ABB 5HK Series Installation and operating instructions

IB
6.2
.
1.7
D
Page
2
Ann
MIPIP
ASEA
BROWN
BOVERI
J
CONTENTS
PAGE
INTRODUCTION
RECEIVING
AND
STORAGE
CIRCUIT
BREAKER
INSTALLATION
INFORMATION
General
Installation
Inspection
Removing
Interphase
Barrier
Removing
Arc
Chutes
Insulation
Structure
Manual
Slow
-
close
to
Check
Contact
Pressure
Installing
Arc
Chutes
Installing
Interphase
Barriers
Installing
Circuit
Breaker
into
Compartment
CIRCUIT
BREAKER
REMOVAL
Removal
From
Connected
Position
Disconnect
Position
Removal
from
Switchboard
Safe
Operation
Recommendations
MAINTENANCE
AND
ADJUSTMENTS
General
Information
Contact
Pressure
Contact
and
Insulation
Cleaning
Millivolt
Drop
Test
Puffers
Bridge
Pivot
Opening
Times
Closing
and
Opening
Times
Arc
Chutes
Operating
Mechanism
Control
Relay
Adjustment
Racking
Mechanism
Lubrication
Dielectric
Tests
Electrical
Characteristics
of
Control
Devices
.
.
..
ELECTRICAL
OPERATING
SEQUENCE
GROUND
AND
TEST
DEVICES
RENEWAL
PARTS
3
3
3
3
3
3
4
4
4
5
5
5
6
6
6
J
r
'
6
6
6
6
7
8
8
8
9
9
9
9
10
10
10
11
11
11
12
13
)
Courtesy of NationalSwitchgear.com

IB
6.2
.
1.7
D
Page
3
AII
It
MIPIP
ASEA
BROWN
BOVERI
Section
3
.
CIRCUIT
BREAKER
INSTALLATION
3.1
GENERAL
Priorto
installation
of
thecircuit
breaker
into
a
switchboard
,
certain
preliminary
inspections
are
made
to
ensure
proper
operation
.
Section
1
.
INTRODUCTION
These
instructions
for
installation
,
operation
and
mainte
-
nance
of
HK
circuit
breakers
should
be
read
carefully
and
used
as
a
guide
during
installation
and
initial
operation
.
The
specific
ratings
of
each
model
circuit
breaker
are
listed
on
the
individual
nameplates
.
File
these
instructions
in
a
readily
accessible
place
to
-
gether
with
drawing
and
descriptive
data
of
the
switchgear
.
These
instructions
are
guides
to
proper
maintenance
of
the
equipment
to
prolong
its
life
and
usefulness
.
CAUTION
CAUTION
CAUTION
CAUTION
PRIOR
TO
ANY
DISASSEMBLY
OR
INSPECTION
OF
THE
CIRCUIT
BREAKER
THE
CLOSING
SPRINGS
SHOULD
BE
DISCHARGED
AND
THE
BREAKER
SHOULD
BE
OPEN
.
IF
IT
IS
NECESSARY
TO
RAISE
OR
MOVE
THE
BREAKER
ATTACH
THE
LIFTING
YOKE
AT
POINTS
4
(
FIGURE
1
)
,
OR
A
FIFTH
WHEEL
AT
POINT
7
(
FIGURE
2
)
TO
TRANSPORT
THE
BREAKER
AS
RE
-
QUIRED
.
Section
2
.
RECEIVING
AND
STORAGE
Immediately
upon
receipt
of
the
circuit
breakers
,
examine
the
cartons
to
determine
if
any
damage
or
loss
was
sus
-
tained
during
transit
.
If
injury
or
rough
handling
is
evident
,
file
a
damage
claim
at
once
with
the
carrier
and
promptly
notify
the
nearest
district
office
.
Asea
Brown
Boveri
,
Inc
.
is
not
responsible
for
damage
of
goods
after
delivery
to
the
carrier
.
However
,
the
company
will
lend
assistance
if
noti
-
fied
of
claims
.
Unpack
the
circuit
breakers
as
soon
as
possible
after
receipt
.
If
unpacking
is
delayed
,
difficulty
may
be
experi
-
enced
in
making
a
claim
for
damages
not
evident
upon
receipt
.
Use
care
in
unpacking
in
order
to
avoid
damaging
any
of
the
circuit
breaker
parts
.
Check
the
contents
of
each
carton
against
the
packing
list
before
discarding
any
pack
-
ing
material
.
If
any
shortage
of
material
is
discovered
,
promptly
notify
the
nearest
district
office
.
Information
speci
-
fying
the
purchase
order
number
,
sales
order
number
,
carton
number
and
part
numbers
of
the
damaged
or
miss
-
ing
part
should
accompany
the
claim
.
Circuit
breakers
should
be
installed
in
their
permanent
location
as
soon
as
possible
.
If
the
breakers
are
not
to
be
placed
in
service
for
some
time
,
it
is
requ
ired
that
adequate
means
of
protection
be
provided
.
This
may
be
done
by
keeping
the
breaker
in
its
original
shipping
carton
and
storing
in
a
warm
(
approximately
15
°
C
)
dry
(
50
%
max
humidity
)
and
uncontaminated
atmosphere
.
If
the
circuit
breaker
cannot
be
stored
properly
due
to
abnormal
circum
-
stances
,
it
must
be
thoroughly
checked
before
going
into
service
to
ensure
that
it
is
without
damage
and
it
has
not
become
generally
contaminated
.
3.2
INSTALLATION
INSPECTION
Inspect
condition
of
circuit
breaker
arc
chutes
,
contact
and
electrical
connections
priorto
installing
the
circuit
breaker
into
the
switchboard
.
Even
though
each
circuit
breaker
is
completely
adjusted
and
tested
at
the
factory
,
shipping
and
handling
conditions
could
cause
defects
.
3.3
REMOVING
INTERPHASE
BARRIER
For
5
HK
75
,
150
and
250
,
remove
two
lower
front
sheet
screws
,
lift
straight
up
above
arc
chutes
by
grasping
front
handle
and
top
sheet
at
rear
,
then
draw
barrierforward
and
away
from
circuit
breaker
.
For
5
HK
350
,
remove
two
lower
front
sheet
screws
,
and
lift
front
sheet
up
and
away
from
the
breaker
.
Remove
arc
chute
tie
bar
at
upper
front
of
arc
chutes
.
Pivot
rear
brace
at
rear
of
each
barrier
upward
and
slide
the
separate
barriers
forward
and
away
from
the
circuit
breaker
.
CAUTION
CAUTION
CAUTION
CAUTION
THE
5
HK
350
BARRIERS
WILL
NOT
STAND
UNSUP
-
PORTED
AND
MUST
BE
BRACED
.
These
instructions
do
not
purport
to
cover
all
details
or
variations
in
equipment
nor
to
provide
for
every
possible
contingency
to
be
met
in
connection
with
installation
,
operation
or
maintenance
.
Should
further
information
be
desired
or
should
particular
problems
arise
which
are
not
covered
sufficiently
for
purchaser
'
s
purposes
the
matter
should
be
referred
to
the
nearest
District
Office
.
Courtesy of NationalSwitchgear.com

