19
Starting with voltage ramp:
This is the most commonly used method.
The Soft-Starter imposes the voltage on the motor without any
kind of voltage or current feedback applied to the motor. This is
applied to loads with lower initial torques or quadratic torques.
This kind of control can be used as an initial working test.
Starting by current limitation:
The maximum current level is maintained during the start, being
set according to the needs of the application.
Applied to loads with higher initial torques or constant torques.
This type of control is used to adapt the start to the capacity
limits of the supply network.
P204 (1)
Loads parameters
with factory default
values
0 to 5
[ 0 ]
-
Reprograms all the parameters to the factory default values,
making P204=5.
Parameters P000, P295, P308 and P312 are not changed when
P204=5 (factory default).
P205
Selection of the
reading parameter
0 to 999
[ 1 ]
-
Selects which parameters will be shown on the display after
the Soft-Starter is energized.
The value programmed at P205 is equal to the parameter number
that will be shown on the display after it is energized.
If the programmed value corresponds to a non-existent
parameter, the adopted value will be 1=P001.
Range
[Factory Setting]
UnitParameter Description/ Notes
P204 Action
0 to 4 No function
5 Loads factory default
Table 6.4 - Loads parameters with factory default
P203
Fan Control
0 to 2
[ 2 ]
-
P203 defines the operation mode of the heatsink cooling fan.
The ventilation kit is an option. Refer to the Optional Devices
Chapter on the User Manual.
The SSW-07/SSW-08 from 17 to 30A models do not need the
ventilation kit.
When in the “fan controlled by software” mode (P203 = 2), the
fan is switched ON when the SCR’s are conducing or when the
heatsink temperature is higher than 65°C. The fan is switched
OFF when the SCR’s are not conducing and the temperature is
lower than 55°C.
Table 6.3 - Options for the fan control
P203 Action
0 The Fan is always OFF
1 The fan is always ON
2 The fan is controlled by software
P206 (3)
Auto-Reset time
0 = Inactive
1 to 1200
[ 900 ]
1s
When an error occurs, except for E04, E10, E24, E28, E3x,
E67 and E77, the Soft-Starter will reset automatically, after passing
the time given by P206.
After the auto-reset, if the same error occurs again three times
consecutively, the auto-reset function will be inhibited. If an error
appears again up to 30 seconds after the auto-reset is executed,
it is considered to be a reoccurrence,
Therefore, if an error occurs four times consecutively, this error
will continue being indicated (and the Soft-Starter will continue to
be disabled) permanently.
NOTE!
For Electronic Motor Overload and Power Overtemperature there
is a specific algorithm for the automatic reset time.