Received Received
Interrupted Interrupted
ON ON
OFF OFF
ON ON
OFF OFF
• In case of the through-beam type, to prevent malfunction, output of units keeps the state of OFF
for 0.5 sec after power ON.
Received Ta
Interrupted
ON tTtT
OFF
ON
OFF
• T: Setting time by the adjuster (setting time: 0.1 to 2 sec)
• t: ≤ 3 ms (When the adjuster is set to Min (0.1 sec))
• If the interrupted time (Ta) after receiving the light is shorter than the setting time (T),
the transistor output maintains the ON state.
• In case of the built-in timer model, you can set the OFF Delay timer.
(adjustable time: 0.1 to 2 sec)
• Use the oered adjustment screwdriver. Do NOT turn with excessive force to prevent product
damage.
Min. Max.
• Be sure to install this product by following the usage environment, location, and specied
ratings. Consider the listed conditions below.
- Installation environment and background (reected light)
- Sensing distance and sensing target
- Direction of target’s movement
- Characteristic curves
• When installing multiple sensors closely, it may result in malfunction due to mutual
interference.
• For installation, tighten the screw with a torque of 0.5 N m. Mount the brackets correctly to
prevent the twisting of the sensor’s optical axis.
• Do not impact with a hard object or bend the cable excessively. That could decrease the
product’s water resistance.
• Use this product after the test. Check whether the indicator works appropriately for the
positions of the detectable object.
Emitter - Receiver:
Install to face each other
Sensor - Sensing target:
Install to face each other (parallel with the
sensing side of the unit)
• Bracket B
• M12 connector cable: C□D(H)4-□-□
• Slit for through-beam type: BYD3M-ST (sticker)
This is only for reference, the actual product does not support all combinations.
For selecting the specied model, follow the Autonics website.
BYD - ---
Number: Sensing distance (unit: mm)
Number+M: Sensing distance (unit: m)
No mark: Cable type
W: Cable connector type
T: Through-beam
D: Diuse reective
D: Convergent reective
No mark: NPN open collector output
P: PNP open collector output
(Through-beam type)
D: 12 - 24 VDCᜡ
No mark: Front operation indicator
U: Upper operation indicator
T: Built-in timer (OFF delay mode)
T: Solid state (transistor)
2
3
1
4
Pin Color Function
Brown +V
- -
Blue 0 V
Black OUT
• Connector pin ④ is N.C (not connected) terminal
for the emitter.
Connections
• Emitter
(BYD3M-TDT1-□)
• Receiver (BYD3M-TDT2-□)
12-24 VDCᜡ
Brown
Blue 01)
12-24 VDCᜡ
LOAD
Brown
Black
Blue
Max. 100 mA
12-24 VDCᜡ
LOAD
Brown
Black
Blue
01) Through-beam type: max. 100 mA, diuse reective or convergent reective type: max. 50 mA
Sensitivity Adjustment
• Set the adjuster for stable Light ON area, minimizing the eect of the installation environment.
• Use the oered adjustment screwdriver. Do NOT turn with excessive force to prevent
product damage.
• The steps below are based on Light ON mode.
STEP Status
01 Received
Turn the adjuster from MIN to MAX sensitivity and
check the position (A) where the operation indicator
activates under the light ON area.
02 Interrupted
Turn the adjuster from (A) to MAX and check the
position (B) where the operation indicator activates
under the light OFF area.
If the operation indicator does NOT activate at the
MAX (maximum sensitivity): MAX = (B).
03 -Set the adjuster at the mid position between (A) and
(B) for optimal sensitivity.
Dimensions
• Unit: mm, For the detailed drawings, follow the Autonics website.
• This dimensions shows the cable type.
Refer to the ‘Specications’ for the core, wiring and connector.
12.4
32
18
2-Ø3.4
26
3
C
B
B
12.4
32
17 4
Ø3.5, 2m Ø3.5, 2m
A
Through-beam Diffuse reflective,
Convergent reflective
AOptical axis
BUpper operation indicator of convergent reective type (red)
CSensitivity adjustment adjuster or timer adjuster of built-in timer model
Bracket A
14
20
66
8
6
C4
1.2
25
21.5
12
10°
4
35
R26
Circuit
CIRCUIT
LOAD
OCP
SCP
01)
CIRCUIT
LOAD
OCP
SCP Max. 100 mA
01) Through-beam type: max. 100mA, diuse reective or convergent reective type: max. 50 mA
• OCP (over current protection), SCP (short circuit protection)
• If short-circuit the control output terminal or supply current over the rated specication, normal control signal is
not output due to the protection circuit.