
+050004122 - rel. 1.0 - 19.10.2009
CAREL INDUSTRIES HQs
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
T
el.
(+39)
049
9
7
1
66
1
1
–
Fax
(+39)
049
9
7
1
6600
–
http://www.carel.com
–
e-mail:
[email protected]CAREL reserves the right to modify the features of its products without prior notice.
Disposal of the product
The appliance (or the product) must be disposed of separately in accordance with the local waste disposal
legislation in force.
WARNING: separate as much as possible the probe and digital input signal cables from the cables carrying
inductive loads and power cables to avoid possible electromagnetic disturbance. Never run power cables
(including the electrical panel wiring) and signal cables in the same conduits.
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
Table of parameters
Parameter Min. Max. Def. UOM
PS PASSWORD 0 200 22 -
/ PROBE PARAMETERS
/5 Select °C / °F ( 0 = °C; 1 = °F) 0 1 0 -
/6 Disable decimal point (1 disabled) 0 1 0 -
/C1 Probe calibration -50.0 50.0 0.0 °C/°F
/C2 Probe 2 calibration -50.0 50.0 0.0 °C/°F
r CONTROL PARAMETERS
St Control temperature -50.0 90.0 -18.0 °C/°F
rd Control differential (hysteresis) 0.0 19.0 2.0 °C/°F
c COMPRESSOR PARAMETERS
c0 Comp. and fan start delay after start-up 0 100 0 min
c1 Min. time between successive comp. starts 0 100 1 min
c4 Compressor safety (duty setting) 0 100 15 min
d DEFROST PARAMETERS
d0 Type of defrost (0= heater; 1= hot gas; 2= heater by time;
3= hot gas by time; 4= heater by time with temp. cont.)
04 0-
dI Interval between two defrosts 0 199 6 h/min
dt End defrost temperature 50.0 130.0 8 °C/°F
dP Max. or effective defrost duration 1 199 25 min/s
d4 Defrost when the instrument is switched on (1= activated) 0 1 0 -
d6 Disable temperature display during defrost (1= display disabled) 0 1 1 -
dd Dripping time after defrost 0 15 1 min
d/ Defrost probe reading - - - °C/°F
A ALARM PARAMETERS
A0 Alarm and fan differential -20.0 20.0 -2.0 °C/°F
AL Low temperature alarm threshold/deviation (AL= 0; alarm
disabled)
-50.0 250.0 -50 °C/°F
AH High temperature alarm threshold/deviation (AH= 0; alarm
disabled)
-50.0 250.0 50 °C/°F
Ad Low and high temperature alarm delay 0 199 0 min
F FAN PARAMETERS
F0 Fan management: 0= fans on excluding specific phases;
1= fans on according to parameter F1 excluding specific phases
01 1-
F1 Fans shutdown temperature 50.0 130.0 2 °C/°F
F3 Fans status during defrost: 0= fan ON; 1= fan OFF 0 1 1 -
H OTHER SETTINGS
H2 Enable keypad
0= keypad disabled
1= keypad enabled
2= keypad enabled except for ON/OFF function
02 1-
EZY restore the Default settings 0 1 0 -
Table of alarms
Alarm
code
buzzer and
alarm relay
LED Description Parameters involved
E0 active ON probe 1 error= control -
E1 inactive ON probe 2 error= defrost [d0 = 0 / 1]
LO active ON low temperature alarm [AL] [Ad]
HI active ON high temperature alarm [AH] [Ad]
EE inactive ON unit parameter error -
EF inactive ON operating parameter error -
Ed inactive ON defrost ended by timeout [dP] [dt] [d4] [A8]
dF inactive OFF defrost running [d6=0]
How to restore the Default settings (refer to table of parame-
ters in this sheet)
1) Access parameter EZY (entering password 22 and scroll parameter list).
2) Select the desired configuration:
• EZY = 0 ¼No changes;
• EZY = 1 ¼Restore of default settings (refer to Table of parameters in this sheet);
3) Exit the setting procedure (holding SET button for more than 3 sec).
