Installation and Operating Instruction for
B.E.G.-Occupancy detectors
PD4-M-DIM-SM/-FC/-FM
1. Mounting preparations
Work on the 230 V mains supply
may only be carried out by quali-
fied professionals or by instructed
persons under the direction and
supervision of qualified skilled
electrical personnel in accordance
with electrical regulations.
Disconnect supply before installing!
The device is not suited for safe
disconnection of the mains supply.
When in Master/Slave mode of op-
eration, the Master-appliance must
always be installed at the location
where there is least daylight.
LUXOMAT®PD4-M-DIM
GB
4. DIP switch functions
DIP
OFF ON
1
2
3
The DIP settings are enabled again by
• Adjusting the DIP switches when closed
• Reset with test sun setting at the potentiometers
• Reset when open
Corridor function: After deactivation by an external push button, the
detector switches off and returns to automatic mode after 5sec.
Function LEDs OFF: In the open state and in test mode, the LEDs are
always ON.
3. Position DIP-switches
The DIP switch settings are
overriden using the remote
control.
Surface mounting
123
OFF ON
VA
LED
HA
COR
ONOFF
DIP
x
7. Option:
Wall bracket for remote
control IR-PDim
IR-PDim
8. Settings by remote control
Unlocking device - Activation of
the programming mode
Resetting when-
open: Deletes all
values set with
the remote con-
trol, light OFF.
or Start of the dim process
Luminance set point for
constant light control
50
Lux to 1500
Lux
1
min to 30
min
1
min to 60
min
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
or
max
50
Lux
1500
Lux
ON
OFF
9s 2s
LED ON
LED OFF
25 22
18
1
6
10
3
1
TEST 6
30
R1
120 6050
40
30
15
10
A
16 10 5
2
1
30
15
TEST
2000
1200
600
200
40
5
60
5
10
30
50
ON
OFF
112
2
25 22
18
1
6
10
3
1
TEST 6
30
R1
120 6050
40
30
15
10
A
16 10 5
2
1
30
15
TEST
2000
1200
600
200
40
5
25 22
18
1
6
10
3
1
TEST 6
30
R1
2000
1200
600
200
40
False ceiling mounting Flush mounting
123
ON
OFF
DIP
2a. Installation of the LUXOMAT®
PD4-M-DIM-SM
A circular opening of
diameter 68 mm must first
of all be produced in the
ceiling.
Having connected up the
cables in accordance with
regulations, the detector is
inserted into the opening
as shown in the drawing
opposite and fixed into
position with the assis-
tance of the spring clip.
2b. Installation of the LUXOMAT®
PD4-M-DIM-FC
The detector can be installed
in conventional inlet-sockets
mounted on the ceiling.
The assembly plate enclosed must
be stripped off prior to installa-
tion and secured to the ceiling
using four screws and ensuring
that it flat. Having connected up
the cables in accordance with
regulations, the detector can be
placed in position as shown in
the drawing opposite and, ap-
plying a little pressure, can then
be locked into position with the
assistance of the spring clips.
(Please refer to the connection
diagrams)
2c. Installation of the LUXOMAT®
PD4-M-DIM-FM
B.I.T.
Q.C.
PASSED
1
close
open
The detector must be installed
on a solid and level surface.
The circular cover ring
must be removed prior to
assembly. To do this, twist the
lens anticlockwise through
approximately 5° and lift off.
Having connected up the
wires in accordance with
regulations, secure the
detector with 2 screws. After
installation replace the lens
and lock (turn clockwise).
Mains to be connected.
max
50
Lux
1500
Lux
ON
OFF
optional optional optional
t < 5 sec.
Light on / off when closed
=> (see page 2, point 12)
Dimming in the closed state
=> (see page 2, point 11)
Test operation in the closed condition to enable
Disable the test mode: press reset
Resetting when closed
The lighting relay is switched off, i.e. opened and the follow-up times
reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illuminated). This
operating mode can only be activated during the period of 5 seconds after
pressing the “lock“ button. This status will only permit actuating the function
“Light on/Light off”. The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 - 59 seconds
3. Switch of the current again
4. Apply current
5. Open detector
Dim in the open state
