
SYSTEM OPERATION
15 Rev 1
COOLING
The refrigerant used in the system is R-22. It is a clear,
colorless, non-toxic, non-irritating, and non-explosive liquid.
The chemical formula is CHCLF2. The boiling point, at
atmospheric pressure is -41.4°F.
A few of the important principles that make the refrigeration
cycle possible are: heat always flows from a warmer to a
cooler body. Under lower pressure, a refrigerant will absorb
heat and vaporize at a low temperature, the vapors may be
drawn off and condensed at a higher pressure and tempera-
ture to be used again.
The indoor evaporator coil functions to cool and dehumidify
the air conditioned spaces through the evaporative process
taking place within the coil tubes.
NOTE: The pressures and temperatures shown in the
refrigerant cycle illustrations on the following pages are for
demonstration purposes only. Actual temperatures and
pressures are to be obtained from the "Expanded Perfor-
mance Chart."
Liquid refrigerant at condensing pressure and tempera-
tures, (270 psig and 122°F), leaves the outdoor condensing
coil through the drier and is metered into the indoor coil
through the metering device. As the cool, low pressure,
saturated refrigerant enters the tubes of the indoor coil, a
portion of the liquid immediately vaporizes. It continues to
soak up heat and vaporizes as it proceeds through the coil,
cooling the indoor coil down to about 48°F.
Heat is continually being transferred to the cool fins and
tubes of the indoor evaporator coil by the warm system air.
This warming process causes the refrigerant to boil. The
heat removed from the air is carried off by the vapor.
As the vapor passes through the last tubes of the coil, it
becomes superheated, that is, it absorbs more heat than is
necessary to vaporize it. This is assurance that only dry gas
will reach the compressor. Liquid reaching the compressor
can weaken or break compressor valves.
The compressor increases the pressure of the gas, thus
adding more heat, and discharges hot, high pressure super-
heated gas into the outdoor condenser coil.
In the condenser coil, the hot refrigerant gas, being warmer
than the outdoor air, first loses its superheat by heat trans-
ferred from the gas through the tubes and fins of the coil. The
refrigerant now becomes saturated, part liquid, part vapor
and then continues to give up heat until it condenses to a
liquid alone. Once the vapor is fully liquefied, it continues to
give up heat which subcools the liquid, and it is ready to
repeat the cycle.
HEATING
The heating portion of the refrigeration cycle is similar to the
cooling cycle. By energizing the reversing valve solenoid
coil, the flow of the refrigerant is reversed. The indoor coil
now becomes the condenser coil, and the outdoor coil
becomes the evaporator coil.
The check valve at the indoor coil will open by the flow of
refrigerant letting the now condensed liquid refrigerant by-
pass the indoor expansion device. The check valve at the
outdoor coil will be forced closed by the refrigerant flow,
thereby utilizing the outdoor expansion device.
The restrictor orifice used with the CCA-F, CCH-F and BHA-
F coils will be forced onto a seat when running in the cooling
cycle, only allowing liquid refrigerant to pass through the
orifice opening. In the heating cycle it will be forced off the
seat allowing liquid to flow around the restrictor. A check
valve is not required in this circuit.
COOLING CYCLE
When the contacts of the room thermostat close making
terminals R to Y & G, the low voltage circuit of the trans-
former is completed. Current now flows through the mag-
netic holding coils of the compressor contactor (CC) and fan
relay (RFC).
This draws in the normally open contact CC, starting the
compressor and condenser fan motors. At the same time
contacts RFC close starting the indoor fan motor.
When the thermostat is satisfied, it opens its contacts,
breaking the low voltage circuit, causing the compressor
contactor and indoor fan relay to open, shutting down the
system.
If the room thermostat fan selector switch should be set on
the "on" position, then the indoor blower would run continu-
ous rather than cycling with the compressor.
RHA, RHD, RHE, & RHF models energize the reversing
valve thorough the "O" circuit in the room thermostat.
Therefore the reversing valve remains energized as long as
the thermostat subbase is in the cooling position. The only
exception to this is during defrost.
DEFROST CYCLE
The defrosting of the outdoor coil is jointly controlled by the
defrost timing board, defrost (30/60) control, and compres-
sor run time.
HEATING CYCLE
The RHA, RHD, RHE, & RHF model heat pumps use a
different control circuit than preceding heat pump models.
These models do not use a reversing relay to energize the
reversing valve. Also many previous models energized the
reversing valve off the "B" terminal on the thermostat, and all
previous models energized the reversing valve in the heat-
ing cycle.
The reversing valve on the RHA, RHD, RHE & RHF models
is energized in the cooling cycle thorough the "O" terminal on
the room thermostat.
These models have a 24 volt reversing valve coil. When the
thermostat selector switch is set in the cooling position, the
"O" terminal on the thermostat is energized all the time.
Care must be taken when selecting a room thermostat.
Refer to the installation instructions shipped with the product
for approved thermostats.