AXE MCH Series User manual

Rev.1.2
AXE
6 DIGIT HIGH SPEED MICROPROCESS COUNTER
MCH series
■FEATURES
◎Accept more type sensors(switch, encoder, proximity switch
,…etc)finish length/flow control ◎16BIT DAC analog output can be modified
◎Readout Range from -999999~999999 ◎Seven alarm control mode (N/F/R/Q/C/P/K) can be modified
◎Seven counting modes:Front/after edge,Up,Down,Up/Down,
direct-Up/Down ,Quadrature-Up/Down can be modified ◎RS485 Communication interface, Protocol MODBUS RTU
MODE
◎Power down saving ◎BAUD RATE:38400/19200/9600/4800/2400
◎Decimal point can be modified ◎0.56”highlight display
◎Input scaling multiplied 0.00001~9.99999 can be modified ◎Man-machine interface, easy to operate
◎Reset by panel or connect terminal ◎EEPROM Saving, data safekeeping about 10 years
◎Quadrature sensing up to 4 times resolution ◎Modified inside parameter, must have pass code
■Name of Parts
■Connect Diagram
■
Input function jumper table
◎Contact input (PNP) ◎Sensor input (PNP 5V/12V)
◎Contact input (NPN) ◎Sensor input (NPN 5V/12V) Position 1 ON:IN(B) NPN
Position 3 ON:IN(A) NPN
Key Introduce Operation Manual
Key Function1.In normal display, The key function is call out setting group
2.In parameter setting page, The key function is data Enter , and go to next page
Key Function1.In normal display, The key function is call out alarm value setting page
2.Into parameter setting page, the parameter mark & data is alternate display, If need modify data
can press shift key into setting procedure, The display is lock parameter data, this time must let off
key about 0.2 sec, press again, the cursor(twinkle express)is cycle moving left. (Key Response
about 0.2 sec)
Set
-
value up(Scale adjustment call out )
Set
-
value down
(Analog output adjustment call out)
Cursor shift
(
Alarm adjustment call out
)
Parameter E
nter
(
Function call out
)
Alarm Indicate
燈
Communication
Indicate
Polar
Indicate
Display Reset
POL
DIO
AL1
AL2
Display
A-ADJ
R
ST
SCALE
ALARM
FUNC
ENT
EN
COM
IN
12V
Inside jumper
1
2
3
4
OFF
O
FF
OFF
OFF
Sensor
COM
IN
12V
Inside jumper
1
2
3
4
ON
OFF
O
N
OFF
Sensor
1
2
3
4
COM
IN
12V
Inside jumper
1
2
3
4
OFF
O
FF
O
FF
OFF
COM
IN
12V
Inside jumper
1
2
3
4
ON
OFF
ON
OFF