IB
6.2
.
1.7
D
Page
4
A
»
11
MIPIP
ASEA
BROWN
BOVERI
3.4
REMOVING
ARC
CHUTES
(
See
Figure
1
)
For
5
FIK
75
,
150
and
250
,
remove
nut
(
6
)
and
gently
disconnect
return
connection
(
5
)
.
Grasp
the
arc
chute
(
I
)
at
the
front
and
top
and
gently
tilt
on
its
pivot
towards
the
rear
until
it
rests
on
the
lead
support
molding
(
2
)
.
If
other
than
visual
inspection
is
to
be
done
,
the
arc
chute
,
in
the
tilted
position
,
should
be
lifted
straight
out
of
the
pivot
guide
slots
and
fingers
and
removed
from
the
circuit
breaker
.
For
5
HK
350
,
remove
nut
(
6
)
and
gently
disconnect
return
connection
(
5
)
.
Remove
bolt
connecting
the
front
leg
of
the
arc
chute
to
the
block
on
the
base
sheet
of
the
circuit
breaker
.
Attach
the
accessory
lifting
bracket
to
the
tie
bar
bushing
at
the
top
front
of
the
arc
chute
and
slowly
raise
the
arc
chute
as
required
by
means
of
a
hoist
.
It
will
pivot
at
its
terminal
connection
and
then
should
be
guided
straight
out
of
the
pivot
guide
slot
and
fingers
and
removed
away
from
the
circuit
breaker
.
If
only
a
visual
examination
is
to
be
made
,
each
arc
chute
may
be
tilted
back
gently
,
hand
held
and
then
slowly
lowered
.
3.5
ARC
CHUTE
EXAMINATION
Examine
arc
chutes
carefully
before
placing
into
service
.
Look
for
any
breakage
to
liner
plates
and
arc
chute
plates
.
Check
for
presence
of
any
foreign
particles
such
as
chips
of
ceramic
and
metal
.
Inspect
exterior
for
any
damage
or
deformation
.
The
polyester
glass
moldings
occasionally
have
some
small
cracks
develop
in
resin
-
rich
areas
,
but
these
cracks
do
not
indicate
defective
material
and
should
not
cause
concern
.
3.6
INSULATION
STRUCTURE
All
insulated
parts
should
be
checked
for
damage
.
Any
dust
or
dirt
should
be
removed
by
compressed
air
or
wiped
with
a
clean
,
lint
-
free
cloth
saturated
with
an
oil
-
free
solvent
.
This
is
important
because
the
soot
or
dirt
can
accumulate
and
,
with
moisture
,
place
the
circuit
breaker
in
jeopardy
,
dielectrically
.
The
lead
support
moldings
are
polyester
glass
and
occasionally
have
some
resin
-
rich
cracks
or
crazing
develop
,
but
these
do
not
indicate
defective
mate
-
rial
and
should
not
cause
concern
.
CAUTION
CAUTION
CAUTION
CAUTION
3.7
MANUAL
SLOW
-
CLOSE
TO
CHECK
CONTACT
PRESSURE
(
Figure
2
)
NOTE
:
Ensure
that
accessories
that
affect
electrical
/
me
-
chanical
operation
are
set
in
their
operating
positions
:
i
.
e
.
,
undervoltage
devices
should
be
energized
or
mechanically
closed
;
mechanical
interlocks
,
key
or
other
,
should
be
properly
set
,
etc
.
1
.
Turn
racking
screw
clockwise
approximately
two
to
three
turns
until
the
racking
-
unlocking
lever
snaps
into
the
first
position
corresponding
to
the
“
DISCONNECT
”
position
.
2
.
Engage
manual
charge
handle
(
8
)
with
charging
lever
(
3
)
.
Pump
charging
lever
until
breakerclosing
springs
snap
into
charge
position
,
then
remove
handle
.
3
.
Insert
BOTH
tangs
of
spring
retainer
bracket
(
7
)
into
holes
of
closing
spring
guides
(
2
)
.
4
Pull
manual
close
lever
(
4
)
to
discharge
closing
springs
onto
tangs
of
spring
retainer
bracket
(
7
)
.
At
this
time
the
contacts
will
partially
close
.
5
.
Re
-
engage
manual
charge
handle
(
8
)
with
charging
lever
(
3
)
,
then
slowly
pump
to
slow
-
close
breaker
contacts
.
Check
contact
pressure
as
listed
in
paragraph
5.2
.
Use
the
manual
trip
button
(
6
)
to
open
the
breaker
.
6
.
To
remove
spring
retainer
bracket
(
7
)
from
circuit
breaker
,
continue
pumping
until
closing
springs
are
again
heard
to
snap
into
fully
-
charged
position
.
Spring
retainer
bracket
can
now
be
removed
.
7
.
Discharge
closing
springs
by
pulling
manual
close
lever
(
4
)
and
pushing
manual
trip
button
(
6
)
at
the
same
time
to
effect
trip
-
free
operation
.
(
The
breaker
can
also
be
closed
first
and
then
tripped
.
)
BE
SURE
RETURN
CONNECTION
IS
CLEAR
AND
DOES
NOT
CATCH
ON
THE
ARC
CHUTE
.
ALSO
BLOCK
WHEELS
TO
PREVENT
BREAKER
FROM
ROLLING
.
)
Fig
.
1
-
View
Showing
Chute
and
Contact
Structure
Courtesy of NationalSwitchgear.com

