GB
Thank you for your choice. We trust you will be satisfied with your purchase.
General features
pCO1is an electronic controller based on a microprocessor designed by CAREL for a wide range of applications in the Air-Conditioning and
Refrigeration sectors. pCO1is a flexible controller, which can respond to all customer requirements.
pCO1carries out the regulation program and it is fitted with a set of terminals that connect it to the controlled devices (for ex. valves,
compressors, power contactors, fans).
The program and the parameters are stored on FLASH-MEMORY, thus allowing their permanence even in case of power failure (it is not necessary
for you to have a maintenance battery). The program can be loaded through PC or by means of a suitable programming key. pCO1allows
the connection to the local pLAN network (pCO Local Area Network) - already provided in the previous versions of the pCO and pCO2controllers.
The pLAN network is made up of several controllers and terminals which interact among themselves. Every controller in the pLAN network can
exchange information (any digital and analog variable according to the used application program) at high transmission speed. In order to rapidly
exchange information, up to 32 units - pCO1and terminals - can be connected to the pLAN network. The connection towards the supervising/
telemaintenance serial line, according to the RS485 standard, is carried out by inserting the optional serial cards on the pCO1with the CAREL stan-
dard communication protocol or MODBUS™.
Key
1. power supply connector [G (+), G0 (-)]
2. 250 Vac, 2 A delayed fuse (T2 A)
3. universal analog inputs NTC, 0 to 1V, 0 to 5V, 0 to 20mA, 4 to 20mA
4. passive analog inputs NTC and ON/OFF
5. passive analog inputs NTC
6. yellow LED showing power supply voltage and 3 signalling LEDs
7. analog outputs 0 to 10V and PWM phase-cutting outputs
8. 24 Vac/Vdc digital inputs
9. 230 Vac or 24 Vac/Vdc digital inputs
10. connector with Vrif for the power supply of the 5 V ratiometric probes and V Term for the terminal power supply
11. connector for all pCO*series standard terminals and for the application program download
12. pLAN local network connector
13. connector for the connection to the programming key
14. relay digital outputs
15. hatch for selecting the type of the analogical inputs
16. hatch for inserting the serial card: - RS485 for the supervisor
- RS232 for the modem interface
- Gateway (protocol converter)
17. hatch for inserting the clock card
Available models:
• SMALL (cod. PCO1000AS0), MEDIUM (cod. PCO1000AM0)
• SMALL (cod. PCO1002AS0), MEDIUM (cod. PCO1004AM0), with solid status relay digital outputs (SSR)
• SMALL (cod. PCO1000CS0), MEDIUM (cod. PCO1000CM0) expanded memory version
• SMALL (cod. PCO1002CS0), MEDIUM (cod. PCO1004CM0) expanded memory and solid status relay digital outputs (SSR) versions
Connectors kit:
• SMALL (cod. PCO1CON0S0), MEDIUM (cod. PCO1CON0M0) screw
• SMALL (cod. PCO1CON1S0, MEDIUM (cod. PCO1CON1M0) spring
Power supply
During installation a safety Class II transformer rated at least 40 VA must be used to supply only one pCO1controller.
It is advisable to keep separate the pCO1controller and terminal (or more pCO1 and terminals) from the power supply of the other electric devices
(contactors and other electromechanical components) in the electric panel.
If the transformer secondary winding is grounded, check that the ground cable is connected to G0 terminal.
If more than one pCO1board, connected to the pLAN, must be powered, please check if G and G0 references are observed (G0 reference must be
kept in every board).
If using the pLAN network, ask for the CAREL pCO1user’s manual.
Further information can be found in the installation manual - code +030220335.
WARNING: pCO1(as pCO2)can not supply the graphic terminals PCOT00PGH0 and PCOI00PGL0, which can be supplied by other sources.