Rev.1.2
Key Function1.In normal display, The key function is call out adjustment display scale page
2.Into parameter setting page, the parameter mark & data is alternate display, If need modify data
can press up key into setting procedure, The display is lock parameter data, this time must let off
key about 0.2 sec, press again, the parameter data will increment. (Key Response about 0.2 sec)
Key Function1.In normal display, The key function is call out adjustment analog output AZERO&ASPAN page
2.Into parameter setting page, the parameter mark & data is alternate display, If need modify data
can press down key into setting procedure, The display is lock parameter data, this time must let off
key about 0.2 sec, press again the parameter data will decrement. (Key Response about 0.2 sec)
& Key Function 1.In setting group or setting page press & key return normal display, but if in setting page the
modify data will be lost
No Key in anything 1.In setting group or setting page no key in anything about 2 minutes, return normal display, b
ut if in
Setting page the modify data will be lost
Step
Parameter mark description
Parameter mark
Operation manual
1
Normal display
Press /FUNC key into P.COD setting page
2
P.COD(Pass code input page)
1.Key in 6 digit pass code with or or key
2.Press key,the pass code is right into setting group,otherwise return
normal display
3
SYS(System setting group)
ROP(Alarm setting group)
AOP(Analog output setting
group)
DOP(Communication setting
group)
1.Select setting group with key
2.Press key into setting page of selection setting group
4
SYS(System setting group)
Press key decide SYS setting group , press key into DP setting
page
4-1
DP(Decimal Point)
Default = 0
1.Decide decimal point position with or key(0~5)
2.Press key enter data and into TYPE setting page
4-2
TYPE(Type)
Default = 1U2G
1.Decide input type with or key (1U2G,1G2U,1D2G,1G2D
,1U2D,1P2D,1A2B)
2. Press key enter data and into CNTS setting page
4-3
CNTS(Count Rates Select)
Default = 50KHZ
1.Decide Count Rates Select with or key (50HZ,500HZ,50KHZ)
2. Press key enter data and into CODE setting page
4-4
CODE(Pass Code)
Default = 0
1.Decide pass code with or or key (0~999999)
2. Press key enter data and into LOCK setting page
4-5
LOCK(Panel Lock)
Default = NO
1. Decide panel lock with or key(NO or YES)
2. Press key enter data and return SYS setting group
5
ROP( Alarm setting group)
Press key decide ROP setting group, press key into OP.MODE
setting page
5-1
OP.MODE(Output Mode )
Default = N
1. Decide output mode with & key (N,F,R,Q,C,P,K)
2. Press key enter data and intoACT1.T setting page
5-2
ACT1.T(Active 1 Time )
Default = 0
1.Decide Active 1 Time with or or key (0.0~99.9)sec.
2. Press key enter data and intoACT2.T setting page
3.ACT1.T=0 sec. is self-holding output 1
.ACT1.T=0.1~99.9 sec. is one-shot output 1
5-3
ACT2.T(Active 2 Time )
Default = 0
1. Decide Active 2 Time with or or key (0.0~99.9)sec.
2. Press key enter data and return ROP setting group
3. ACT2.T=0 sec. is self-holding output 2
ACT2.T=0.1~99.9 sec. is one-shot output 2
6
AOP(Analog output setting
group)
Press key decide AOP setting group , press key into ANLO
setting page

Rev.1.2
6-1
ANLO(Analog Output Zero-
According to Display)
Default = 0
1. Decide ANLO with or or key (-999999~999999)
2. Press key enter data and intoANHI setting page
6-2
ANHI(Analog Output Span-
According to Display )
Default = 999999
1. Decide ANHI with or or key (-999999~999999)
2. Press key enter data and return AOP setting group
7
DOP(Communication setting
group)
Press key decide DOP setting group, press key into ADDR
setting page
7-1
ADDR(Communication –Addr
ess )
Default = 0
1.Decide address with or or key(0~255)
2.Press key enter data and into BAUD setting page
7-2
BAUD(Communication Baud
Rate)
Default = 19200
1. Decide baud rate with or key (38400,19200,9600,4800,2400)
2. Press key enter data and intoPARI setting page
7-3
PARI(Communication Parity
Check)
Default = n.8.2.
1.Decide Parity Check with or key(n.8.2.,n.8.1.,even,odd)
2.Press key enter data andreturn DOP setting group
Step
Parameter mark description
Parameter mark
Operation manual
8
Normal display
Press /ALARM key about 3 sec, into AL1setting page
8-1
AL1 (Alarm 1)
Default = 0
1. Decide alarm value 1 with or or key (0~999999)
2. Press key enter data and into AL2 setting page
8-2
AL2 (Alarm 2)
Default = 0
1. Decide alarm value 2 with or or key (0~999999)
2. Press key enter data andreturn normal display
Step
Parameter mark description
Parameter mark
Operation manual
9
Normal display
Press /SCALE key about 3 sec, into SCALE setting page
9-1
SCALE (Scale)
Default = 1
1. Decide scale with or or key (0.00001~9.99999)
2. Press key enter data and return normal display
Step
Parameter mark description
Parameter mark
Operation manual
10
Normal display
Press /A-ADJ key about 3 sec, into AZERO adjustment page
10-1
AZERO(Analog Output
Zero Adjust)
Default = 0
1. Adjustment analog output zero with or or key(±6000)
2. Press key enter data and into ASPAN adjustment page
10-2
ASPAN(Analog Output
Span Adjust)
Default = 0
1. Adjustment analog output span with or or key(±6000)
2. Press key enter data and return normal display
Appendix
Error Mark Description
Error Mark Analyze & Description
1
EEPROM error detect
1.External interference when EEPROM read/write
2.EEPROM write over 1 million times(guarantee 10 years)
Please power reset, if still display E-00, doing following step:
1.E-00 & No alternate display for inquire reset EEPROM
2.Decide Yes with or key, press key return normal display
3.EEPROM has reset, Please follow step 1~10 set again