IB
6.2
.
1.7
D
Page
5
Aim
MIPIP
ASEA
BROWN
BOVERI
8
.
Lift
front
sheet
in
place
so
that
it
looks
over
the
arc
tie
bar
.
9
.
Secure
the
barrier
front
sheet
in
place
with
the
two
lower
front
sheet
screws
.
CAUTION
CAUTION
CAUTION
CAUTION
ON
5
HK
350
,
FOR
OLDER
UNMARKED
BARRIERS
,
INSURE
THAT
THE
FLUX
SHUNT
PAD
IS
INSTALLED
BETWEEN
POLES
.
3.10
INSTALLING
CIRCUIT
BREAKER
INTO
COM
-
PARTMENT
(
See
Figures
2
and
3
)
NOTE
:
CLOCKWISE
ROTATION
of
racking
crank
for
inserting
breaker
.
COUNTERCLOCKWISE
rotation
of
racking
crank
for
removal
of
the
breaker
1
.
Turn
motor
disconnect
switch
(
if
supplied
) (
1
,
Figure
2
)
to
“
OFF
”
position
.
2
.
Engage
racking
crank
(
4
,
Figure
3
)
and
push
racking
unlocking
lever
(
3
)
to
left
,
then
rotate
racking
crankcounter
-
clockwise
only
until
resistance
to
motion
is
felt
.
(
DO
NOT
FORCE
.
)
3
.
Engage
f
ifth
wheel
with
hole
guide
(
5
,
Figure
2
)
and
push
circuit
breaker
into
compartment
until
stopped
.
(
If
closing
springs
were
left
in
charged
condition
,
they
will
automati
-
cally
discharge
.
)
4
.
Engage
racking
crank
and
rotate
clockwise
until
racking
mechanism
automatically
stops
at
“
DISCONNECT
”
posi
-
tion
.
(
Breaker
is
now
held
captive
in
compartment
.
)
5
.
To
rack
circuit
breaker
to
‘
TEST
”
position
,
push
racking
unlocking
lever
(
3
,
Figure
3
)
to
left
,
rotate
racking
crank
approximately
1
/
4
turn
clockwise
,
then
release
unlocking
lever
.
Continue
cranking
until
racking
mechanism
auto
-
matically
stops
at
“
TEST
’
position
.
6
.
With
the
circuit
breaker
racked
to
“
TEST
”
position
,
check
for
proper
operation
by
operating
all
possible
means
of
Fig
.
2
—
Front
View
of
Control
Panel
3.8
INSTALLING
ARC
CHUTES
(
See
Figure
I
)
Position
arc
chute
(
I
)
in
tilted
position
,
squarely
down
into
its
rear
pivot
guide
slots
and
fingers
(
avoid
bumping
and
chipping
of
all
moldings
)
,
then
lower
slowly
into
position
.
CAUTION
CAUTION
CAUTION
CAUTION
BE
SURE
RETURN
CONNECTION
IS
CLEAR
AND
NOT
CATCH
ON
THE
ARC
CHUTE
.
Securely
fasten
return
connection
(
5
)
by
its
nut
(
6
)
Also
,
on
5
HK
350
breakers
the
front
arc
chute
support
leg
must
be
secured
to
its
hold
down
block
.
3.9
INSTALLING
INTERPHASE
BARRIER
1
.
For
5
HK
75
,
150
and
250
,
lift
barrier
and
slide
it
approxi
-
mately
halfway
on
the
breaker
.
2
.
After
aligning
the
vertical
sheets
of
the
barrier
properly
between
the
lead
support
moldings
and
inside
the
clips
on
the
outside
moldings
,
slide
the
barrier
as
far
to
the
rear
as
possible
.
3
.
Lift
the
barrier
slightly
by
its
handle
at
the
lower
front
(
Figure
2
)
to
permit
the
rear
brace
of
the
barrier
to
drop
down
behind
the
arc
chutes
.
4
.
Push
firmly
down
and
back
on
the
barrier
handle
to
properly
position
the
interphase
barrier
in
place
.
5
.
Secure
the
barrier
in
place
with
the
two
lower
front
sheet
screws
.
6
.
For
the
5
HK
350
,
slide
the
right
and
left
interphase
barriers
,
as
marked
,
in
place
between
the
lead
support
moldings
and
inside
of
the
clips
on
the
outside
moldings
,
and
pivot
the
rear
brace
downward
hehind
the
arc
chutes
.
7
.
Install
the
arc
chute
tie
bar
at
the
upper
front
on
the
arc
chutes
.
Fig
.
3
-
Method
of
Racking
Circuit
Breaker
Courtesy of NationalSwitchgear.com

IB
6.2
.
1.7
D
Page
6
ABB
ASEA
BROWN
BOVERI
opening
and
closing
.
This
includes
control
switches
,
relays
,
etc
.
Turn
motor
disconnect
switch
(
1
,
Figure
2
)
to
“
ON
”
position
to
charge
the
closing
springs
,
and
operate
the
breaker
as
required
.
If
motor
disconnect
switch
(
1
,
Figure
2
)
is
not
provided
,
springs
will
automatically
charge
when
approaching
‘
TEST
portion
.
FOR
SAFETY
:
When
racking
circuit
breaker
to
“
CON
-
NECTED
”
position
,
close
compartment
door
(
1
,
Figure
3
)
and
insert
racking
crank
(
4
,
Fiqure
3
)
through
sliding
panel
(
2
,
Figure
3
)
.
7
.
Push
unlocking
lever
(
3
)
to
left
and
turn
racking
crank
(
4
)
approximately
1
/
4
turn
clockwise
,
then
release
unlocking
lever
.
Continue
cranking
until
racking
mecha
-
nism
automatically
stops
at
“
CON
NECTED
”
position
.
4.4
SAFE
OPERATION
RECOMMENDATIONS
1
.
It
is
recommended
that
any
circuit
breaker
be
withdrawn
and
stored
in
the
test
position
whenever
it
is
to
be
main
-
tained
in
the
open
position
with
no
planned
switching
.
2
.
It
is
recommended
that
a
ground
test
device
be
con
-
nected
to
the
proper
compartment
when
any
work
is
to
be
done
on
any
bus
or
feeder
circuit
.
Section
5
.
MAINTENANCE
AND
ADJUSTMENTS
5.1
GENERAL
INFORMATION
HK
circuit
breakers
are
designed
for
minimum
mainte
-
nance
and
tested
to
ensure
that
minimum
maintenance
will
be
required
.
Only
one
basic
adjustment
is
normally
re
-
quired
and
that
is
contact
adjustment
.
This
should
be
checked
to
the
dimensional
values
required
as
described
in
paragraph
5.2
.
Other
adjustments
are
required
only
when
operational
check
indicates
a
need
.
During
maintenance
checks
,
all
accessible
bolts
,
nuts
and
screws
should
be
routinely
checked
to
ensure
that
they
are
tight
.
It
is
recom
-
mended
that
the
5
HK
75
,
5
HK
150
and
5
HK
250
circuit
breakers
be
normally
inspected
after
2000
operations
and
that
the
5
HK
350
circuit
breakers
be
normally
inspected
after
1000
operations
.
These
operations
can
be
either
no
-
load
mechanical
or
load
current
switching
where
the
power
factor
is
relatively
high
.
When
the
circuit
breakers
are
used
for
direct
bulk
capacitor
or
reactor
switching
operations
or
for
motor
starting
applications
,
it
is
recommended
the
5
HK
75
,
5
HK
150
and
5
HK
250
circuit
breakers
be
inspected
after
1000
operations
and
that
the
5
HK
350
circuit
breakers
be
inspected
after
500
operations
because
of
the
switching
severity
If
however
,
after
the
first
inspection
period
,
there
is
no
indication
of
any
problem
,
actual
operating
experience
can
dictate
the
inspection
cycle
.
Regarding
maintenance
recommendations
following
fault
duty
,
reference
is
made
to
ANSI
Standard
C
37.04
to
which
the
circuit
breakers
have
been
tested
.
In
accordance
with
this
standard
,
a
total
of
400
%
asymmetrical
fault
duty
can
be
accumulated
.
This
is
to
be
ten
or
less
close
-
open
operations
at
less
than
85
%
of
full
duty
;
but
it
can
be
an
accumulation
over
a
long
time
period
of
lower
currents
.
The
condition
of
the
breaker
should
be
such
that
after
this
duty
it
is
capable
of
one
more
close
-
open
operation
at
full
fault
current
.
Inspection
is
to
be
made
at
this
time
to
ensure
compliance
with
this
requirement
.
Final
operation
can
be
made
if
everything
is
satisfactory
.
At
this
time
,
maintenance
should
be
performed
,
reconditioning
done
and
replace
-
ment
made
as
indicated
.
In
accordance
with
the
same
standard
it
is
recommended
that
after
a
major
fault
duty
cycle
(
CO
-
15
SEC
CO
)
Which
is
known
to
be
between
85
and
100
%
of
the
circuit
breaker
CAUTION
CAUTION
CAUTION
CAUTION
DO
NOT
ATTEMPT
TO
RACK
ANY
FURTHER
The
circuit
breaker
may
now
be
put
in
service
and
be
operated
as
required
Section
4
.
CIRCUIT
BREAKER
REMOVAL
(
See
Figure
3
)
4.1
REMOVAL
FROM
“
CONNECTED
”
POSITION
To
remove
circuit
breaker
from
“
CONNECTED
”
position
,
open
the
breaker
as
required
.
1
.
Open
sliding
door
(
2
)
in
front
compartment
door
(
1
)
.
2
.
Engage
racking
crank
(
4
)
and
push
racking
unlocking
lever
(
3
)
to
left
.
3
.
Rotate
racking
crank
(
4
)
counterclockwise
approxi
-
mately
1
/
4
turn
,
then
release
unlocking
lever
.
4
.
Continue
cranking
counterclockwise
until
racking
mechanism
automatically
stops
at
“
TEST
”
position
.
4.2
“
DISCONNECT
”
POSITION
Repeat
same
operation
for
"
DISCONNECT
”
position
.
4.3
REMOVAL
FROM
SWITCHBOARD
To
position
the
racking
mechanism
for
withdrawal
of
the
circuit
breaker
from
the
switchboard
,
again
push
racking
unlocking
lever
to
the
left
and
turn
racking
crank
counter
-
clockwise
only
until
resistance
to
motion
is
felt
.
(
Approxi
-
mately
2
-
3
turns
-
DO
NOT
FORCE
.
)
The
circuit
breaker
can
now
be
removed
from
the
compart
-
ment
by
pulling
on
the
handle
located
at
the
bottom
of
the
front
barrier
,
or
by
pulling
at
the
lower
edge
of
the
front
barrier
on
the
1200
and
2000
ampere
,
5
HK
350
breaker
.
NOTE
:
The
closing
springs
,
if
charged
,
will
automatically
discharge
when
the
circuit
breaker
is
withdrawn
from
the
switchboard
.
)
Courtesy of NationalSwitchgear.com

