Template 40941_J 04-02-10 56281/56282/56283_97_A 02-01-13
2
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.
Part # EPN Date Originator Changes Made
56281
56282
56283
3833 02-01-13 Balboa Initial Generic Configuration
Based on 56129-01
System Revision History
Service - Input Power Requirements (Circle Letter Assignment)
B240VAC, 60Hz, 48A, Class A GFCI-protected service (Circuit Breaker = 60A max.),
4 wires [hot, hot, neutral, ground]
C120/240VAC, 60Hz, 16/32A, Class A GFCI-protected service (Circuit Breaker = 20/40A max.),
3 or 4 wires [hot, hot (optional), neutral, ground]
D240VAC, 60Hz, 40A, Class A GFCI-protected service (Circuit Breaker = 50A max.)
4 wires (Hot–Line 1, Hot–Line 2, Neutral, Ground)
A120/240VAC, 60Hz, 16/40A, Class A GFCI-protected service (Circuit Breaker = 20/50A max.),
3 or 4 wires [hot, hot (optional), neutral, ground]
H240VAC, 60Hz, 32A, Class A GFCI-protected service (Circuit Breaker = 40A max.),
4 wires [hot, hot, neutral, ground]
F120VAC, 60Hz, 16A, Class A GFCI-protected service (Circuit Breaker = 20A max.),
3 wires [hot, neutral, ground]
Y120/240VAC, 60Hz, 16/48A, Class A GFCI-protected service (Circuit Breaker = 20/60A max.),
3 or 4 wires [hot, hot (optional), neutral, ground]
Service - Input Power Requirements (Circle Letter Assignment)
240VAC, 60Hz, 48A, Class A GFCI-protected service (Circuit Breaker = 60A max.),
wires [
ot,
ot, neutra
,
roun
]
20
240VAC, 60Hz, 16
32A, C
ass A GFCI-protecte
service
Circuit Brea
er = 20
40A max.
,
3 or 4 wires [hot, hot
optional
, neutral, ground]
240VAC, 60Hz, 40A, Class A GFCI-protected service (Circuit Breaker = 50A max.)
wires
Hot–Line 1, Hot–Line 2, Neutra
, Groun
20
240VAC, 60Hz, 16
40A, C
ass A GFCI-protecte
service
Circuit Brea
er = 20
50A max.
3 or 4 wires [
ot,
ot
optiona
, neutra
, groun
]
H240VAC, 60Hz, 32A, C
ass A GFCI-protecte
service
Circuit Brea
er = 40A max.
,
wires [hot, hot, neutral, ground]
20VAC, 60Hz, 16A, Class A GFCI-protected service (Circuit Breaker = 20A max.),
3 wires [
ot, neutra
,
roun
]
20
240VAC, 60Hz, 16
48A, C
ass A GFCI-protecte
service
Circuit Brea
er = 20
60A max.
,
3 or 4 wires [hot, hot (optional), neutral, ground]