HA
ON/OFF
18. Range of Coverage
In case the sensing area of the LUXOMAT®
PD4-M-1C-C-PS is too large or areas are being covered
that should not be monitored, the range can be reduced
or limited through use of the enclosed masking clips.
19. Exclude sources of interferences
Typ SM FC FM
PD4-M-1C-C-SP (Master) 92485 92480 –
PD4-S-C (Slave) 92442 92444 92445
LUXOMAT®Remote control:
IR-PD-1C (incl. wall bracket) 92520
IR-PD-Mini 92159
Accessory:
BSK Ball basket guard 92199
Wall bracket for remote control as
replacement
92100
22. Article / Part nr. / Accessory
20.
Technical data
PD4-Master-1C-C-SP
1. If the switch-on threshold has been modified by the potentiometer
or remote control, the switch-off threshold stored in the EEPROM is
deleted and is then recalculated on the next activation.
Determining the switch-off value
1. Switch on for 5min. with dark and motion
2. Light OFF for 2 sec.
3. Internal calculation of the switch-off value
2. If the eye push button is pressed, the switch-off threshold is
recalculated. See also Remote control –> Eye section
3. Switch-off delay
If the determined switch-off threshold is exceeded during
operation, the detector only switches off after a delay of approx.
15 minutes. This compensates for any brief fluctuations in the
brightness.
14. Switch-off threshold brightness
21. Wiring diagram
Standard mode with Master 1-channel occupancy
detectors-PS with R and S terminal
walking across
walking towards
2
Sensor and power supply in one case
Power supply: 230 V~ ±10 %
Power consumption: < 1W
Ambient temperature: -25°C – +50°C
Degree of protection/class:
SM IP54, FC IP20 / II /
Settings:
locally and by remote control
Light values - IR-PD-1C:
20 - 1000 Lux
Extension of the detection area:
with Slaves
Area of coverage:
narrow detection area, ideal for
corridors
Range of coverage Ø H 2.50 m / T=18°C:
tangential 40m / radial 20 m
Mounting height:
2 - 3 m
Light measurement:
daylight + artificial light
Lux values - Potentiometer:
10 - 2000 Lux
• 1 Relay/Channel for light-connection
Type of contact:
NOC / with pretravel tungsten
contact
Contact load:
2300 W, cos ϕ=1 /
1150 VA, cos ϕ= 0.5,
µ-
Contact
Time-settings:
15 sec. - 16 min./ test with potentiometer
5 min. - 30min./ test with remote control
Dimensions H x Ø [mm]
SM FC
PD4-M-1C-C-SP 76 x 101 103 x 97
Visible portion when built into ceiling: 30x97mm
Technical data PD4-Slave-C
Power supply: 230 V~ ±10 %
Impulse output: Optocoupler max. 2 W
Impulse duration: 2 sec. or 9 sec.
Dimensions: see above
Declaration of Conformity:
The product complies with the low
voltage recommendation 2006/95/EC and the EMV recommen-
dation 2004/108/EC.
The “Corridor“ and “Light ON/OFF“ functions are mutually
exclusive. If both are activated, the detector performs the corridor
function.
The behaviour when the push button is pressed is defined
as follows:
Corridor function activated
Light ON:
Push button pressed briefly: Light OFF -> Active after 5sec.
Push button held down: Light OFF -> Active after 5 sec.
Light OFF:
Push button pressed briefly: Light ON as long as motion + Lag time
Push button held down: Light ON as long as motion + Lag time
15a. Behaviour of external push button/IR “Light“
12 h Light ON/OFF activated
Light ON:
Push button pressed briefly: Light OFF -> Active after 5sec.
Push button held down: 12 h OFF
Light OFF:
Push button pressed briefly: Light ON as long as motion + Lag time
Push button held down: 12 h ON
12 h Light ON/OFF deactivated
Light ON:
Push button pressed briefly: Light OFF as long as motion + Lag time
Push button held down: Light OFF as long as motion + Lag time
Light OFF:
Push button pressed briefly: Light ON as long as motion + Lag time
Push button held down: Light ON as long as motion + Lag time
15b. Behaviour of external push button/IR “Light“
Activation of light for 12 h via mains interruption
1. Interrupt current
2. Apply current for 2 to 5 sec.
3. Interrupt current again
4. Apply current
5. Detector is now ON for 12 h
Exiting sabotage
1. Interrupt current
2. Apply current for 30 to 60 sec.
3. Interrupt current again
4. Apply current
5. Detector is in simple closed state
230 V AC permanently at the slave input
If 230 V AC is applied at the slave input for longer than 10sec.,
the light is switched on permanently. When the 230V is removed,
the light is switched off and automatic mode is activated.
230 V AC for 1 - 3 sec. at push button connection S
If 230 V AC is applied for 1 - 3 sec. at push button connection
S, this is interpreted as a Slave signal at slave connection R. This
ensures that the detector is compatible with previous versions.
16. Other functions
Forced shutdown active
Light OFF:
Light OFF: Push button pressed briefly: Light ON for approx.
30min., then forced shutdown if the set brightness is still exceeded.
15c. Behaviour of external push button/IR
“Forced shutdown”
17. Fully-automatic and semi-automatic mode
(see functions IR-PD-1C)
Fully-automatic operation
In this operating mode, the lighting switches automatically
on and off for increased comfort, depending on presence
and brightness.
- Channel 1 switches on in the event of motion if “dark“ is
detected.
Semi-automatic operation
In this operating condition, in order to gain increased
savings, the lighting is energized only after being manually
switched on.
Switch-off takes place automatically or manually.
The semi-automatic mode basically behaves like the fully-
automatic one. However, the difference is that switching-on
must always be carried out manually!
As many (closer-contact) buttons as desired can be wired in
parallel on the “S” button input (ON/OFF).
Triggering in semi-automatic mode: If the detector switches
off in semi-automatic mode (lag timer elapsed), the detector
is switched on again within 10 sec. by motion (despite semi-
automatic mode).