4) Power off the device and then power it on again while holding SET button.
5) The display shows “CE” to indicate that the configuration has been restored.
Switching the device ON/OFF
Press UP for more than 3 s. The control and defrost algorithms are now disabled and the instru-
ment displays the message “OFF” alternating with the temperature read by the set probe.
Manual defrost
Press DOWN for more than 3 s (the defrost starts only if the temperature conditions are valid).
Continuous cycle
Press UP and DOWN together for more than 3 s.
Technical specifications
power supply 230 Vac +10 /-15% 50/60 Hz;
rated power 3,5 VA
inputs NTC probes
relay outputs 16 A relay UL: 12 A Res. 5 FLA 30 LRA - 240 Vac C300,
EN60730-1: 12(2) A NO/NC, 10(4) A up to 60 °C NO,
2(2) A CO - 250 Vac
8 A relay UL: 8 A Res. 2 FLA 12 LRA - 240 Vac C300,
EN60730-1: 8(4) A NO, 6(4) A NC, 2(2) A CO - 250 Vac
type of probe Std CAREL NTC 10 KΩat 25 °C
connections Screw terminals for cables with cross-sect. from 0.5 mm2 to 1.5 mm2
Rated maximum current per terminal 12 A
assembly Terminal: using screws from the front panel or with rear brackets
Interface: wall mounting, 4 screws, spacing 101x151 mm
display 3 digit LED display with sign (-199 to 999) and decimal point; six status LEDs
operating conditions -10T50 °C - humidity <90% rH non-condensing
storage conditions -20T70 °C - humidity <90% rH non-condensing
range of measurement -50T90 °C (-58T194 °F) - resolution 0.1 °C/°F
front panel index of protection panel installation with IP65 type 1 gasket
case plastic terminal, 81x36x65 mm
classification according to protection
against electric shock
Class II when suitably integrated
environmental pollution normal
PTI of the insulating material 250 V
period of stress across the insulating parts long
category of resistance to heat and fire category D (UL94 - V0)
immunity against voltage surges category 1
type of action and disconnection 1C relay contacts
no. of relay automatic operating cycles EN60730-1: 100,000 operations
UL: 30,000 operations (250 Vac)
software class and structure Class A
cleaning the instrument Only use neutral detergents and water.
cable max. lenght serial: 1 km
probes: 30 m
relay: 10 m
Note: do not run the power cable less than 3 cm from the bottom part of the device or from the
probes; for the connections only use copper wires.
Safety standards
compliant with the relevant European standards. Installation precautions:
the connection cables must guarantee insulation up to 90 °C;•
for 12 Vac versions use Class II transformers. To ensure compliance with the immunity standards•
(surge), the transformer must be one of the models specified (see the CAREL price list). For the 12
Vac/dc versions, as double insulation cannot be guaranteed between the power supply and the
relay outputs, only use safety low voltage loads (up to 42 V effective rated value);
ensure a space of at least 10 mm between the case and the nearby conductive parts;•
digital and analogue input connections less than 30 m away; adopt suitable measures for separa-•
ting the cables so as to ensure compliance with the immunity standards;
Secure the connection cables of the outputs so as to avoid contact with very low voltage parts.
IMPORTANT WARNINGS
The CAREL product is a state-of-the-art device, whose operation is specified in the technical documentation sup-
plied with the product or can be downloaded, even prior to purchase, from the website www.carel.com.
The customer (manufacturer, developer or installer of the final equipment) accepts all liability and risk relating to
the configuration of the product in order to reach the expected results in relation to the specific final installation
and/or equipment. The failure to complete such phase, which is required/indicated in the user manual, may cause
the final product to malfunction; CAREL accepts no liability in such cases. The customer must use the product
only in the manner described in the documentation relating to the product. The liability of CAREL in relation to its
products is specified in the CAREL general contract conditions, available on the website www.carel.com and/or by
specific agreements with customers.