Technical Specifications
Mechanical Specifications
dimensions SMALL board models can be mounted on 13 DIN modules, 110x227.5x60mm
MEDIUM board models can be mounted on 18 DIN modules, 110x315x60mm
mounting on DIN rail
Plastic case
material technopolymer
self-extinguishing V0 (complying with UL94) and 960 °C (complying with IEC 695)
ball pressure test 125 °C
comparative tracking index 250 V
colour RAL7035 grey
it can be fastened on DIN rail according to DIN 43880 and CEI EN 50022 standards
cooling vent-holes
Electrical specifications
power (controller with terminal connected) 22 to 38 Vdc and 24 Vac ±15 % 50/60 Hz - P= 13 W maximum absorption
terminal block with removable-screw male/female connectors - max. voltage: 250 Vac
cable cross-section: min. 0.5 mm2– max. 2.5 mm2
CPU H8S2320, 16 bit and 14 MHz
program memory (on FLASH MEMORY) 1 MB organized in 16 bit (2 MB in expandend memory version)
data memory (static RAM) 128 kB organized in 16 bit (512 kB in expandend memory version)
parameter data memory 4 kB organized in 16 bit (max limit: 400.000 writings per memory location)
operating cycle duration (middle complexity applications) 0.5 s (typical value)
Vi ringraziamo per la scelta fatta, sicuri che sarete soddisfatti del vostro acquisto.
Caratteristiche generali
pCO1è un controllore elettronico a microprocessore, sviluppato da CAREL per molteplici applicaz. nel settore del condizionamento dell’aria e della
refrigerazione. Assicura la più assoluta versatilità di applicazione, consentendo di realizzare prodotti specifici su richiesta del cliente. pCO1è dedicato
all’esecuzione del programma di regolazione ed è dotato del set di morsetti necessari alla connessione verso i dispositivi controllati (ad esempio:
valvole, compressori, contattori di potenza, ventilatori).
Il programma e i parametri sono memorizzati su FLASH-MEMORY, consentendo il loro mantenimento anche in caso di mancanza di alimentazione
(senza la necessità di una batteria di mantenimento). Il caricamento del programma può essere eseguito a mezzo PC o tramite apposita chiave di
programmazione. pCO1permette anche la connessione alla rete locale pLAN (pCO Local Area Network) già prevista per i modelli precedenti di con-
trollori pCO e pCO2.
La rete pLAN è costituita da più controllori e più terminali, che interagiscono tra loro. Ogni controllore in rete pLAN può scambiare informazioni
(qualsiasi variabile, digitale o analogica, a seconda del programma applicativo utilizzato) con velocità di trasmissione elevata. Possono essere col-
legate fino a 32 unità, tra pCO1e terminali, in modo da condividere le informazioni in tempi molto brevi. Il collegamento verso la linea seriale di
supervisione/teleassistenza secondo lo standard RS485, viene realizzato tramite l’inserimento sul pCO1di schede seriali opzionali con il protocollo di
comunicazione CAREL o MODBUS™.
Legenda
1. connettore per l’alimentazione [G (+), G0 (-)]
2. fusibile 250 Vac, 2 A ritardato (T2 A)
3. ingressi analogici universali NTC, 0…1 V, 0…5 V, 0…20 mA, 4…20 mA
4. ingressi analogici passivi NTC e ON/OFF
5. ingressi analogici passivi NTC
6. LED giallo indicazione presenza tensione di alimentazione e 3 LED di segnalazione
7. uscite analogiche 0…10 V e uscite PWM taglio di fase
8. ingressi digitali a 24 Vac/Vdc
9. ingressi digitali 230 Vac o 24 Vac/Vdc
10. connettore con Vrif per alimentazione sonde 5 V raziometrici e V Term per alimentazione terminale
11. connettore per tutti i terminali standard della serie pCO* e per il download del programma applicativo
12. connettore rete locale pLAN
13. connettore per la connessione alla chiave per la programmazione
14. uscite digitali a relè
15. sportello per selezione tipo di ingressi analogici
