The illustration shows the D132A modules wired for both detector loops triggered by the
same output. For loops triggered by separate outputs, connect one D132A module reverse
trigger to the A relay and the other D132A revese trigger to the B relay.
5
1
ZONEX IN
ZONEX POWER
ZONEX
1
1
2
1
1
1 1 1
2
2
5
67
Point
Point Point
Point
Point
Point Point
Point
3
6
7
8
EARTH GROUND
COMMON
BATTERY NEGATIVE ONLY
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do not short
Requires Unswitched Outlet
Do not share with other equipment
GROUND FAULT DETECT
Enabled
Disabled
PHONE
LED
RED
ON when
communicating
OFF when idle
Commercial Protected-Premises Control Panel
D9412GV2 Control Panel is UL Listed For Central Station, Local, Auxiliary, Proprietary, and
Household Fire Alarm, and Central Station, Local, Police Station Connect, Household Burglar Alarm
and Encrypted Line Security when communicating via a network.
System is intended to be checked by a Qualified Technician at least every 3 years.
The types of initiating circuits the control panel has been approved for are A, M, W, SS.
The types of signaling the control panel has been approved for are DAC, OT, NC
Reset Pin
Disable all except Battery
Charging and Programming
PERIPHERAL DEVICE CONNECTIONS
RED POWER +
YELLOW DATA BUS A
GREEN DATA BUS B
BLACK COMMON
ZONEX OUT 1
ZONEX IN 1
N.F.P.A.
Style 4.0
Signaling
Line
Circuits
F01U003643-01
1211 13
Point 1 Point 2
1514 16
Point 3 Point 4
1817 19
Point 5 Point 6
2120 22
Point 7 Point 8
LEDs Off When Normal
Charging Status
Low Battery - 12.1 VDC
YEL
RED
10.2 VDC - Battery Load Shed
This equipment should be installed in accordance with the NFPA 70 (National Electrical Code)
and NFPA 72 (National Fire Alarm Code) for Local, Central Station, Proprietary and Household Fire
Warning Systems and under the limits of the Local Authority Having Jurisdiction (National Fire
Protection Association, Battermarch Park, Quincy, MA 02269). Printed information describing
proper installation, operation, testing, maintenance, evacuation planning and repair service is to
be provided with this equipment.
D9412GV2
26
25
ZONEX POWER + 24
ZONEX COMMON 23
PHONE LINE SEIZED
TIP RING
TELCO CORD
MODEL D161
SDI Connector
ZONEX OUT 2
ZONEX IN 2
Refer to the D9412GV2/D7412GV2 Approved Applications Compliance Guide (P/N: F01U003639)
For System Wiring Diagram, Issue A and for Compatible Smoke Detectors
POWER SUPPLY REQUIREMENTS
The Power Supply provides a maximum of 1.4 Amps for the Control Panel and all
Accessory Devices. For System Loading, refer to the D9412GV2/D7412GV2
Operation and Installation Guide (P/N: F01U003641).
(P/N: F01U003641) for Power Requirements relating to Terminals 6 and 7 .
CAUTION: Refer to the D9412GV2/D7412GV2 Operation and Installation Guide
All external connections except Terminal 5 (battery positive) are inherently power
limited. Requirements for battery standby time might reduce allowable output.
WARNING!
Multi-Battery installation requires
Model D122/D122L Dual Battery
Harness. Improper installation can
be a fire hazard.
Battery: Replace every 3 to
5 years with one or two Model
D126 or D1218 12V Lead Acid
Batteries.
VOLTAGE RANGES
Open 3.7 - 5.0 VDC Short 0.0 - 1.3 VDC
Normal 2.0 - 3.0 VDC
Operation Monitor
Pulses When Normal
Flickers When Ringing
GRN
D5200/D5360
PROG CONN
Point 8
S3 Option
Closed = 1KWEOL
Normal Operation
Open =AB-12 UL
Bell Box 220 KW
Incorrect wiring will
damage this equipment.
Suitable for dry indoor
use only.
Devices powered by the
AUX power output must
be supervised.
Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2000:
UL Listed and Classified control unit Model D9412GV2, D7412GV2, or D7212GV2;
UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW;
UL Listed Local Bell
CAUTION: Avoid damage to Panel.
Do not connect 24 V to terminals.
Maximum charging current 1.4 A
PROGRAMMABLE
ALARM OUTPUTS
Terminals
SWITCHED AUX
and
6 7
Terminal
8
5
6
7
8
9
10
4
3
1
12
11
13
DETECTOR
+
DETECTOR
-
FIRE PT
+
FIRE PT
-
AUX PWR
+
AUX PWR
-
REVERSE
TRIGGER
TRBL PT
+
TRBL PT
-
R4
D132A
+12 VDC
+24 VDC
Common (-)
(+)
(-)
(+)(+)
(-)
(-)
2
14 15
(+) COM
N/O (-)
relay Pulls High in Alarm. Use a D130/
PAM-4 to accomplish this.