Aim
MIPIP
IB
6.2
.
1.7
D
Page
7
ASEA
BROWN
BOVERI
rated
asymmetrical
short
circuit
current
,
the
circuit
breaker
be
inspected
regardless
of
any
time
period
or
number
of
operations
.
Also
,
when
the
circuit
breaker
is
applied
on
reclosing
duty
,
it
should
be
inspected
immediately
afterthe
series
of
fault
operations
in
the
same
range
of
currents
.
The
condition
of
the
circuit
breaker
after
interruption
de
-
pends
on
circuit
conditions
regarding
such
things
as
power
factor
,
X
/
R
ratio
and
relay
delay
times
.
Experience
with
specific
circuits
will
indicate
the
future
amount
of
mainte
-
nance
that
will
be
required
for
the
various
breakers
and
then
procedural
modification
can
follow
.
Where
unusual
service
conditions
exist
,
as
covered
by
ANSI
Standard
C
37.04
,
it
must
be
assumed
that
these
conditions
were
considered
at
the
time
of
order
;
that
the
equipment
supplied
was
designed
for
the
special
applica
-
tion
;
and
that
an
appropriate
supplemental
maintenance
program
has
been
developed
.
These
maintenance
instruc
-
tions
cover
only
circuit
breakers
used
under
standard
usual
service
conditions
.
After
normal
service
without
major
fault
interruption
,
the
following
tests
and
adjustments
should
be
made
.
NOTE
:
The
following
tabulated
tests
and
adjustments
are
all
that
are
normally
necessary
for
proper
maintenance
and
operation
of
the
HK
circuit
breaker
.
The
remaining
portions
of
the
breaker
-
close
coil
assembly
,
shunt
trip
device
,
control
relay
,
auxiliary
switch
and
motor
—
require
no
main
-
tenance
during
the
standard
life
of
the
circuit
breaker
regardless
of
the
operatinq
duty
.
5.2
CONTACT
PRESSURE
(
See
Figure
4
)
(
A
)
With
the
circuit
breaker
withdrawn
from
the
switch
-
board
,
the
following
step
-
by
-
step
procedure
should
be
followed
for
properly
checking
and
/
or
adjusting
the
contact
pressure
on
an
“
HK
”
type
circuit
breaker
.
1
.
Remove
interphase
barrier
assembly
and
remove
arc
chutes
as
described
previously
.
2
Turn
racking
screw
clockwise
approximately
two
to
three
turns
until
the
racking
-
unlocking
lever
snaps
into
the
first
position
corresponding
to
the
‘
’
DISCONNECT
’
position
.
3
.
Manually
slow
-
close
the
circuit
breaker
as
described
in
parag
raph
3.7
,
but
only
to
the
point
that
the
arc
contacts
just
touch
.
All
arcing
contacts
shouldtouch
within
1
/
32
"
,
after
all
free
play
has
been
removed
by
pulling
the
bridge
arm
toward
the
open
position
.
4
.
Continue
the
slow
-
close
operation
to
fully
close
the
breaker
.
Each
pole
should
have
approximately
7
/
64
”
to
3
/
16
”
main
contact
compression
measured
at
"
A
”
between
the
edge
of
the
metal
stop
plate
and
the
main
contact
stop
.
(
This
dimension
measured
on
either
side
is
sufficient
)
.
A
rod
or
drill
of
these
sizes
can
be
used
for
measuring
.
Complete
charging
the
sprinqs
and
remove
the
slow
close
bracket
.
Fig
.
4
—
Contact
Pressure
and
Bridge
Pivot
Pressure
5
.
Open
the
breaker
.
Fast
close
the
breaker
.
Each
pole
should
have
between
7
/
64
"
to
3
/
16
"
main
contact
pressure
.
At
this
point
,
if
the
adjustments
are
correct
,
complete
steps
B
6
,
B
7
,
B
8
and
B
9
following
.
(
B
)
If
any
adjustment
is
incorrect
,
use
the
following
proce
-
dure
to
readjust
contact
pressure
or
to
initially
adjust
when
changes
are
made
.
1
Completely
slow
-
close
the
circuit
breaker
and
set
each
pole
for
7
/
64
"
main
contact
compression
at
"
A
”
(
A
7
/
64
”
rod
ordrill
should
fit
tightly
between
the
EDGE
of
the
metal
stop
plate
and
the
main
contact
stop
.
)
2
.
Open
thecircuit
breaker
,
manually
recharge
the
closing
springs
,
and
partially
slow
-
close
the
circuit
breaker
until
the
arcing
contacts
of
any
pole
or
poles
just
touch
.
3
.
Advance
the
adjustment
of
the
lagging
pole
or
poles
so
that
the
three
arcing
contacts
touch
simultaneously
within
1
/
32
"
.
This
adjustment
is
made
by
loosening
locking
bolt
or
set
screw
(
depending
on
model
) (
2
)
and
rotating
adjusting
stud
(
3
)
.
4
Complete
slow
-
close
operation
to
fully
closed
position
and
check
that
the
main
contact
compression
of
the
pole
or
poles
that
were
advanced
does
not
exceed
3
/
16
"
.
Also
,
the
arcing
contact
springs
on
these
poles
should
not
be
fully
compressed
.
If
the
3
/
16
"
dimension
is
exceeded
,
the
entire
procedure
should
be
repeated
to
obtain
the
correct
gap
at
“
A
”
.
NOTE
:
Occasionally
,
the
centerpole
contact
pressure
may
slightly
exceed
3
/
16
"
However
,
if
the
outer
poles
are
within
3
/
16
"
dimension
and
the
arcing
contact
springs
of
the
Courtesy of NationalSwitchgear.com

