WIKA DIH50-F User manual

D
GB
Operating instructions
Betriebsanleitung
Field display models DIH50-F,
DIH50-I, DIH50-S, DIH52-F, DIH52-I, DIH52-S
Field indicator for current loops with HART®communication
Models DIH50, DIH52, DIH62
Feldanzeige für Stromschleifen mit HART®-Kommunikation
Typen DIH50, DIH52, DIH62
Field display
models DIH62-I,
DIH62-S

D
GB
2WIKA operating instructions models DIH50, DIH52, DIH62
14008548.03 05/2013 GB/D
© 2011 WIKA Alexander Wiegand SE & Co. KG
All rights reserved. / Alle Rechte vorbehalten.
WIKA®is a registered trademark in various countries.
WIKA®ist eine geschützte Marke in verschiedenen Ländern.
Prior to starting any work, read the operating instructions!
Keep for later use!
Vor Beginn aller Arbeiten Betriebsanleitung lesen!
Zum späteren Gebrauch aufbewahren!
Operating instructions models DIH50, DIH52, DIH62
Page 3 - 36
Betriebsanleitung Typen DIH50, DIH52, DIH62
Seite 37 - 65

WIKA operating instructions models DIH50, DIH52, DIH62 3
GB
14008548.03 05/2013 GB/D
1. General information 4
2. Safety 5
3. Specications 10
4. Design and function 11
5. Transport, packaging and storage 14
6. Commissioning, operation 14
1
7. Electrical connection 17
8. Menu guidance 20
9. Information on mounting and operation in hazardous areas 25
10. Maintenance and cleaning 28
11. Faults 29
12. Dismounting, return and disposal 30
Appendix 1: EC declaration of conformity 31
Appendix 2: FM/CSA installation drawing 32
Appendix 3: ATEX/IECEx installation drawing 33
Appendix 4: Manufacturer's statement 36
Contents
Contents
Declarations of conformity can be found online at www.wika.com.

4WIKA operating instructions models DIH50, DIH52, DIH62
GB
14008548.03 05/2013 GB/D
1. General information
■
The eld indicators described in the operating instructions have been designed and
manufactured using state-of-the-art technology. All components are subject to stringent
quality and environmental criteria during production. Our management systems are
certied to ISO 9001 and ISO 14001.
■
These operating instructions contain important information on handling the instrument.
Working safely requires that all safety instructions and work instructions are observed.
■
Observe the relevant local accident prevention regulations and general safety
regulations for the instrument‘s range of use.
■
The operating instructions are part of the product and must be kept in the immediate
vicinity of the instrument and readily accessible to skilled personnel at any time.
■
Skilled personnel must have carefully read and understood the operating instructions,
prior to beginning any work.
■
The manufacturer‘s liability is void in the case of any damage caused by using the
product contrary to its intended use, non-compliance with these operating instructions,
assignment of insuciently qualied skilled personnel or unauthorised modications to
the instrument.
■
The general terms and conditions contained in the sales documentation shall apply.
■
Subject to technical modications.
■
Further information:
- Internet address: www.wika.de / www.wika.com
- Relevant data sheet: AC 80.10
- Application consultant: Tel.: (+49) 9372/132-0
Fax: (+49) 9372/132-406
E-mail: info@wika.com
Explanation of symbols
WARNING!
... indicates a potentially dangerous situation which can result in serious injury or
death if not avoided.
CAUTION!
... indicates a potentially dangerous situation which can result in light injuries or
damage to the equipment or the environment if not avoided.
1. General information

WIKA operating instructions models DIH50, DIH52, DIH62 5
GB
14008548.03 05/2013 GB/D
Information
… points out useful tips, recommendations and information for ecient and
trouble-free operation.
DANGER!
...identies hazards caused by electric power. Should the safety instructions not
be observed, there is a risk of serious or fatal injury.
WARNING!
... indicates a potentially dangerous situation in the hazardous area that can
result in serious injury or death, if not avoided.
2. Safety
WARNING!
Before mounting, commissioning and operation, make sure that the display is
suitable for the application.
Non-observance can result in serious injury and/or damage to the equipment.
WARNING!
This is protection class 3 equipment for connection at low voltages, which
are separated from the power supply or voltage by greater than AC 50 V or
DC 120 V. Preferably, a connection to an SELV or PELV circuit is recommended;
alternatively protective measures from HD 60346-4-41 (DIN VDE 0100-410).
Alternatively for North America:
The connection can be made in line with "Class 2 Circuits" or "Class 2 Power
Units" in accordance with CEC (Canadian Electrical Code) or NEC (National
Electrical Code).
Further important safety instructions can be found in the individual chapters of
these operating instructions.
2.1 Intended use
The eld indicators models DIH50, DIH52 and DIH62 are used for converting an analogue
current signal (4 … 20 mA) into an indication of the corresponding measured value and are
intended for mounting in the eld.
They comprise a display and operating unit without power supply for looping in 4 … 20 mA/
HART®circuits.
1. General information / 2. Safety