To set a target value, proceed as follows (example workplace):Place one
lux meter flat on the desk. Set the light with the help of remote control IR-
PDim by pressing the buttons „max“ or „min“ for starting the dim process.
Wait until the desired light level is reached.
Conrmation by the preset value
Light during the initialization
The light is on by default in the initialization time.
On / off with the „Light“ button during Initialization. The final condition
is then active.
Follow-up time orientation light ON / OFF when open
Note:
Also during the orientation phase of the light constant light control is
active: With sufficient brightness is <20% dimmed and turned off the lights
if necessary.
max
50
Lux
1500
Lux
ON
OFF
t < 5 s
9. Explanation of the remote control button functions
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
Stop of the dim process and reading
in the current light value as new
luminance set point
DIP-
switch
ON OFF
1 Semi automatic mode Fully automatic mode
2 LED OFF LED ON
3 Corridor mode Standard mode
5. Putting into operation / Settings
Initialization
In the first 60 seconds after connecting the power supply the LUXOMAT®
PD4-M-DIM will go through a self test cycle. During this time the device
doesn´t respond to movement, but will stay on the status depending on the
selected initialization mode on or off (INI OFF or ON).
Warning: In the Ini-OFF mode, does not switch on lights at power start
up. After 60 seconds, detector would switch on lights on upon detecting
movement.
Follow-up time for light control
The time can be set infinitely variably at between
1 and 30 minutes.
Symbol TEST: Test mode (Every movement switches on the light
for a period of 1 second, switching it off for a period of 2
seconds after that regardless of the level of brightness)
Twilight-switch for light control (relay 1)
The switch-on value for the light can be set at between 10 and
2000 Lux. Using the rotary control, the luminance set points can
be set as desired.
Symbol : Night-time operation
Symbol : Daytime/Night-time operation
Orientation lighting
This rotary controller serves to determine the working time of
the orientation lighting (fixed to 20%).
“ON” for permanent orientation lighting.
“OFF” for deactiviation of orientation lighting.
Pulse spacing PD-Slave
2 or 9 seconds can be set for the pause between 2 pulses sent
to the master. The setting can be made with activated ( ) or
deactivated ( ) LED indicator.
For devices with a separate slave input, 2 sec. can be set.
6. Settings carried out using remote
control (optional)
Remote control
LUXOMAT®IR-PDim
1. Check Battery:
open battery compartment by pressing the
plastic springs together and removing the
battery-holder.
2. IMPORTANT
Please pay attention, that the setting is
Potentio-meter 1 at “TEST” and Potentiometer
2 not at “SUN”. All values which have
been programmed using the remote control
will be deleted in the event of power failure
in the position “TEST/SUN”. Please switch
Potentiometer 2 over to “MOON” or any
other value.
Caution:
Settings with remote control supersede the
settings by courtesy of potentiometers.
Preset/user mode
=> (see page 2, point11)
Follow-up time light
Orientation lighting and its
follow-up time
Orientation lighting ON/OFF
20 % of the nominal light
Fully automatic/semi automatic
mode => (see page 2, point10)
Locking device – Exit programming
mode
Permanent protection against
sabotage
LED ashes
In the initialization period
During initialization phase/self test cycle
Lights can be set to on or off status during initialization(60 Seconds) by using
INI OFF/ON mode.
max
50
Lux
1500
Lux
ON
OFF
!
18.
Technical data
PD4-M-DIM
15. Wiring diagrams
Typ SM FC FM
PD4-M-DIM (Master) 92147 92247 92248
PD4-S (Slave) 92142 92254 92163
LUXOMAT®Remote control:
IR-PDim (incl. wall bracket) 92200
IR-PD-DIM-Mini 92098
Accessory:
BSK Ball basket guard 92199
Occupancy detectors – Covering IP23 92206
17. Article / Part nr. / Accessory
MAN 7259 – 1908132–2
In case the sensing area of the LUXOMAT®PD4-M-DIM
is too large or areas are being covered that should