IB
6.2
.
1.7
D
Page
8
ASEA
BROWN
BOVERI
center
pole
are
not
fully
compressed
no
readjustments
need
be
made
.
When
this
condition
exists
,
the
center
pole
parts
before
the
outer
poles
on
opening
.
5
.
Open
breaker
,
recharge
closing
springs
,
remove
slow
-
close
bracket
,
fast
close
the
breaker
,
recheck
adjustments
for
7
/
64
"
to
3
/
16
”
,
“
A
”
dimension
.
NOTE
:
Fast
-
closing
the
circuit
breaker
may
result
in
a
slight
increase
in
contact
pressure
over
slow
-
closing
.
6
.
Tighten
the
locking
bolt
(
2
)
on
each
adjusting
stud
(
3
)
to
lock
the
contact
pressure
adjustment
stud
in
place
.
7
.
The
arc
chutes
can
now
be
replaced
,
and
the
interphase
barrier
assembly
can
now
be
reinstalled
.
8
.
Return
the
racking
screwto
its
original
position
by
turning
it
counterclockwise
approximately
two
to
three
turns
until
it
stops
.
9
.
The
circuit
breaker
can
now
be
replaced
in
its
compart
-
ment
and
returned
to
service
.
The
following
table
lists
the
millivolt
drop
and
resistance
values
for
the
circuit
breakers
,
when
manufactured
,
cov
-
ered
by
this
instruction
book
,
from
terminal
,
exclusive
of
the
primary
disconnects
.
Maximum
Micro
-
Ohms
Maximum
MV
Drop
*
Circuit
Breaker
5
HK
75
,
5
HK
150
,
5
HK
250
5
HK
350
,
1200
Ampere
8
40
5
HK
150
,
5
HK
250
,
5
HK
350
2000
Ampere
7
35
5
HK
350
,
3000
Ampere
4
20
5.3
CONTACT
AND
INSULATION
CLEANING
All
dirt
,
soot
or
grease
should
be
removed
from
circuit
breaker
contacts
and
surface
of
entire
current
-
carrying
structure
,
as
well
as
ail
insulation
surfaces
,
with
a
cloth
saturated
with
an
oil
-
free
OSHA
-
approved
solvent
.
Clean
-
ing
of
insulation
is
important
because
soot
and
dirt
can
accumulate
and
,
with
moisture
,
place
the
circuit
breaker
in
jeopardy
,
dielectrically
.
A
degree
of
burning
and
pitting
of
circuit
breaker
arcing
contacts
is
to
be
expected
from
normal
operation
;
also
,
on
highly
inductive
or
capacitative
circuits
and
after
major
interruptions
,
some
pitting
may
occur
on
main
contacts
.
A
moderate
amount
of
pitting
will
not
interfere
with
operation
of
the
contacts
.
When
necessary
to
dress
the
contacts
,
cover
the
puffer
nozzle
(
5
,
Figure
1
)
with
a
cloth
,
then
follow
the
contour
of
the
contacts
with
a
fine
file
.
Do
not
attempt
to
eliminate
pitting
entirely
.
Afterthis
maintenance
,
contact
pressure
(
paragraph
5.2
)
;
and
millivolt
drop
(
paraqraph
5.4
)
should
be
checked
.
NOTE
:
Replacement
of
contacts
is
required
when
:
after
repeated
dressing
of
any
contacts
,
less
than
50
%
of
the
original
contact
material
thickness
is
left
;
*
the
tips
of
the
stationary
arcing
contacts
have
been
eroded
away
;
any
contact
has
been
broken
or
cracked
.
*
On
5
HK
350
,
3000
the
arcing
contct
can
be
inverted
when
working
surface
is
reduced
to
less
than
50
%
.
*
Millivolt
drop
with
200
amperes
flowing
.
Breakers
operating
with
normal
loading
will
require
no
maintenance
if
the
millivolt
drop
does
not
exceed
150
%
of
the
listed
values
.
If
the
millivolt
drop
does
exceed
150
%
of
the
above
values
,
the
main
and
arcing
contacts
should
be
dressed
with
a
fine
file
,
cleaned
and
adjusted
for
proper
contact
pressure
and
then
rechecked
.
If
the
values
are
still
in
excess
of
the
150
%
value
,
the
bridge
pivot
pressure
should
be
readjusted
as
outlined
in
Paragraph
5.6
.
NOTE
:
For
optimum
performance
of
the
circuit
breakers
during
periods
of
increased
loading
,
it
is
recommended
that
the
listed
values
be
met
.
After
all
above
steps
have
been
taken
and
the
millivolt
drop
is
still
excessive
,
contact
the
nearest
district
office
for
recommendations
.
)
5.5
PUFFERS
(
3
,
Figure
1
)
CAUTION
CAUTION
CAUTION CAUTION
FOR
SAFETY
KEEP
CLEAR
OF
ALL
MOVING
PARTS
.
The
performance
of
the
puffers
should
be
checked
during
a
normal
maintenance
interval
.
Each
puffer
should
provide
a
moderate
blast
of
air
at
breaker
contacts
,
on
opening
of
thecircuit
breaker
.
This
can
be
detected
by
holding
a
piece
of
paper
approximately
8
-
1
/
2
"
x
11
"
over
the
top
of
the
contacts
and
opening
the
circuit
breaker
.
All
three
poles
must
have
puffing
action
or
the
circuit
breaker
must
not
be
placed
in
service
.
5.4
DC
MILLIVOLT
DROP
TEST
During
normal
maintenance
periods
the
condition
of
the
circuit
breaker
can
easily
be
determined
by
performing
a
millivolt
drop
test
.
This
test
shou
Id
be
performed
regardless
of
whether
the
circuit
breaker
had
interrupted
low
or
high
currents
or
has
minimum
operations
.
Courtesy of NationalSwitchgear.com