Rev.1.2
■InputTypeandCountValue
UP(Increment)Type
1U2G(PNP) 1G2U(NPN)
IN(A):Countinput;IN(B):Prohibit(gate)input
IN(A):Prohibit(gate)input;IN(B):Countinput
DOWN(Decrement)Type
1D2G(PNP) 1G2D(NPN)
IN(A):Countinput;IN(B):Prohibit(gate)input
IN(A):Prohibit(gate)input;IN(B):Countinput
UP/DOWNType
1U2D 1P2D
1A2B(x4mode)
0
Count
value
1
2
0
3
IN(A)
H
L
IN(B)
H
L
4
5
IN(A)
H
L
IN(B)
H
L
Count
value
0
1
2
0
3
4
5
IN(A)
H
L
IN(B)
H
L
Count
value
0
n-1
n
IN(A)
H
L
IN(B)
H
L
Count
value
0
n
-
2
n
-
3
n
-
4
n
-
5
n
n-1
n
-
2
n
-
3
n-4
n-5
0
Count
value
IN(A)
H
L
IN(B)
H
L
0
1
2
3
2
1
2
3
IN(A)
H
L
IN(B)
H
L
0
1
2
3
2
1
1
2
3
0
Count
value
IN(A)
H
L
IN(B)
H
L
0
1
2
3
2
1
2
3
0
Count
value

Rev.1.2
■Alarm Output Mode Setting
Input Type
UP DOWN UP/DOWN
Operation
Description
N
The display value
continues to
increase/decrease.
The OUT1 output
are held until
Reset is input.
F
As soon as OUT1
has active,the
display value are
held until Reset is
input.
The OUT2 output
time is indepen-
dent of OUT1.
R
The display value
continues to
increase/decrease
during the OUT1
one-shot output
time.but return to
the reset start
status after the
OUT1 one-shot
output time has
elapsed.
The output repeat
OUT1 one-shot
operation.OUT2
self-holding
output
turns OFF
after the OUT1
one-shot output
time.The OUT2
one-shot output
time is indepen-
dent of OUT1.
Alarm
Output
Mode
setting
Q
The display value
return to the reset
start status after
the OUT1 one-
shot output time.
The output repeat
OUT1 one-shot
operation. OUT2
self-
holding output
turns OFF
after the OUT1
one-shot output
time.The OUT2
one-shot output
time is indepen-
dent of OUT1.
999999
AL1
AL2
0
Reset
999999
AL1
AL2
0
Reset
Reset
999999
AL1
AL2
0
Reset
OUT2
OUT1
OUT2
OUT1
0
999999
AL1
AL2
OUT2
OUT1
OUT2
OUT1

Rev.1.2
Input Type
UP DOWN UP/DOWN
Operation
Description
C
As soon as the
count reaches
AL1,the display
value return to the
reset start status
The output repeat
OUT1 one-shot
operation. OUT2
self-
holding output
turns OFF
after the
OUT1 one-shot
output time.The
OUT2 one-shot
output time is
independent of
OUT1.
P
The display value
dose not change
during the OUT1
one-shot output
time.but the actual
count return to the
reset start status.
The output repeat
OUT1 one-shot
operation. OUT2
self-
holding output
turns OFF after the
OUT1 one-shot
output time.The
OUT2 one-shot
output time is
independent of
OUT1.
Alarm
Output
Mode
setting
K
The display value
continues to
increase/decrease.
OUT2 self-
holding
output turns OFF
after the OUT1
one-shot output
time.The OUT2
one-shot output
time is
independent of
OUT1.
Note:1.Self-holding output ,One-shot output ,Self-holding output or One-shot output
2.When count value reaches 999999,it return to 0,Count value below -999999,Down mode return to AL1,Up/Down mode
return to 0
3.Counting cannot be performed during Reset input.
4. If Reset is input while one-shot output is ON, one-shot output turns OFF.
5. If there is power failure while output is ON, output will turn ON again when the power supply has recovered.
6. When count value reaches to alarm again during the One-shot output, the One-shot output time will be restart.
7. Seven alarm output mode is according to AL1 setting value
999999
AL1
AL2
0
Reset
Reset
999999
AL1
AL2
0
Reset
999999
AL1
AL2
0
OUT2
OUT1
OUT1
OUT2
OUT2
OUT1
One-shot output
Self-holding output