6WIKA operating instructions models DIH50, DIH52, DIH62
GB
14008548.03 05/2013 GB/D
The instrument has been designed and built solely for the intended use described here,
and may only be used accordingly.
The technical specications contained in these operating instructions must be observed.
Improper handling or operation of the instrument outside of its technical specications
requires the instrument to be taken out of service immediately and inspected by an
authorised WIKA service engineer.
If the instrument is moved from a cold into a warm environment, the formation of
condensation may result in the instrument malfunctioning. Before putting it back into
operation, wait for the instrument temperature and the room temperature to equalise.
The manufacturer shall not be liable for claims of any type based on operation contrary to
the intended use.
2.2 Personnel qualication
WARNING!
Risk of injury if qualication is insucient!
Improper handling can result in considerable injury and damage to equipment.
■
The activities described in these operating instructions may only be carried
out by skilled personnel who have the qualications described below.
■
Keep unqualied personnel away from hazardous areas.
Skilled personnel
Skilled personnel are understood to be personnel who, based on their technical training,
knowledge of measurement and control technology and on their experience and
knowledge of country-specic regulations, current standards and directives, are capable of
carrying out the work described and independently recognising potential hazards.
Special operating conditions require further appropriate knowledge, e.g. of aggressive
media.
2. Safety

WIKA operating instructions models DIH50, DIH52, DIH62 7
GB
14008548.03 05/2013 GB/D
2.3 Additional safety instructions for instruments per ATEX
WARNING!
Non-observance of these instructions and their contents may result in the loss
of explosion protection.
WARNING!
Do not use eld indicators with any damage to the exterior!
CAUTION!
■
Repairs are strictly prohibited.
■
Do not use displays presenting externally visible damage.
■
Observe the instructions for mounting and operation as well as the require-
ments for the use of the devices in hazardous areas.
2.4 Special hazards
WARNING!
Observe the information given in the applicable type examination certicate and
the relevant country-specic regulations for installation and use in hazardous
areas (e.g. EN/IEC 60079-14, NEC, CEC). Non-observance can result in serious
injury and/or damage to the equipment.
For further important safety instructions for instruments with ATEX approval, see
chapter 9 "Information on mounting and operation in hazardous areas".
WARNING!
For hazardous media such as oxygen, acetylene, ammable or toxic gases or
liquids, and refrigeration plants, compressors, etc., in addition to all standard
regulations, the appropriate existing codes or regulations must also be followed.
WARNING!
To ensure safe working on the instrument, the operating company must ensure
■
that suitable rst-aid equipment is available and aid is provided whenever
required,
■
that the operating personnel are regularly instructed in all topics regarding
work safety, rst aid and environmental protection, and know the operating
instructions, in particular the section on safety instructions.
2. Safety

8WIKA operating instructions models DIH50, DIH52, DIH62
GB
14008548.03 05/2013 GB/D
WARNING!
When working during a running process operation, measures to prevent
electrostatic discharge from the connecting terminals should be taken, as a
discharge could lead to temporary corruption of the measured value.
DANGER!
Danger of death caused by electric current
Upon contact with live parts, there is a direct danger of death.
■
The instrument may only be installed and mounted by skilled personnel.
■
Operation using a defective power supply unit (e.g. short circuit from the
mains voltage to the output voltage) can result in life-threatening voltages at
the instrument!
WARNING!
Residual media in the dismounted instrument can result in a risk to persons, the
environment and equipment. Take sucient precautionary measures.
2.5 Labelling, safety marks
■
Product label for whole instrument
2. Safety
Year of manufactureModel
Approval number