A
IK
I
!
MINK
IB
6.2
.
1.7
D
Page
9
ASEA
BROWN
BOVERI
5.8
ARC
CHUTES
The
arc
chutes
should
be
inspected
internally
to
ensure
that
no
breakaqe
occurred
to
liner
plates
or
arc
plates
.
Further
,
there
may
be
a
crust
formed
on
the
liner
plates
if
load
current
interruptions
were
close
to
the
continuous
current
rating
of
the
breaker
,
or
moderate
faults
were
interrupted
.
This
crust
should
be
removed
by
carefully
using
a
carbo
-
rundum
stone
or
scraper
.
The
arc
chute
should
then
be
blown
out
with
compressed
air
to
remove
the
resultant
dust
and
particles
.
After
400
%
accumulated
current
or
major
interruptions
occur
,
the
circuit
breaker
should
be
inspected
immediately
.
All
maintenance
checks
or
tests
noted
above
should
be
carried
out
,
plus
close
examination
of
the
arc
chute
.
Arc
plate
and
liner
plate
breakage
should
be
carefully
looked
for
,
along
with
excessive
erosion
of
the
arc
plates
.
Arc
plates
are
made
of
ceramic
material
and
perform
the
function
of
extracting
heat
from
the
arc
as
it
is
beinq
forced
into
and
elongated
by
them
.
The
leading
edges
become
coated
with
glass
that
comes
to
the
surface
from
the
extreme
heat
.
Direct
measure
of
use
is
the
amount
of
glass
beads
evident
.
When
the
entire
leading
edge
and
portions
of
the
flat
arc
plate
are
heavily
encrusted
with
glass
beads
,
the
arc
chute
should
be
replaced
.
It
should
be
noted
that
this
condition
will
vary
between
arc
chutes
on
the
same
breaker
because
of
single
-
phase
fault
and
asymmetrical
current
incidences
.
5.6
BRIDGE
PIVOT
PRESSURE
(
See
Figure
4
)
Bridge
pivot
pressure
should
be
adjusted
only
when
the
millivolt
drop
test
indicates
a
problem
.
When
adjustment
is
necessary
,
adjust
as
follows
:
1
.
Locking
bolt
(
2
)
should
be
loosened
on
solid
pushrod
models
.
Springloaded
pushrod
models
do
not
require
dis
-
connecting
.
2
.
Bridge
(
I
)
should
be
disconnected
from
adjusting
stud
(
3
)
on
solid
pushrod
models
.
3
.
Loosen
one
set
screw
(
6
)
in
one
pivot
nut
-
either
side
.
4
.
Tighten
bridge
pivot
nut
(
5
or
7
)
securely
(
approximately
75
ft
.
lbs
.
)
.
Then
gradually
backup
pivot
nut
(
approximately
1
/
2
to
1
-
1
/
2
flats
until
bridge
motion
is
just
free
when
bridge
is
moved
by
hand
.
On
spring
-
loaded
pushrod
models
,
lift
bridge
against
spring
and
then
slowly
release
,
ensuring
that
it
resets
freely
.
5
.
Tighten
set
screw
(
6
)
in
nut
that
was
loosened
,
reconnect
adjusting
stud
,
if
disconnected
,
and
readjust
contact
pres
-
sure
as
described
in
Paragraph
5.2
.
5.7
CLOSING
AND
OPENING
TIMES
After
operation
intervals
noted
previously
or
a
chanqe
in
bridge
pivot
adjustment
,
it
is
recommended
that
opening
and
closing
times
be
checked
by
use
of
a
cycle
counter
,
time
-
travel
analyzer
,
'
oscillograph
,
etc
.
,
to
monitorthe
time
from
energizing
to
arcing
contact
touch
or
part
.
*
For
measuring
circuit
breaker
speeds
,
analyzer
mounting
support
and
instructions
are
available
on
special
order
.
Circuit
breaker
closing
and
opening
times
should
be
within
the
following
time
ranges
for
normal
operation
.
5.9
OPERATING
MECHANISM
(
See
Figure
5
)
The
operating
mechanism
is
adjusted
at
the
factory
for
proper
operation
and
should
not
be
disturbed
unless
the
circuit
breaker
does
not
close
electrically
on
reclosing
duty
.
This
condition
is
caused
when
the
latch
check
switch
(
2
)
at
right
side
of
breaker
(
when
used
)
is
not
actuated
.
Circuit
breaker
should
not
close
before
trip
latch
(
4
)
has
reset
.
Latch
-
check
switch
adjustments
made
with
latch
(
4
)
against
stop
pin
(
3
)
:
1
.
Turn
in
adjusting
screw
(
1
)
until
contacts
of
switch
(
2
)
“
break
”
as
indicated
by
an
audible
click
or
check
with
bell
ringer
.
2
.
Retract
adjusting
screw
until
switch
contacts
“
make
’
'
.
3
Rotate
adjusting
screw
one
turn
more
.
(
Adjustment
screw
is
self
-
locking
.
)
Opening
Time
Range
-
MS
**
Closing
Time
Range
-
MS
*
*
5
HK
75
,
5
HK
150
,
5
HK
250
1200
Ampere
5
HK
150
and
5
HK
250
2000
Ampere
5
HK
350
,
1200
and
2000
3000
Ampere
50
-
90
23
-
35
60
-
95
23
-
35
50
-
90
65
-
95
23
-
35
23
-
35
*
*
At
125
Vdc
-
times
at
other
voltages
may
vary
slightly
.
NOTE
:
5
HK
250
,
80
/
kA
/
hiqh
momentary
,
same
as
5
HK
350
,
1200
and
2000
Ampere
,
in
table
above
.
NOTE
:
Below
0
°
C
,
the
closing
times
will
increase
(
but
with
no
reduction
in
closing
force
)
;
and
opening
times
will
be
within
the
limits
.
Adjustments
to
correct
speeds
,
if
found
to
be
outside
limits
,
are
critical
and
the
nearest
district
office
should
be
contacted
for
recommendations
.
Courtesy of NationalSwitchgear.com

IB
6.2
.
1.7
D
Page
10
ASEA
BROWN
BOVERI
©
@
\
A
"
O
IKVCR
iQ
)
'
OPENING
THE
R
.
H
.
HOUSING
PADLOCK
LOCKOUT
PLATT
-
4
Fig
.
7
—
Racking
Mechanism
Fig
.
5
—
Latch
Check
Switch
Adjustment
5.10
CONTROL
RELAY
ADJUSTMENT
(
See
Figure
6
)
The
control
relay
does
not
normally
require
any
adjustment
in
the
field
.
The
gap
between
the
control
device
lever
and
the
limit
switch
crank
should
be
between
0.06
"
and
0.09
"
with
the
closing
springs
charged
.
If
the
gap
measurement
is
incorrect
adjust
all
5
HK
circuit
breakers
except
5
HK
350
,
3000
by
shimming
either
at
the
lever
bracket
or
the
control
device
mounting
screws
as
illustrated
in
Figure
6
.
Before
changing
shims
at
the
two
control
device
screws
,
loosen
all
three
screws
,
replace
shims
and
then
tighten
all
three
screws
.
The
5
HK
350
,
3000
is
adjusted
by
means
of
an
adjusting
head
screw
fastened
to
the
lever
.
tioned
properly
,
which
should
be
corrected
as
follows
1
.
Remove
the
front
mechanism
coverplate
.
2
.
With
circuit
breaker
closed
,
make
adjustments
by
regu
-
lating
length
of
connecting
rod
(
1
)
for
1
/
8
"
minimum
to
3
/
16
"
maximum
clearance
at
“
A
”
between
trip
link
(
3
)
and
block
-
ing
lever
(
2
)
.
)
5.12
LUBRICATION
The
HK
circuit
breakers
are
lubricated
during
factory
assembly
:
1
.
All
mating
surfaces
of
moving
current
-
carrying
joints
have
been
lubricated
with
NO
-
OX
-
ID
special
grade
"
A
"
grease
manufactured
by
Sanchen
Company
.
2
.
All
other
mechanism
parts
,
bearings
,
pins
,
etc
.
,
have
been
lubricated
with
ANDEROL
757
manufactured
by
Huls
America
Inc
.
(
formerly
Nuodex
,
Inc
.
)
(
ABB
No
.
71299
A
,
4
oz
.
tube
)
.
If
the
grease
should
become
contaminated
or
parts
are
replaced
,
lubrication
should
be
done
with
NO
-
OX
-
ID
or
ANDEROLgrease
as
applicable
.
Use
of
othergreases
have
not
been
proven
by
test
and
are
not
recommended
.
NOTES
:
1
.
Do
not
use
NO
-
OX
-
ID
grease
on
any
main
and
moving
contact
surfaces
.
2
.
It
is
recommended
that
the
primary
disconnects
be
maintained
by
renewing
with
the
NO
-
OX
-
ID
grease
during
maintenance
periods
.
3
.
Do
not
use
light
oil
to
lubricate
any
mechanism
parts
.
In
emergency
situations
,
Anderol
732
may
be
used
as
a
temporary
lubricant
.
In
these
cases
,
allow
time
for
the
solvents
to
evaporate
prior
to
any
mechanical
operations
.
It
is
mandatory
that
the
breaker
undergo
thorough
lubrication
with
Anderol
757
at
the
next
maintenance
interval
.
Use
of
solvents
to
free
contaminated
lubricant
is
strictly
forbidden
without
immediate
relubrication
using
Anderol
757
.
Note
that
bearing
surfaces
must
be
repacked
and
this
will
require
disassembly
of
the
mechanism
.
Do
not
operate
the
circuit
breaker
without
completing
this
procedure
.
4
.
The
charging
motor
is
sealed
and
no
lubrication
is
required
.
SHIM
IF
REQUIRED
CONTROL
PAN
I
fff
"
~
~
Lli
I
'
LEVER LEVER
PIVOT
BRACKET
CONTROL
DEVICE
LIMIT
SWITCH
CRANK
Fig
.
6
—
Control
Relay
5.11
RACKING
MECHANISM
(
See
Figure
7
)
The
circuit
breaker
racking
mechanism
is
adjusted
at
the
factory
and
should
not
be
disturbed
unless
it
becomes
possible
to
close
the
breaker
during
a
racking
operation
.
If
it
is
possible
to
close
breaker
during
a
racking
operation
,
it
may
be
that
interlocked
blocking
members
are
not
posi
-
Courtesy of NationalSwitchgear.com