not be monitored, the range can be reduced or limited
through use of the enclosed masking clips (e).
14. Exclude sources of interference
13. Range
10. Fully / Semi automatic mode
(for IR-PDim functions see page 1)
The system switches over when the “Light” push-button is
open (see remote control functions, page 1). Each time
a push-button is pressed, the current operating mode is
indicated:
Red lights for 3 sec. = Fully automatic mode
Green lights for 3 sec. = Semi-automatic mode
Fully automatic operation
In this operating mode, the lighting switches automatically
on and off for increased comfort, depending on presence
and brightness.
Semiautomatic operation
In this operating condition, in order to gain increasedsav-
ings, the lighting is energized only after being manually
switched on. Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic. However, the difference is that switching-on must
always be carried out manually!
As many (closer-contact) buttons as desired can be wired in
parallel on the “S” button input (ON/OFF Dimm).
e
Walking across
Walking towards
Seated
24 m
8 m
6,40 m
24 m
360°
2,50 m
2
3
1
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
16. Connections
PD4-M-DIM-SM socket
PD4-M-DIM-FC/-FM
L
N
R
Slave
L'L S
N
– +
R
T1
N
L
+
–
E1
1-10 V
EB
Sensor and power supply in one case
Power supply: 230 V~ ±10 %
Power consumption: < 1W
Ambient temperature: -25°C to +50°C
Degree of protection/class:
SM IP54, FC and FM IP20 / II
Settings:
locally and by remote control
Light values - IR-PDim:
50 - 1500 Lux
Extension of the detection area:
with Slaves
Area of coverage:
circular 360°
Range of coverage Ø H 2.50m / T = 18°C:
seated 6.
40m
/ tangential 24 m /
radial 8 m
Recommended height for mounting:
2 - 3 m
Light measurement:
Mixed light, daylight + artificial light
Lux values - Potentiometer:
10 - 2000 Lux
• Channel 1 for light-connection
Type of contact:
NOC/with pretravel tungsten contact
Contact load:
2300 W cos ϕ=1 /
1150 VA cos ϕ=0.5, µ-Contact
Time-settings:
1 - 30min. / Test
DIM-Output:
1 x (1-10V)
Max. no. of series-connected electronic ballasts:
max. 50 electronic ballasts by one single supply with
max. 100 m cable run and a conductur cross-section of
0.75 mm²
Dimensions H x Ø [mm]
SM FC FM
PD4-M-DIM 76 x 101 103 x 97 84 x 97
Visible portion when built into ceiling: 30x97mm
Version: v.01
Technical data
PD4-Slave
Power supply: 230 V~ ±10 %
Impulse output: Optocoupler max. 2 W
Impulse duration: 2 sec. or 9 sec.
Dimensions: see above
Declaration of Conformity:
The product complies with the low
voltage recommendation 2006/95/EC and the EMV recommen-
dation 2004/108/EC.
12. Manual Switching
You can switch the lighting on and off manually by
pressing the pushbutton for a short time. It will stay on or
off as long as people are detected plus the congured
follow up time.
L
N
R
Slave
L'L SNN– + R
T1
N
L
+
–
E1
1-10 V
EB
11. Manual Dimming – Preset /User
(for IR-PDim functions see page 1)
Manual dimming – Start the dim process by pressing the
push button „min/max“. Stop by pressing the push button
„eye“.
PRESET – the luminance set point is set during start-up
operation by the installer and remains unchanged. The
luminance set- point congured through manual dimming is
only applied for the time being.
Caution:
The constant light regulation is now deactivated!
The currently set articial light is retained independent of
the ambient/daylight brightness!
After switching off and then back on, the originally set
luminance set-point is reset = constant light regulation is
activated.
USER
The luminance set-point is changed upon each manual dim-
ming and re-adjusted by the user (Conformation through
relay clicking!) The constant light regulation remains
activated!
The system switches over when the “Doublelock” push-button
is open (see remote control functions, page 1). Each time
a push-button is pressed, the current operating mode is
indicated:
Red lights for 3 sec. = Preset
Green lights for 3 sec. = User
max
50
Lux
1500
Lux
ON
OFF
Standard mode with master DIM occupancy detectors








