
HD4/R - HD4/R-SEC - HD4/RE-SEC - INSTALLATION AND OPERATING INSTRUCTIONS18
—
7. Installation
7.7 Earthing
Earth fixed version circuit breakers by means of
the special screw marked with the relative
symbol. Clean and degrease the area around the
screw corresponding to a diameter of about
30 mm. Use a conductor (busbar or cord) with a
cross-section conforming to the Standards in
force.
When the assembly is completed, cover the joint
with vaseline grease.
7.6.2 Maximum dimensions of the connections
For fixed version HD4/R and HD4/RE circuit
breakers, the connections must be shaped and
installed in accordance with the indications given
in figures 14, 15, 16 and 25, and the distances
indicated.
7.6.3 Surface treatment of the connections
The connections can be made of bare copper or
bare aluminium. However, it is always advisable to
silver-plate the contact surfaces.
The thickness of the surface treatment must be
even and regular.
7.6.4 Assembly of the connections
Make sure that the contact surfaces of the
connections are perfectly flat and without burrs,
traces of oxidation or deformities caused by
drilling or impact sustained.
Depending on the conductive material used and
the surface treatment given, the operations
indicated in the following table must be carried
out on the surface contact of the conductor.
Bare copper Clean with a fine file or emery cloth
Copper or
silverplated
aluminium
Clean with a rough dry cloth
Only if there are traces of oxidation that are difficult
to shift, clean with ultra-fine grain emergy cloth and
take care not to remove the surface layer
Repeat the surface treatment if necessary
Bare
aluminium
Clean with a metal brush or emery cloth
Immediately smear neutral grease over the contact
surfaces
Insert a bi-metal copper-aluminium strip with
beaded surfaces between the aluminium connection and
the copper terminal (copper side touching the terminal,
aluminium side touching the connection)
Assembly procedures
Place the connections in contact with the circuit
breaker terminals.
Insert a spring washer and a flat washer
between the head of the bolt and the
connection.
The diameter of the flat washers must be able to
distribute the torquing pressure over a wide
area.
Tighten the bolt, taking care to prevent the
insulating parts from being stressed (consult
the table with the rightening torque values).
Make sure that the connections do not exert any
force on the terminals.
Carefully comply with the manufacturer’s
instructions for terminating the cables in cable
connections.
Table of tightening torque values
Screw Tightening torque values
Figure 13
Make sure that the circuit breaker is open
and the closing springs discharged before
removing the operating mechanism cover to
access the terminal box.
7.8 Connection of the auxiliary
circuits
The minimum cross-section of the wires used for
the auxiliary circuits must not be less than the one
used for the internal cabling.
They must also be insulated for 3 kV test voltage.
7.8.1 Fixed version circuit breakers
The auxiliary circuits of the circuit breaker must be
connected by means of the terminal box installed in
the circuit breaker’s operating mechanism.
The wires outside the circuit breaker must be
routed inside appropriately earthed metal tubes or
ducts.
7.8.2 Plug-in circuit breaker
The auxiliary circuits of the plug-in or removable
circuit breaker are fully wired in the factory
through to the connector. Please refer to the
wiring diagram of the switchgear for the
connections.