3. Protections functions
The IED features, three-phase, multi-slope
transformer differential protection with an
instantaneous stage and a stabilized (biased)
stage to provide fast and selective protection
for phase-to-phase, winding interturn and
bushing flash-over faults. Besides second
harmonic restraint an advanced waveform-
based blocking algorithm ensures stability at
transformer energization and a fifth harmonic
restraint function ensures good protection
stability at moderate overexcitation of power
transformers. Sensitive restricted earth-fault
protection (REF) completes the overall
differential protection to detect even single
phase-to-earth faults close to the neutral
earthing point of the transformer. Either the
conventional high-impedance scheme or a
numerical low-impedance scheme can be
selected for protection of the windings. When
the low-impedance REF protection is used
neither stabilizing resistors nor varistors are
needed and as a further benefit the
transforming ratio of the neutral earthing CTs
can differ from those of the phase current
transformers. Due to its unit protection
character and absolute selectivity REF does
not need time grading with other protection
schemes, and therefore high-speed fault
clearance can be achieved.
The IED also incorporates a thermal overload
protection function, which supervises the
thermal stress of the transformer windings to
prevent an accelerated aging of the winding's
insulation. Multiple stages of short-circuit,
phase-overcurrent, negative-phase-sequence
and earth-fault back-up protection are
separately available for both windings. Earth-
fault protection based on the measured or
calculated residual overvoltage is also
available. Finally, the IED also offers circuit-
breaker failure protection.
Enhanced with optional hardware and
software, the IED also features three light
detection channels for arc fault protection of
the circuit breaker, busbar and cable
compartment of metal-enclosed indoor
switchgear.
The arc-fault protection sensor interface is
available on the optional communication
module. Fast tripping increases personal
safety and limits material damage within the
switchgear in an arc fault situation.