Aim
MWIP
IB
6.2
.
1.7
D
Page
11
ASEA
BROWN
BOVERI
5.13
DIELECTRIC
TESTS
If
it
is
desired
to
make
dielectric
tests
during
maintenance
periods
,
the
following
test
values
should
be
used
.
These
are
to
be
applied for
a
one
-
minute
period
.
TABLE
3
DIELECTRIC
TEST
VALUES
5.15
ELECTRICAL
CHARACTERISTICS
OF
CONTROL
DEVICES
For
operating
voltage
ranges
for
various
nominal
control
voltages
refer
to
Table
4
,
Operating
Voltage
Ranges
.
For
average
current
values
at
various
nominal
control
voltages
,
referto
Table
5
,
Average
Current
Values
.
Current
values
given
in
this
table
are
average
,
steady
-
state
values
and
momentary
inrush
currents
for
all
charging
motors
and
AC
coils
are
approximately
six
to
eight
times
these
values
.
Circuit
60
Hz
Primary
Ciruit
11.5
kV
‘
Secondary
Circuit
1100
V
"
It
is
necessary
that
the
changing
motor
be
disconnected
for
this
test
by
turning
the
motor
disconnect
switch
to
the
"
OFF
"
position
.
If
a
test
is
desired
on
the
motor
,
then
the
motor
disconnect
switch
should
be
turned
to
the
"
ON
"
position
and
the
circuit
retested
at
540
V
,
60
Hz
.
TABLE
4
OPERATING VOLTAGE
RANGE
Undervoltage
Spring
Charging
Motor
Nominal
Control
Voltage
Close
Pick
up
Maximum
Trip
Coil
DropOut
Coil
18
-
28
35
-
50
90
-
130
180
-
260
95
-
125
190
-
250
7
-
14
24
Vdc
48
V
dc
125
Vdc
250
Vdc
115
V
dc
230
Vdc
21
14
-
30
28
-
60
70
-
140
140
-
280
*
95
-
125
*
190
-
250
35
-
50
90
-
130
180
-
260
95
-
125
190
-
250
15
-
29
38
-
75
75
-
150
34
-
69
69
-
138
41
5.14
TROUBLESHOOTING
The
following
chart
lists
typical
problems
,
their
causes
and
corrective
action
required
to
remedy
the
malfunction
.
TROUBLESHOOTING
CHART
106
212
97
195
Problem
Breaker
Fails
to
Close
Probable
Cause
Corrective
Action
Low
or
Incorrect
Control
Voltage
Adjust
to
proper
Level
Closing
Springs
Not
Charged
Control
Relay
Limit
switch
out
of
Adjustment
Adjust
per
section
5.10
TABLE
5
AVERAGE
CURRENT
VALUES
Breaker
is
not
Racked
into
Test
or
Connected
Position
Turn
operating
crank
clockwise
until
lever
is
locked
into
the
desired
position
Nominal
Control
Voltage
Spring
Charging
Motor
Trip
Lockout
Close
Under
-
Voltage
N
.
E
.
C
.
Fuse
Coil
Coil
Coil
Latch
Check
Switch
not
Making
(
When
Supplied
)
Adjust
per
Section
5.9
24
Vdc
48
V
dc
125
Vdc
250
Vdc
115
Vdc
230
Vdc
0.30
22.0
22.0
0.9
30
10.7
0.15
25.0
10.7
0.5
30
Auxiliary
Switch
t
)
"
Contact
not
making
Determine
cause
and
0.06
5.0
10.0
5.0
0.2
30
0.03
2.2
5.0
2.2
0.1
30
*
4.5
0.40
10.0
4.5
02
30
Racking
Release
Lever
Linkage
not
property
adjusted
Adjust
per
section
5.11
*
2.3
0.20
5.0
2.3
0.1
30
Excessive
Friction
Insufficient
or
contaminated
lubrication
(
see
section
5.12
)
*
Alternating
current
is
never
recommended
because
the
control
power
is
affected
by
the
power
system
that
it
is
protecting
.
A
sufficient
reduction
in
control
power
during
a
heavy
fault
condition
could
prevent
the
HK
circuit
breaker
from
opening
,
leading
to
loss
of
total
load
and
/
or
equipment
damage
.
"
Y
“
Contact
not
Making
*
Defective
"
Y
"
coil
curcuit
Undervoltage
not
operating
(
When
Supplied
)
Low
or
improper
Voltage
applied
Defective
Close
Coil
Assembly
Replace
close
coil
assembly
Breaker
Faite
to
Low
or
Incorrect
Control
Voltage
Adjust
to
proper
level
Trip
Auxiliary
Switch
“
a
"
Contact
not
Making
Determine
cause
and
repair
Section
6
.
ELECTRICAL
OPERATING
SEQUENCE
Please
refer
to
the
specific
schematic
diagrams
and
other
operational
information
furnished
with
your
order
.
Figure
8
is
provided
as
a
typical
schematic
for
general
information
on
electrical
operation
with
dc
closing
.
Figure
9
is
provided
as
a
typical
schematic
for
general
information
on
electrical
operation
for
HK
breakers
with
ac
closing
.
The
following
is
the
sequence
of
electrical
opera
-
tion
with
ac
closing
.
Defective
Trip
Coil
Assembly
Replace
trip
coil
Assembly
Excessive
Friction
Insufficient
or
Contaminated
Lubrication
(
See
Sec
.
5.12
)
*
Caution
-
Improper
"
Y
”
circuit
operation
could
permit
the
breaker
to
pump
to
destruction
.
Courtesy of NationalSwitchgear.com