WIKA operating instructions models DIH50, DIH52, DIH62 9
GB
14008548.03 05/2013 GB/D
Explanation of symbols
Before mounting and commissioning the instrument, ensure you read
the operating instructions!
CSA, Canadian Standard Association®
The instrument has been inspected and certied by CSA International.
Instruments bearing this mark comply with the applicable Canadian
standards on safety (including explosion protection).
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant European directives.
ATEX European Explosion Protection Directive
(Atmosphère = AT, explosible = EX)
Instruments bearing this mark comply with the requirements of the European
directive 94/9/EC (ATEX) on explosion protection.
FM, Factory Mutual
The instrument was inspected and certied by FM Approvals. Instruments
bearing this mark comply with the applicable US standards on safety (including
explosion protection).
2. Safety
■
Product labels for indicator module
Year of manufacture
Model
Approval number

10 WIKA operating instructions models DIH50, DIH52, DIH62
GB
14008548.03 05/2013 GB/D
3. Specications
Specications Models DIH50 Models DIH52, DIH62
Display
■
Principle LCD, rotatable in 10° steps
■
Measured value 7-segment LCD, 5-digit, character size 9 mm
■
Bar graph 20-segment LCD
■
Information line 14-segment LCD, 6-digit, character size 5.5 mm
■
Status indicators : HART®mode (signalling of HART® parameter adoption)
: Unit lock
:Warnings or error messages
■
Indication range -9999 ... 99999
Measuring rate 4/s
Accuracy
±0.1 % of the measuring span
±0.05 % of the measuring span
Temperature coecient
±0.1 % of the measuring span/10 K
Permitted current carrying
capacity
100 mA
Voltage drop < DC 3 V (< DC 2 V at 20 mA); supply via current loop
HART®functionality
■
Access control - Secondary master
■
Automatically set
parameters
Unit, measuring range
■
Available commands -
Unit, measuring range start/end, format, zero
point, span, damping, polling address
■
Identied commands Generic mode:
1, 15, 35, 44
Generic mode:
0, 1, 6, 15, 34, 35, 36, 37, 44
■
Multidrop not supported
Measured values are automatically taken
from the HART®digital data and displayed
Permissible
■
Ambient temperature
-20 ... +85 °C -20 ... +70 °C
■
Vibration resistance
3 g per EN 60068-2-6
■
Shock resistance 30 g per EN 60068-2-27
CE conformity
■
EMC directive
2004/108/EC, EN 61326 emission (group 1, class B) and interference im-
munity (industrial application)
Field case Model DIH50, DIH52 Model DIH62
Material Aluminium, stainless steel;
window in polycarbonate Aluminium, plastic, stainless steel;
window from polycarbonate
Colour Aluminium: night blue, RAL 5022
Stainless steel: silver Aluminium, plastic: night blue, RAL 5022
Stainless steel: silver
Cable glands 3 x M20 x 1.5 or 3 x ½ NPT 2 x M20 x 1.5 or 2 x ½ NPT
Ingress protection IP 66
Weight Aluminium: approx. 1.5 kg
Stainless steel: approx. 3.7 kg
Dimensions see drawing
3. Specications
♥

WIKA operating instructions models DIH50, DIH52, DIH62 11
GB
14008548.03 05/2013 GB/D
Basic module Models DIH50-Z, DIH50-B, DIH52-Z, DIH52-B, DIH62-Z, DIH62-B
Material Polycarbonate
Weight approx. 80 g
Dimensions see drawing
For further specications see WIKA data sheet AC 80.10 and the order documentation.
For further important safety instructions for operation in hazardous areas, see
chapter 9 "Information on mounting and operation in hazardous areas".
4. Design and function
4.1 Description
The eld indicators model DIHxx are external display and operating units without separate
power supply for 4 … 20 mA/HART®sensors.The instruments are used for measured
value display and operation remote from the measuring point.They are looped anywhere
in the 4 … 20 mA signal line and measure the current in the current loop. At the same time,
they read and display the measured values with unit via the HART®signal.
The eld indicators are powered directly from the 4 ... 20 mA current loop, with a resultant
voltage drop of less than 3 V.
The eld indicators meet the requirements of:
■
Explosion protection (depending on the version)
■
Electromagnetic compatibility in accordance with DIN EN 61326 and NAMUR
recommendation NE21
Versions
Model DIHxx-ZBasic module without eld case, no Ex protection
Model DIHxx-BBasic module without eld case, Ex protection (intrinsically safe)
Model DIHxx-SField indicator, no Ex protection (standard)
Model DIH5x-FField indicator, Ex protection (ameproof enclosure)
Model DIHxx-IField indicator, Ex protection (intrinsically safe)
Model DIHx0HART® slave (standard)
Model DIHx2HART®master
3. Specications / 4. Design and function