Rev.1.2
MCH Modbus RTU Mode Protocol Address Map
Data format 16Bit/32Bit, sign bit 8000~7FFF(-32768~32767),80000000~7FFFFFFF(-2147483648~2147483647)
Address
Name Description Accept
0000 DP Decimal Point,Input Range 0000~0005 (0~5)(0:10
0
,1:10
-1
,2:10
-2
,3:10
-3
,4:10
-4
,5:10
-5
) R/W
0001 TYPE Input Type,Input Range 0000~0006 (0:1U2G,1:1G2U,2:1D2G,3:1G2D,4:1U2D,5:1P2D,6:1A2B) R/W
0002 LOCK Panel Lock,Input Range 0000~0001 (0~1)(NO/YES) R/W
0003 OP.MODE
Output Mode,Input Range 0000~0006 (0~6)(0:N,1:F,2:R,3:Q,4:C,5:P,6:K) R/W
0004 CNTS Count Rates Select,Input Range 0000~0002 (0~2) (0:50HZ,1:500HZ,2:50KHZ) R/W
0005 ACT1.T
Active 1 Time,Input Range 0000~03E7 (0~99.9) R/W
0006 ACT2.T
Active 2 Time,Input Range 0000~03E7 (0~99.9) R/W
0007 ADDR Communication Address,Input Range 0000~00FF(0~255) R/W
0008 BAUD Communication Baud Rate,Input Range 0000~0004(0~4)( 0:38400,1:19200,2:9600,3:4800,4:2400)
R/W
0009 PARI Communication Parity Check,Input Range 0000~0003(0~3)(0:N82,1:N81,2:EVEN,3:ODD)
R/W
000A A_ZERO
Analog Output Zero Adjust,Input Range E890~1770(-6000~6000) R/W
000B A_SPAN
Analog Output Span Adjust,Input Range E890~1770(-6000~6000) R/W
000C CODE Pass Code,Input Range 00000000~000F423F(0~999999)high word R/W
000D Pass Code,Input Range 00000000~000F423F(0~999999)low word R/W
000E SCALE Scale,Input Range 00000001~000F423F(0.00001~9.99999)high word R/W
000F Scale,Input Range 00000001~000F423F(0.00001~9.99999)low word R/W
0010 ANLO Analog Output Zero According to Display,Input Range FFF0BDC1~000F423F (-999999~999999)high word
R/W
0011 Analog Output Zero According to Display,Input Range FFF0BDC1~000F423F (-999999~999999)low word R/W
0012 ANHI Analog Output Span According to Display,Input Range FFF0BDC1~000F423F (-999999~999999)high word
R/W
0013 Analog Output Span According to Display,Input Range FFF0BDC1~000F423F (-999999~999999)low word R/W
0014 AL1 Alarm 1,Input Range 00000000~000F423F (0~999999)high word R/W
0015 Alarm 1,Input Range 00000000~000F423F (0~999999)low word R/W
0016 AL2 Alarm 2,Input Range 00000000~000F423F (0~999999)high word R/W
0017 Alarm 2,Input Range 00000000~000F423F (0~999999)low word R/W
0018 DISP Display Value,Display Range FFF0BDC1~000F423F (-999999~999999)high word R
0019 Display Value,Display Range FFF0BDC1~000F423F (-999999~999999)low word R
001A STATUS
Alarm Status,Display Range 0000~0007(0~7)Bit0:AL1,Bit1:AL2(0:OFF,1:ON) R
001B RST Write = 0001(Function 06),Reset Alarm Output W
Table of contents
Other AXE Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

LINSHANG
LINSHANG LS132 user manual

Dwyer Instruments
Dwyer Instruments SCC-POT/C quick start guide

Algodue ELETTRONICA
Algodue ELETTRONICA UPM3100 manual

Konica Minolta
Konica Minolta REGIUS 110 Service manual

Gatekeeper Systems
Gatekeeper Systems NITRO 401 installation guide

PCB Piezotronics
PCB Piezotronics 356A12/NC Installation and operating manual

Honeywell Home
Honeywell Home EW130 Series Installation & user guide

Kenwood
Kenwood FL-180A instruction manual

ISKRAEMECO
ISKRAEMECO MT382 quick start guide

Hanna Instruments
Hanna Instruments HI 931100 instruction manual

Siemens
Siemens sitrans PROBE LU Quick start manual

Transfer Flow
Transfer Flow TRAX3 owner's manual