IB
6.2
.
1.7
D
Page
12
ABB
ASEA
BROWN
BOVERI
With
the
circuit
breaker
open
,
the
closing
springs
un
-
charged
,
and
the
control
power
source
energized
across
disconnects
5
and
02
and
01
and
6
and
motor
disconnect
switch
closed
,
operation
occurs
as
follows
:
1
.
Immediately
upon
the
availability
of
control
power
at
secondary
disconnects
“
5
”
and
“
02
"
the
spring
charging
motor
(
MOT
)
is
energized
,
which
,
in
turn
,
charges
the
closing
springs
.
When
the
closing
springs
are
charged
,
limit
switch
contacts
“
LSb
”
are
opened
,
and
limit
switch
contact
“
LSa
”
is
closed
.
Also
,
upon
availability
of
control
power
at
secondary
disconnects
“
01
"
and
“
6
”
and
after
the
closing
springs
have
been
charged
,
the
lockout
relay
coil
(
Y
)
will
be
energized
through
the
circuit
breaker
auxiliary
switch
“
b
”
contact
and
the
parallel
resistors
R
2
and
R
3
.
The
lockout
relay
will
pick
up
and
open
contact
“
Yb
”
and
close
contact
“
Ya
”
.
2
.
Connecting
secondary
disconnects
“
03
”
or
7
”
to
control
via
operation
of
the
close
control
switch
energizes
the
latch
release
coil
(
X
)
through
the
circuit
breaker
auxiliary
switch
“
b
”
contact
,
the
normally
open
lockout
relay
contact
"
Ya
”
,
and
the
limit
switch
contact
“
LSa
”
.
The
latch
release
coil
(
X
)
releases
the
closing
latch
.
The
springs
then
discharge
to
close
the
Circuit
breaker
.
3
.
When
the
springs
discharge
,
limit
switch
contacts
“
LSb
”
close
,
and
limit
switch
contact
"
LSa
”
opens
.
4
.
When
limit
switch
contact
“
LSb
”
in
the
motor
circuit
closes
,
the
spring
charging
motor
is
energized
,
which
,
in
turn
,
recharges
the
closing
springs
.
5
.
When
the
circuit
breaker
closes
,
all
auxiliary
switch
“
b
”
contacts
open
and
all
auxiliary
switch
“
a
”
contacts
close
.
*
6
.
When
limit
switch
contacts
“
LSb
”
close
,
the
lock
-
out
relay
coil
(
Y
)
is
de
-
energized
and
opens
lockout
relay
contact
“
Ya
”
,
which
de
-
energizes
the
latch
release
coil
(
X
)
.
Lockout
relay
contact
“
Yb
”
closes
,
which
locks
out
the
lockout
coil
(
Y
)
as
long
as
the
“
Close
”
contact
is
maintained
.
This
is
true
because
control
power
maintained
on
secon
-
dary
disconnects
“
03
”
or
“
7
”
with
“
Yb
”
contact
closed
puts
resistor
R
1
in
parallel
with
the
“
Y
”
coil
.
The
additional
current
flow
through
R
2
and
R
3
,
and
the
associated
in
-
creased
voltage
drop
across
R
2
and
R
3
leaves
insufficient
voltage
to
pick
up
the
lockout
relay
The
purpose
of
the
lockout
relay
coil
(
Y
)
is
to
prevent
pumping
of
the
closing
mechanism
when
closing
against
a
faulted
circuit
.
7
.
After
the
breaker
has
closed
and
when
the
closing
control
switch
is
released
by
the
operator
,
the
lockout
relay
coil
(
Y
)
remains
de
-
energized
due
to
the
auxiliary
switch
“
b
”
con
-
tact
in
the
closing
circuit
being
open
.
8
.
The
circuit
breaker
can
be
tripped
by
operation
of
a
remote
trip
switch
,
which
energized
the
circuit
breaker
trip
coil
(
TC
)
through
the
auxiliary
switch
“
a
”
contact
.
9
.
The
undervoltage
device
,
if
furnished
,
provides
a
direct
acting
lock
-
open
and
undervoltage
tripping
feature
.
This
device
must
be
energized
to
intitially
close
the
breaker
,
and
also
to
maintain
the
breaker
in
a
closed
position
.
10
.
The
latch
check
switch
,
if
furnished
,
ensures
that
the
operating
mechanism
must
be
reset
prior
to
energizing
the
closing
latch
release
coil
(
X
)
.
11
.
The
remote
mounted
capacitor
trip
feature
,
if
furnished
,
provides
an
electrical
energy
storage
network
,
whereby
should
a
loss
of
control
power
occur
at
the
instant
of
a
tripping
signal
,
sufficient
energy
will
be
furnished
to
ensure
an
electrical
tripping
operation
.
12
.
The
stopping
device
switch
,
if
applicable
,
prevents
electrical
reclosing
of
thecircuit
breaker
after
a
manual
trip
until
the
stopping
device
switch
has
been
manually
reset
.
When
AC
closing
control
power
is
supplied
,
the
circuit
breaker
will
not
reclose
unless
the
reclosing
circuit
has
sufficient
time
delay
to
permit
the
“
Y
”
coil
to
pick
up
.
Operation
of
accessories
,
when
installed
as
ordered
,
can
affect
electrical
/
mechanical
operations
of
the
circuit
breaker
when
the
circuit
breaker
is
being
tested
electrically
or
mechanically
,
undervoltage
devices
should
be
energized
or
otherwise
mechanically
closed
and
mecnanical
inter
-
locks
,
key
or
other
,
should
he
set
in
the
“
operate
”
position
.
Section
7
.
GROUND
AND
TEST
DEVICES
These
devices
are
supplied
when
ordered
and
are
basi
-
cally
three
design
types
,
with
certain
component
variations
such
as
test
ports
and
interlocks
.
-
Simple
,
three
-
terminal
,
non
automatic
.
-
Simple
,
three
-
terminal
,
electrically
operated
.
-
Complex
,
six
-
terminal
,
electrically
operated
with
manual
selector
switch
.
These
devices
are
basically
maintenance
free
for
their
normal
operating
life
.
Racking
procedure
is
the
same
as
for
the
basic
circuit
breaker
as
outlined
previously
,
and
all
detailed
operational
instructions
are
attached
to
the
individ
-
ual
devices
.
Courtesy of NationalSwitchgear.com

IB
6.2
.
1.7
D
Page
13
A
»
11
MIPIP
ASEA
BROWN
BOVERI
Section
8
.
RENEWAL
PARTS
Asea
Brown
Boveri
recommends
only
those
renewal
parts
be
stocked
that
will
be
required
to
ensure
proper
and
timely
maintenance
for
normal
operation
of
HK
circuit
breakers
.
Copies
of
the
applicable
Renewal
Parts
Bulletin
for
specific
circuit
breakers
will
he
furnished
on
request
to
the
nearest
district
office
.
The
minimum
quantity
of
assemblies
and
items
recmmended
in
these
bulletins
are
predicated
on
infre
-
quent
replacement
of
parts
based
on
accumulated
test
and
operating
experience
.
Total
assemblies
are
recommended
forfast
replacement
,
when
necessary
,
to
return
the
breaker
to
service
as
quickly
as
possible
.
Then
certain
replaced
assemblies
,
such
as
the
stationary
upper
terminals
,
can
be
returned
to
the
factory
for
nominal
reconditioning
.
The
bulletins
contain
specific
part
-
ordering
instructions
.
Spe
-
cific
instructions
regarding
replacement
of
those
part
as
-
semblies
recommended
are
available
if
required
.
Courtesy of NationalSwitchgear.com
This manual suits for next models
3
Table of contents
Other ABB Circuit Breaker manuals
Popular Circuit Breaker manuals by other brands

TERASAKI
TERASAKI TemBreak 2 E125 instruction manual

Siemens
Siemens FSV Instructions, Installation, Operation, Maintenance

OEZ
OEZ FH00-3 Series Instructions for use

Eaton
Eaton VCP-TL Series Instructions for the Use, Operation and Maintenance

Allen-Bradley
Allen-Bradley 140G-NS Installation

Eaton
Eaton Bussmann Series installation manual