12 WIKA operating instructions models DIH50, DIH52, DIH62
GB
14008548.03 05/2013 GB/D
4.1.1 Basic module (DIH50-B, DIH50-Z, DIH52-B, DIH52-Z)
The basic modules comprise a mounting adapter with two integrated connection terminals
and connecting cables, as well as a display unit including the display and the electronics.
Both parts are connected via a cable with plug-in coupling. Depending on their design, the
basic modules can be mounted in dierent cases or thermometer connection heads.
1920741.01
Use cases suitable for eld mounting which comply with the valid regulations and
requirements. In particular, observe the ambient conditions dened in chapter 3
"Specications" and the requirements dened in chapter 9 "Information on mounting and
operation in hazardous areas".
4.1.2 Field indicators (DIH5x-S, DIH5x-I, DIH5x-F, DIH62-S, DIH62-I)
The eld indicators comprise a case with integrated display and operation module and a
terminal insert with two terminal blocks.
■
Field indicator, models DIH50, DIH52 (aluminium, stainless steel)
1556707.01
4. Design and function

WIKA operating instructions models DIH50, DIH52, DIH62 13
GB
14008548.03 05/2013 GB/D
■
Field indicator model DIH62
4.2 Operation in safety-related applications
The eld indicators models DIH50, DIH52 are suitable for use in safety-
related applications (required characteristics see Appendix 4 "Manufacturer's
statement").
4.3 Scope of delivery
Cross-check the scope of delivery with the delivery note.
4. Design and function
Single chamber case,
deep-drawn stainless steel
Single chamber case,
plastic
Single chamber case,
aluminium or cast stainless steel
02231961 02231918
02231993

14 WIKA operating instructions models DIH50, DIH52, DIH62
GB
14008548.03 05/2013 GB/D
5. Transport, packaging and storage
5.1 Transport
Check the instrument for any damage that may have been caused by transport.
Obvious damage must be reported immediately.
5.2 Packaging
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport (e.g. change in
installation site, sending for repair).
5.3 Storage
Permissible conditions at the place of storage:
■
Storage temperature: -40 ... +85 °C
■
Humidity: 35 ... 85 % relative humidity (without condensation)
Avoid exposure to the following factors:
■
Direct sunlight or proximity to hot objects
■
Mechanical vibration, mechanical shock (putting it down hard)
■
Soot, vapour, dust and corrosive gases
6. Commissioning, operation
In hazardous areas, only use eld indicators that are approved for those
hazardous areas.The approval is marked on the product label.
6.1 Operating modes
The following operating modes are possible:
■
HART® slave / basic mode (4 ... 20 mA)
■
HART® master / basic mode / multidrop (models DIH52, DIH62)
6.1.1 Operating mode: HART®slave (models DIH50, DIH52, DIH62)
The digital indicators powered via the same current loop as the corresponding transmitters
monitor permanently the HART®communication. When modifying the unit or measuring
range of the connected transmitter, the unit of the digital indicator and the corresponding
indication range are adapted automatically.
However, it is required that the unit set in the transmitter is also set in the devices.
5. Transport, packaging and storage / 6. Commissioning, operation

