
3
FIRE HAZARD
• Donotexceedthespeciedvoltage.
• Protectthecontrolfromdirectcontactwithwater
(dripping, spraying, rain, etc.).
• Labelallwiresbeforedisconnectionwhenservicing
controls. Wiring errors can cause improper and
dangerous operation.
• Routeandsecurewiringawayfromame.
SHOCK HAZARD
• Disconnectelectricpowerbeforeservicing.
• Ensureproperearthgroundingofappliance.
• Ensureproperconnectionoflineneutralandline
hot wires.
EXPLOSION HAZARD
• Shutoffmaingastoapplianceuntilinstallationis
complete.
Donotshortoutterminalsongasvalveorprimary
control. Short or incorrect wiring may damage
the thermostat.
Donotshortoutterminalsongasvalveorprimary
control. Short of incorrect wiring may damage
the thermostat.
The 50T35 has only one serviceable part–an automotive
type fuse, which protects the low voltage transformer
from damage if its output is short-circuited. If the fuse
has opened up, remove whatever caused the short circuit
and replace the fuse with only a 3 Amp automotive type
fuse. If the fuse is not the cause of the control’s problem,
replace the entire 50T35 control.There are no other user
serviceable parts.
Remove both access panels.
For GMP & GMPV series units, cut the white jumper wire
between pins 4 & 7 of the 9-pin connector.
For GMPN & GMN series units, DO NOT cut the white
jumper wire.
Remove the edgecard connector and other wires from
the existing module. Discard the thermostat wires
removed from the board (R, W & G).
Remove the existing HSI module.Care should be exercised
as not to damage the nylon standoffs.
Install the 50T35-743 module.
Reconnect the edgecard connector making sure of good
contact.
Push the 9-pin connector into the HSI module. It can go
in only one way. DO NOT force.
Reconnect the supplied thermostat wires.
Remove the red wire from the 24 volt side of the secondary
side of the transformer and discard.
Remove the blue ground wire from the transformer. DO
NOT discard.
Remove the blue wire from the transformer and discard.
Connect the red wire from the 9 pin connector on to “24
volt” of the secondary side of the transformer.
Connect the blue wire from the 9-pin connector to
“Common” terminal of the secondary side of the
transformer. This wire has a piggy back terminal.
Connect the blue ground wire, which was previously
removed, also to the “Common” terminal of the
transformer.
Replace the access panels.
Restore gas and electrical power to the furnace.
Verify the sequence of operation as noted in the furnace
manufacturer’s Installation & Operating Instructions.
MOUNTING AND WIRING
All wiring should be installed according to local and national
electrical codes and ordinances.
The control must be secured to an area that will experience
a minimum of vibration and remain below the maximum
ambient temperature rating of 175°F. The control is
approved for minimum ambient temperatures of -40°F.
Any orientation is acceptable.
Refer to the wiring diagram and wiring table when
connecting the 50T35 control to other components of
the system.
UL approved, 105°C rated 18 gauge, stranded, 2/64” thick
insulation wire is recommended for all low voltage safety
circuit connections.
UL approved 105°C rated 16 gauge min., stranded, 4/64”
thick insulation wire is recommended for all line voltage
connections.
Follow the appliance manufacturer’s recommended
installation or service instructions.
INSTALLATION
Black
White
24 v. Red
Com. Blue
GND. Blue
TRANSFORMER
115v. Supply