #3 screwdriver through the hole on the top of the
cover sleeve and using both hands rotate the cover sleeve
approximately a quarter turn clockwise and a quarter turn
counterclockwise to break the sleeve O-ring seals. Using the
screwdriver, slowly slide the cover sleeve to the downstream
side of the housing. (See Figure B.)
3. Remove the stainless steel check retainer from the housing.
(See Figure B.)
4. Remove the check #1 module by inserting two flat blade
screwdrivers into the slots on either side of the check module
and gently pry the check module toward the open zone.
(See Figure C.)
5.
Remove the check #2 module with the same instructions
as in step 4. (For servicing 6" checks, see the maintenance
instructions for sizes 8" to 10".)
6. To clean or inspect either check module, insert a #3 screw-
driver through the downstream side of the check module.
(See Figures D and E.) When the screwdriver is in place,
remove the E-clip and pin connecting the structural members.
(See Figure F.) The check clapper opens with no tension.
7. Thoroughly clean the seating area. The sealing disc can be
removed, if necessary, by detaching the screws connecting
the keeper plate to the clapper. Reverse and reinstall the
sealing disc if the elastomer is cut or damaged.
8.
Wash the check module and O-ring and inspect for any
damage. If damaged, reinstall new parts.
9.
After a thorough cleaning, lubricate the O-ring with an FDA
Approved lubricant, replace the pin and E-clip in the structural
members, remove the screwdriver, and reinstall the check
modules. Assemble the housing in reverse order of these
instructions.
Maintaining the Check Modules
21⁄2" – 6"
Figure A Figure B Figure C
Figure D Figure E Figure F
#2 Check
Figure D Figure E Figure F
#1 Check
Housing

4
Tool Requirements
• #4 Phillips screwdriver or 3/8" diameter rod, length sufficient to
span the diameter of the checks (See Figures A and B.)
• 1/2" – 13 x 5 fully threaded hex bolt (service bolt)
• 3/4" open end or socket wrench
NOTICE
Due to shipping, storage, and general handling, the Victaulic Coupling
for the shutoff valves may have loosened and should be retightened
during installation.
Instructions
WARNING
!
Before servicing any Ames valve, it is mandatory to shut
down the water system by closing both the inlet and outlet
shutoff valves. After the shutoff valves are closed, open test
cocks No. 2, No. 3, and No. 4 to relieve pressure within the
backflow assembly.
1. After test cock No. 3 has been opened to relieve pressure,
remove the test cock from the housing. (When repairing an
8" or 10" device, remove both Victaulic couplers from the
body. Slide the downstream Victaulic coupler gasket to the
downstream side of the housing. The upstream Victaulic
coupler gasket stays in place.)
2. Remove checks that are to be serviced.
3. Locate the service hole and thread in the service bolt by hand
until it contacts the linkage. (See Figure A.)
4. Continue to thread in service bolt with the wrench until the
service hole in the linkage is aligned with the service notches
on the spring arbors. (See Figure A.)
5. Insert the Phillips screwdriver through the arbors and service
hole of the linkage making sure that the tip of the screwdriver
extends past the ends of the arbors by a minimum of 1/4".
(See Figure B.)
6. Loosen the service bolt until the load is transferred to the
screwdriver. Continue to loosen the service bolt until there is
sufficient clearance to remove the complete spring mechanism.
7. To disconnect the linkage, remove the retaining clip and pin.
Store both items in a safe location for reinstallation.
8. To remove the spring mechanism, grasp the screwdriver at
the center and pull the complete assembly straight out and
store in a safe place.
9. Reinstall the components in reverse order of these instructions.
WARNING
!
While the spring mechanism is removed for check
servicing, never pull the screwdriver out or off the sup-
port notches on the arbors. Doing so may cause bodily
injuries.
Maintaining the Check Modules
8" – 10"
Figure B
Figure A
Service Hole