WIKA operating instructions models DIH50, DIH52, DIH62 15
GB
14008548.03 05/2013 GB/D
A ashing ♥ symbol is shown on the display when a HART®communication takes place for
the rst time and the digital indicators are thus switched to the HART® mode. The ♥ symbol
is displayed permanently when the HART®communication is terminated and the digital
indicator is congured according to the measuring range and the unit of the connected
transmitter.
After the power supply was interrupted or the digital indicator was set manually, the ♥
symbol is no longer displayed.
During operation in the basic mode, the ♥ symbol is not displayed.
CAUTION!
The instruments react only to the HART®standard commands 15 and 35. If
a connected HART® transmitter is congured by means of other commands,
automatic setting is not possible!
The HART®function, i.e. the automatic adaptation of the display to the
congured data of the transmitter, requires a HART®communication between
the transmitter and the HART® software (e.g. WIKA_T32) or between the
transmitter and the eld communicator (e.g. FC375/FC475, MFC4150 etc.).
6.1.2 Operating mode: HART®master (models DIH52, DIH62)
The master mode enables the modication of the measuring range, the unit, the format,
the damping and the polling address of the connected HART®transmitter. Further
modications to the conguration of the transmitter (e.g. selection of the sensor) are not
possible.
During the starting procedure, the eld indicators try to contact the connected HART®
transmitter in the master mode and to apply its settings (unit and measuring range). During
the connection establishment, the status line shows the message "Connecting HART®".
When a HART®sensor is detected, the HART® symbol is displayed. The eld indicator
switches to the HART®mode and starts operation using the settings received from the
transmitter. This procedure is repeated whenever the power supply is switched on.
When pressing any key during the starting process or the device has not detected any
HART® transmitter during approx. 70 seconds, the digital indicator switches to the basic
mode and starts operation on the basis of the factory settings.
6. Commissioning, operation

16 WIKA operating instructions models DIH50, DIH52, DIH62
GB
14008548.03 05/2013 GB/D
6.1.3 Operating mode: Multidrop (models DIH52, DIH62)
In this specially dened operating state for HART® transmitters, the current signal is rmly
set to 4 mA and the measuring information is transmitted via the HART®communication
to the control room.To enable the displaying of the measured value of a transmitter, the
address of the desired transmitter must be set in the "Address" menu item.
If the HART® address is modied during operation, the establishment of a new connection
is started during which, however, the sensor must respond immediately in order to
complete the connection establishment.
The digital indicators show the measured values of the primary variable transmitted via
HART®to the control room.The display is passive, i.e. the transmission of the measured
values must be requested by the control room.The devices function as secondary master
with respect to the sensor during the parameterisation.
6.1.4 Operating mode: Basic mode, 4 ... 20 mA (models DIH50, DIH52, DIH62)
In the basic mode, all settings of the digital indicator must be carried out manually by
means of the front-side keys.
To navigate in the menu levels, four keys with the following functions are available:
▲ (UP) One menu item up
▼ (DOWN) One menu item down
OK Calls the programming menu
ESC Exits the programming menu
- Back to the previous menu level in the menu guidance
- Return from the edit function without saving the modication
see also chapter 8 "Menu guidance"
6.2 User interface
6. Commissioning, operation
Status data
Operating keys
Unit line, info line
Bar graph
Measured value
Models DIH50, DIH52 Model DIH62

WIKA operating instructions models DIH50, DIH52, DIH62 17
GB
14008548.03 05/2013 GB/D
7. Electrical connection
WARNING!
Observe the safety-relevant maximum values for the connection of the power
supply and the sensors dened in chapter 9.1 "Model overview and their
approvals".
When working on the eld indicators (e.g. installation/removal, maintenance work) take
measures to prevent electrostatic discharge from the terminals.
WARNING!
Carry out mounting work only with power disconnected!
Use the recommended cables and tighten the cable gland. Lead the connecting cable
downward before of the cable gland in order to provide additional protection of the device
against penetration of liquids. Rain water and condensed water can thus drip.
The device is connected by means of a commercially available two-wire cable without
screen. If electromagnetic interference exceeding the test values of EN 61326 for industrial
areas is to be expected or the HART®multidrop mode is used, a screened cable must
be used. Use cables with round cross section. An outside diameter of cable of 5 ... 9 mm
(0.2 … 0.35 inch) guarantees the tightness of the cable gland. When using other diameters
or cross sections, the gasket must be replaced or a suitable cable gland must be used.
Connect the cable screen on both sides to earth potential if a screened cable is required.
Connect the screen in the sensor directly to the internal earth terminal.The external earth
terminal of the case must be connected with low impedance to the equipotential bonding.
CAUTION!
If equipotential bonding currents are to be expected, a ceramic capacitor (e.g.
1 nF, 1,500 V) must be used for the connection on the evaluation side. The
low-frequency equipotential bonding currents are thus suppressed, but the high-
frequency interference signals remain.
7. Electrical connection