 

L
N
E1 110 V EB
N
L
+

RS L L΄
΄΄΄N + N LR
T1
C1
optional
T1 = NO button for semi-automatic mode
Slave for enlargement of detection area
WE RECOMMEND THAT BEFORE DIMMING OF THE CONNECTED
LIGHTS A 100 hBURN IN (T5 TUBES OR 80 HOURS FOR T8 TUBES)
FUNCTION TAKES PLACE.
THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN
DOES NOT TAKE PLACE.
19. LED-functional indicators, fault-finding
The functional indicators in the case of the LUXOMAT®
PD4-M-DIM (red and green LED‘s)
Red LED indicating self-checking mode
(over a period of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM/memory empty
Flashing rapidly
EEPROM/memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off (dependent upon operating mode)
Not illuminated
Detector identifies dark, light on (dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for commands from the
remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when an attempt
is made to input twilight-value are too bright or too dark
Green LED as an acknowledgement of receipt for commands from
the remote control
Lights up for 3 seconds
Semi automatic or user signal correctly received
Green LED as an indicator of status
(only for status “Permanent protection against sabotage”)
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off (dependent upon operating mode)
Not illuminated
Detector identifies dark, light on (dependent upon operating mode)
lluminated for 2 seconds
Signal validly received (dependent upon operating mode)
White LED
Lights permanently
Semi-automatic active (shines)
Illuminates 4 seconds, then 1 sec off
Semi-automatic and active corridor
Illuminates 1 seconds, then 4 sec off
Only active corridor
1
2
3

This manual suits for next models

3

Other B.E.G. Security Sensor manuals

B.E.G. LUXOMAT PD1-M-DIM User guide

B.E.G.

B.E.G. LUXOMAT PD1-M-DIM User guide

B.E.G. LUXOMAT PD4-S-K User manual

B.E.G.

B.E.G. LUXOMAT PD4-S-K User manual

B.E.G. LUXOMAT PD4-M-GH-SM User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-GH-SM User guide

B.E.G. LUXOMAT PD2-M-DALI/DSI-1C/PD2-S User guide

B.E.G.

B.E.G. LUXOMAT PD2-M-DALI/DSI-1C/PD2-S User guide

B.E.G. Luxomat BL4 User manual

B.E.G.

B.E.G. Luxomat BL4 User manual

B.E.G. LUXOMAT PD4-S-DAA4G User guide

B.E.G.

B.E.G. LUXOMAT PD4-S-DAA4G User guide

B.E.G. LUXOMAT PD4-DIM User guide

B.E.G.

B.E.G. LUXOMAT PD4-DIM User guide

B.E.G. LUXOMAT PD2-M-DALI/DSI-SM/FC User guide

B.E.G.

B.E.G. LUXOMAT PD2-M-DALI/DSI-SM/FC User guide

B.E.G. LUXOMAT Indoor 180/R-2W UK Service manual

B.E.G.

B.E.G. LUXOMAT Indoor 180/R-2W UK Service manual

B.E.G. LUXOMAT PD4-M-DALI/DSI-SM User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-DALI/DSI-SM User guide

B.E.G. LUXOMAT PD4-S Series User guide

B.E.G.