5
Servicing the Relief Valve
WARNING
!
Before to servicing the relief valve, it is mandatory to shut
down water system by closing both the inlet and outlet
shutoff valves and relieving pressure within the assembly by
opening test cocks No. 2, No. 3, and No. 4.
DO NOT REMOVE SPIDER BUSHING FOR SERVICING
1. Detach the activation module, if installed, from the flood sensor.
2.
Use a #2 Phillips screwdriver to remove the sensor from the
relief valve.
3. Disconnect the hose from the bottom cover plate to the
relief valve.
4.
An O-ring seals the relief valve body to the main housing.
Avoid tightening the connection beyond firm hand tightening.
The relief valve should be removable by unscrewing the relief
valve from the housing.
5.
Remove the cover plate of the relief valve by detaching the
four connecting screws.
6.
Remove the rubber diaphragm from the relief valve. Notice
how the diaphragm is configured so that it can be reinstalled
in the same manner. The hard rubber tab in the diaphragm fits
into a similar socket in the head of the piston. (See Figure A.)
7.
Hold the relief valve in both hands with the threaded end
up and both thumbs on the head of the piston. Push up on
the piston until the piston shaft with the attached E-clip is
exposed. Remove the E-clip. (See Figure B.)
8.
Remove the piston and spring from the relief valve housing and
thoroughly clean all parts including the diaphragm. Inspect all
rubber parts for damage; if any are damaged, replace with
new parts.
9.
Reassemble the relief valve in the reverse order of these
instructions.
Figure B
Figure A

6
Follow the requirements of each test when performed to ensure
successful installation, operation, and maintenance of the
backflow preventer.
Test No.1
Purpose: To test check valve No. 2 for tightness against
reverse flow.
Requirements: Valve must be tight against reverse flow under
all pressure differentials. Slowly open the ‘high’ valve A and the
‘vent’ valve C, and keep the ‘low’ valve B closed. Open test No.
4. Indicated pressure differential is expected to decrease slightly.
If pressure differential continues to decrease (until the vent
opens) check valve No. 2 is reported as ‘leaking.’
Test No. 2
Purpose: To test shutoff No. 2 for tightness.
Requirements: After passing test No. 1, continue to test No. 2
by closing test cock No. 2. The indicated pressure differential is
expected to decrease slightly. If pressure differential continues
to decrease (approaching ‘zero’), shutoff No. 2 is reported to be
‘leaking.’
Test No. 3
Purpose: To test check valve No. 1 for tightness.
Requirements: Valve must be tight against reverse flow under
all pressure differentials. Close ‘high’ valve A and open test cock
No. 2. Close test cock No. 4. Disconnect vent hose at test cock
No. 4. Open valves B and C, bleeding to atmosphere. Then
closing valve B restores the system to a normal static condition.
Observe the pressure differential gauge. If there is a decrease in
the indicated value, check valve No. 1 is reported as ‘leaking.’
Test No. 4
Purpose: To test operation of pressure differential relief valve.
Requirements: The pressure differential relief valve must
operate to maintain the ‘zone’ between the two check valves at
least 2 psi less than the supply pressure. Close ‘vent’ valve C.
Open ‘high’ valve A. Open the ‘low’ valve B very slowly until the
differential gauge needle starts to drop. Hold the valve at this
position and observe the gauge reading when the first discharge
is noted from the relief valve. Record this as the opening
differential pressure of the relief valve.
NOTICE
The differential gauge needle MUST drop slowly. Close test
cocks No. 2 and No. 3. Use the ‘vent’ hose to relieve pressure
from the test kit by opening valves A, B, and C. Remove all
test equipment and open shutoff No. 2.
Testing Reduced Pressure Zone Assemblies
Ball Type Test Valves
AC
B
Needle
Valve
High Hose
(Yellow)
Low Hose
(White or Red)
Vent Hose
(Blue)
Test Cock Test Cock Test Cock Test Cock
No. 1 No. 2 No. 3 No. 4