18 WIKA operating instructions models DIH50, DIH52, DIH62
GB
14008548.03 05/2013 GB/D
7.1 Field indicators models DIH50, DIH52
Open the case cover, push one of the two black fastening clips backwards and pull the
display module upwards.The power supply is connected at the front via the Philips screws
of the display module. Connect the positive pole of the power supply to the terminal marked
with ⊕ and the negative pole of the power supply to the terminal marked with ⊖.
The signal line of the transmitter is to be connected to the terminal blocks inside the eld
case. To do so, connect the positive pole of the signal line to the terminal marked with ⊕
(red cable) and the negative pole of the signal line to the terminal marked with ⊖ (black
cable).
With exible leads we recommend the use of crimped
connector sleeves.
The integrated reverse polarity protection (wrong polarity
on the terminals ⊕ and ⊖) prevents the digital indicator
from damage.
The following maximum values are applicable:
without explosion protection: 42 V
with explosion protection: 30 V
The connected wires must be checked to ensure they are connected properly. Only
well-secured wires can guarantee a fault-free operation.
Recommended tools for terminal screws:
Model Screwdriver Tightening torque
DIH50,
DIH52
Cross head ('Pozidriv' tip)
size 2 (ISO 8764)
0.4 Nm
7.2 Field indicator model DIH62
Open the case cover and remove the display and operation module by slightly turning it to
the left. Loosen the cable gland. Strip the signal lines approx. 10 cm and strip the insulation
of the wire ends approx. 1 cm. Connect the wire ends to the terminals according to the
connection diagram.
7. Electrical connection
Non-hazardous area Ex area
black
spring-loaded
push terminals
Voltage supply
Load
Transmitter
DIH50, DIH52
red

WIKA operating instructions models DIH50, DIH52, DIH62 19
GB
14008548.03 05/2013 GB/D
Note:
Fixed wires as well as exible wires with end splices are inserted directly into the terminal
openings. In the case of exible wires without end splice, press with a slotted screwdriver
the terminal to release the terminal opening. By loosening the slotted screwdriver, the
terminals are closed again.
Check the correct t by slight pulling.
Connect the screen to the internal earth terminal and the external earth terminal to the
equipotential bonding.
Put on the display and operation module and turn slightly to the right.
Tighten the cable gland and mount the case cover.
Note:
The terminal block is pluggable and can be pulled o from the electronics.
To do so, lift the terminal block using a small screwdriver and pull it out.
When plugging it again, it must engage with an audible click.
CAUTION!
When connecting an EN/IEC certied transmitter, please observe the
corresponding operating instructions and the requirements relating to the
transmitter.
7. Electrical connection
1 Connection of the transmitter: Connect the positive pole of the transmitter to the terminal marked with
⊕ (1) and the negative pole of the transmitter to the terminal marked with ⊖ (2).
2 Connection of the voltage supply: Connect the positive pole of the power supply to the terminal
marked with ⊕ (3) and the negative pole of the power supply to the terminal marked with ⊖ (4).
3 Connection of the display module: Put the display module connector accurately (coded!) on the
mating connector and press it down.
Transmitter
Voltage supply
Non-hazardous area Ex area

20 WIKA operating instructions models DIH50, DIH52, DIH62
GB
14008548.03 05/2013 GB/D
8. Menu guidance
8. Menu guidance
Main menu Submenu 1 Submenu 2
Measurement
Display
Conguration
Unit
Measuring range start
Measuring range end
Measuring range format
Unit
Unit lock
Display format
Filter
Alarm
Min/Max memory
Language
Contrast
Reset
User unit
Min. failure message
Max. failure message
Firmware version
on/o
Low alarm
High alarm
delete
display yes/no
Span
Zero
Damping
Adress
This manual suits for next models
7
Table of contents
Other WIKA Measuring Instrument manuals

WIKA
WIKA air2guide A2G-05 User manual

WIKA
WIKA 232.50.100 User manual

WIKA
WIKA 3 Series User manual

WIKA
WIKA CPH62I0-S1 User manual

WIKA
WIKA DG-05 User manual

WIKA
WIKA PG23HP Series User manual

WIKA
WIKA IPT-2 Series User manual

WIKA
WIKA FLC-UFL Series User manual

WIKA
WIKA 7 Series User manual

WIKA
WIKA PGU23.100 User manual