
Tel: (888) 552-6467 Fax: (800) 316-4515 11/22 750.2189 Rev. B
11/12
EMIU 1500W Mini Inverter
TROUBLESHOOTING GUIDE
STATUS
INDICATOR
(LED)
TROUBLESHOOTING GUIDE
SYMPTOMS PROBLEM CORRECTIVE ACTION
LED GREEN
ON Steady, not
flashing
Lamp load is ON None, if unit is in Normally ON
mode. Unit is operating correctly.
Lamp load is OFF None, if unit is in Normally OFF
mode. Unit is operating correctly.
Lamp load is OFF, but the
unit is in Normally ON
mode
Output fuses burned out.
- Verify output is not overloaded.
- Verify there is no short circuit in the load.
- Replace fuses.
Inverter module output fuse burnt
out.
Check field wiring on mini-inverter. Ensure no voltage is being
applied to the output of the mini-inverter. Replace fuse.
-Lamp load is OFF (if
installation is Normally OFF)
-Lamp load is ON (if
installation is Normally ON)
Power at primary AC input +
battery discharged (at LVD) + no
reaction with test button.
- Remove primary AC input + disconnect
battery + wait minimum 10 seconds.
- connect battery + connect primary AC input.
=> unit will restart.
- if unit did not restart, call technical support at 1-(888) 552-6467.
LED flashing
GREEN/
ORANGE
Lamp load is ON None, if unit is in Normally ON
mode +Nexus option.
Unit is operating correctly. Unit is not commissioned to the Nexus
system.
Lamp load is OFF None, if unit is in Normally OFF
mode +Nexus option.
Unit is operating correctly. Unit is not commissioned to the Nexus
system.
LED flashing
GREEN/OFF
Lamp load is ON None, if unit is in test mode or is
sampling load. Unit is operating correctly.
Lamp load is OFF
Output fuses burned out.
- Verify output is not overloaded.
- Verify there is no short circuit in the load.
- Replace fuses.
Inverter module output fuse burnt
out.
Check field wiring on mini-inverter. Ensure no voltage is being
applied to the output of the mini-inverter. Replace fuse.
LED steady
OFF, not
flashing
Lamp load is ON No power at primary AC input + in
emergency mode. Check position of breaker feeding the Mini Inverter in the breaker
panel. If breaker has tripped, check for overload or short circuit.
See “AC SPECS” on page 1.
Lamp load is OFF
No power at primary AC input +
emergency mode stop (battery
discharged).
-Lamp load is OFF (if
installation is Normally
OFF)
-Lamp load is ON (if
installation is Normally ON)
Power at primary AC input +
battery discharged (at LVD) + no
reaction with test button.
- Remove primary AC input + disconnect
battery + wait minimum 10 seconds.
- connect battery + connect primary AC input.
=> the unit will restart.
- if unit did not restart, call for technical support at 1-(888) 552-6467.
LED RED
steady ON +
GREEN LED
on PCBA
charger board
steady ON
Inverter Error
In emergency or in test, no output
(Inverter switch OFF).
Turn inverter ON/OFF switch to ON position.
(Switch is located on right end of inverter module.)
In emergency or in test, no output
(Inverter Failure).
Check inverter control RJ12/RJ50 cable to make sure cable it is
properly connected.
In emergency or in test, output OK
(Inverter Sensing defect). Check if yellow wire is connected. If not, connect. Refer to figure 4.
In emergency or in test, no output
(Inverter Failure).
Reset system (see page 7). If result is the same, replace inverter
module.
Over temperature in emergency
or in test.
- Verify LED Over Temp/Fault is ON on the inverter.
- Verify fan is blocked or not working.
- Call technical support at 1-(888) 552-6467.
Over load in emergency or in test.
- Verify LED Overload/Fault is ON on the inverter.
- make sure the total load connected does not exceed the units
rated capacity. See note on page 1 above warranty information.