7
Replacement Parts
For repair kits and parts, refer to Backflow Prevention
Products Repair Kits & Service Parts price list
PL-A-RP-BPD found on www.amesfirewater.com.
O-ring, Inlet Coupler
Spider Bushing
Spring
Piston Assembly
Cover Screw
Relief Valve Assembly
Retainer E-Clip
Body
Diaphragm
Cover Plate
Assembly
Closure Sleeve Test Cock with O-ring
Closure Sleeve
Sleeve O-Ring
E-clip / Closure Pin
Check Disc
Sleeve O-ring and Gasket
Check Module O-ring
First Check Module
Relief Valve Second Check Module
Troubleshooting
PROBLEM CAUSE SOLUTION
Relief valve discharges water while system is not flowing Check #1 is fouled Remove and clean check #1
Relief valve does not properly close Service relief valve
Municipal water pressure is fluctuating Install check valve upstream of backflow assembly
Relief valve does not shut off properly Fouled relief valve seat Service relief valve
Incorrectly Installed diaphragm Remove diaphragm and correctly install
Damaged rubber surface on piston Replace with new piston
Damaged or plugged pressure hose Repair or replace hose

Add-on and Retrofit Sensor Connection Kits for Building Management Systems
ORDERING CODE ADD-ON/RETROFIT KIT DESCRIPTION
88009418 FP-BF-BMS-21/2-10
BMS Sensor Connection Kit
Series C400-FS, C500-FS, LFC500-FS
Sizes 2½" to 10"
Includes sensor activation module with cable, ground wire, and power adapter. Use
this kit to activate the integrated flood sensor and enable flood detection capabilities
on the relief valve of a new installation linked to a BMS controller (not included).
88009419 FP-RFK-BF-BMS-CFS-21/2-10
BMS Sensor Retrofit Connection Kit
Series C400, C500, LFC500
Sizes 2½" to 10"
Includes flood sensor, sensor activation module with cable, ground wire, and
power adapter. Use this kit to install the flood sensor and enable flood detection
capabilities on the relief valve of an existing installation linked to a BMS controller
(not included).
Add-on and Retrofit Sensor Connection Kits for Cellular Communication
ORDERING CODE ADD-ON/RETROFIT KIT DESCRIPTION
88009420 FP-BF-CFS-21/2-10
Cellular Sensor Connection Kit
Series C400-FS, C500-FS, LFC500-FS
Sizes 2½" to 10"
Includes sensor activation module with cable, Cellular Gateway with mounting kit,
ground wire, and power adapter. Use this kit to activate the integrated flood sensor
and enable flood detection capabilities on the relief valve of a new installation linked
to a cellular network to send alerts by email message, SMS text message, or
voice call.
88009421 FP-RFK-BF-CFS-21/2-10
Cellular Sensor Retrofit Connection Kit
Series C400, C500, LFC500
Sizes 2½" to 10"
Includes flood sensor, sensor activation module with cable, Cellular Gateway with
mounting kit, ground wire, and power adapter. Use this kit to install the flood sensor
and enable flood detection capabilities on the relief valve of an existing installation
linked to a cellular network to send alerts by email message, SMS text message,
or voice call.
Limited Warranty: Ames Fire & Waterworks (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date
of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO
OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO
THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special
or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from
labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control.
This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the
above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
RP/IS-A-C400/C500-FS 2303 7020349 © 2023 Watts
USA: Backflow T: (978) 689-6066 • F: (978) 975-8350 • AmesFireWater.com
USA: Control Valves T: (713) 943-0688 • F: (713) 944-9445 • AmesFireWater.com
Canada: T: (888) 208-8927 • F: (905) 481-2316 • AmesFireWater.ca
Latin America: T: (52) 55-4122-0138 • AmesFireWater.com
This manual suits for next models
2
Table of contents
Other Watts Industrial Equipment manuals

Watts
Watts 4000SS-FS Series Operating instructions

Watts
Watts 919 Series Instruction Manual

Watts
Watts SmartStream UV PWC012 User manual

Watts
Watts LF866 Series Operating instructions

Watts
Watts LF909-FS Use and care manual

Watts
Watts 994-FS Series Operating instructions

Watts
Watts 009 Series Instruction Manual

Watts
Watts AMES Colt C400 Operating instructions

Watts
Watts UR.21.S User manual

Watts
Watts OneFlow OF210-1 User manual