B.E.G. LUXOMAT PD4-S Series User guide

B.E.G. LUXOMAT PD4-M-1C-C-PS User manual

B.E.G.

B.E.G. LUXOMAT PD4-M-1C-C-PS User manual

B.E.G. RC-plus next 130 Service manual

B.E.G.

B.E.G. RC-plus next 130 Service manual

B.E.G. LUXOMAT PD4-M-DALI User manual

B.E.G.

B.E.G. LUXOMAT PD4-M-DALI User manual

B.E.G. LUXOMAT PD4-S Series User guide

B.E.G.

B.E.G. LUXOMAT PD4-S Series User guide

B.E.G. LUXOMAT PD4-M-1C-GH-AP User manual

B.E.G.

B.E.G. LUXOMAT PD4-M-1C-GH-AP User manual

B.E.G. LUXOMAT PD9-DIGI-FC User guide

B.E.G.

B.E.G. LUXOMAT PD9-DIGI-FC User guide

B.E.G. LUXOMAT PD9-S User manual

B.E.G.

B.E.G. LUXOMAT PD9-S User manual

B.E.G. LUXOMAT PD11-KNX-FLAT-DX How to use

B.E.G.

B.E.G. LUXOMAT PD11-KNX-FLAT-DX How to use

B.E.G. PD4-M-1C-GH-SM User guide

B.E.G.

B.E.G. PD4-M-1C-GH-SM User guide

B.E.G. LUXOMAT PD2-M-1C User guide

B.E.G.

B.E.G. LUXOMAT PD2-M-1C User guide

B.E.G. LUXOMAT LC-Click 140 Owner's manual

B.E.G.

B.E.G. LUXOMAT LC-Click 140 Owner's manual

B.E.G. Luxomat PD2-DIM Series User manual

B.E.G.

B.E.G. Luxomat PD2-DIM Series User manual

B.E.G. KNX RC-plus next 230 KNX Service manual

B.E.G.

B.E.G. KNX RC-plus next 230 KNX Service manual

Popular Security Sensor manuals by other brands

Aritech RF4112I4 Installation sheet

Aritech

Aritech RF4112I4 Installation sheet

Dors 1000 user manual

Dors

Dors 1000 user manual

Sperian PHD6 Reference manual

Sperian

Sperian PHD6 Reference manual

Vive LVA1074BED user manual

Vive

Vive LVA1074BED user manual

Extronic PD-22LF installation instructions

Extronic

Extronic PD-22LF installation instructions

TS-market LORNET-24 user manual

TS-market

TS-market LORNET-24 user manual

BW Technologies MicroClip XT Operator's manual

BW Technologies

BW Technologies MicroClip XT Operator's manual

Danieli Automation ID6100 instruction manual

Danieli Automation

Danieli Automation ID6100 instruction manual

schmersal CSS 34F0 operating instructions

schmersal

schmersal CSS 34F0 operating instructions

Detection Systems Security Escort SE88 Series user guide

Detection Systems

Detection Systems Security Escort SE88 Series user guide

Ecolink Firefighter CS-600 Installation manual & users guide

Ecolink

Ecolink Firefighter CS-600 Installation manual & users guide

Smoke Guard 200 Operation & maintenance manual

Smoke Guard

Smoke Guard 200 Operation & maintenance manual

Winland WaterBug WB-200 Installation & owner's manual

Winland

Winland WaterBug WB-200 Installation & owner's manual

Bosch WEU PDO 6 Original instructions

Bosch

Bosch WEU PDO 6 Original instructions

EOT ET-3500AF user guide

EOT

EOT ET-3500AF user guide

Saxby Lighting 90977 instruction manual

Saxby Lighting

Saxby Lighting 90977 instruction manual

GJD D-TECT Pet Immune GJD370 installation manual

GJD

GJD D-TECT Pet Immune GJD370 installation manual

iRay Technology NDT1013LA user manual

iRay Technology

iRay Technology NDT1013LA user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.