16. sportello per l’inserimento della scheda seriale: - RS485 per supervisore
- RS232 per l’interfacciamento modem
- Gateway (convertitore di protocollo)
17. sportello per l’inserimento della scheda orologio
Versioni disponibili:
• SMALL (cod. PCO1000AS0), MEDIUM (cod. PCO1000AM0)
• SMALL (cod. PCO1002AS0), MEDIUM (cod. PCO1004AM0) con uscite digitali a relè a stato solido (SSR)
• SMALL (cod. PCO1000CS0), MEDIUM (cod. PCO1000CM0) versione con memoria espansa
• SMALL (cod. PCO1002CS0), MEDIUM (cod. PCO1004CM0) versione con memoria espansa ed uscite digitali a relè a stato solido (SSR)
Kit connettori:
• SMALL (cod. PCO1CON0S0), MEDIUM (cod. PCO1CON0M0) a vite
• SMALL (cod. PCO1CON1S0, MEDIUM (cod. PCO1CON1M0) a molla
Alimentazione
Nell’installazione si deve utilizzare un trasformatore di sicurezza in Classe II di almeno 40 VA, per l’alimentazione di un solo controllore pCO1. Si
raccomanda di separare l’alimentazione del controllo pCO1e terminale (o più pCO1e terminali) dalla alimentazione del resto dei dispositivi elettrici
(contattori ed altri componenti elettromeccanici) all’interno del quadro elettrico. Qualora il secondario del trasformatore sia posto a terra, verificare
che il conduttore di terra sia collegato al morsetto G0. Attenersi a ciò per tutti i dispositivi connessi al pCO1. Se si alimentano più schede pCO1colle-
gate in rete pLAN, assicurarsi che siano rispettati i riferimenti G e G0 (il riferimento G0 deve essere mantenuto per tutte le schede).
In caso di utilizzo della rete pLAN, richiedere il manuale pCO1CAREL.
Ulteriori specificazioni e notizie si possono reperire sul manuale di installazione - cod. +030220335.
AVVERTENZA: il pCO1(come il pCO2) non può alimentare i terminali grafici PCOT00PGH0 e PCOI00PGL0, che devono quindi essere alimentati con
altre sorgenti.
Caratteristiche tecniche
Caratteristiche meccaniche
dimensioni versione SMALL inseribile su 13 moduli DIN, 110 x 227.5 x 60 mm
versione MEDIUM inseribile su 18 moduli DIN, 110 x 315 x 60 mm
montaggio su guida DIN
Contenitore plastico
materiale tecnopolimero
autoestinguenza V0 (secondo UL94) e 960 °C (secondo IEC 695)
prova biglia 125 °C
resistenza alle correnti striscianti 250 V
colore grigio RAL7035
agganciabile su guida DIN secondo norme DIN 43880 e CEI EN 50022
feritoie di raffreddamento
Caratteristiche elettriche
alimentazione (controllore con term. connesso) 22…38 Vdc e 24 Vac ±15% 50/60 Hz - assorbimento massimo P= 13 W
morsettiera con connettori maschio/femmina estraibili, tensione max 250 Vac
sezione cavo: min. 0,5 mm2- max 2,5 mm2
CPU H8S2320 a 16 bit e 14 MHz
memoria programma (su FLASH MEMORY) 1 MB organizzata a 16 bit (2 MB nella versione con memoria espansa)
memoria dati (RAM statica) 128 kB organizzata a 8 bit (512 kB nella versione con memoria espansa)
memoria dati parametri 4 kB organizzata a 16 bit (limite max: 400.000 scritture per locazione di memoria)
durata ciclo utile (applicazioni media complessità) 0,5 s (tipico)
pCO1Controllore elettronico PCO1**** / Electronic controller PCO1****
cod. +050003220 rel. 1.5 - 13.10.2008
Rx-/Tx-
Rx+/Tx+
GND
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
NO12
C12
NC12
NO13
C13
NC13
C9
NO9
NO10
NO11
C9
G
G0
B1
B2
B3
B4
+VDC
B5
GND
B6
GND
VG
VG0
Y1
Y2
Y3
Y4
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
B7
GND
B8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
Fuse
Analog Selection Serial Card
Clock card
Programming Key
J1
J2
J3
J5
J6
J7
J8
J10
J11
J12
J13
J14
J15
J16
J17
J18
+5V Rif
GND
+VTerm
J9
J4
10
1
11
12
14
3
7
8
4
6
5
8
9
2
16
15 17
13
Fig. 1
123456
ON
OFF
123456 12
123456 123456
123456 123456
123456 123456
123456
NTC
Esempio/Example
123456
B1 B2 B3 B4 B5 B6
Input B1, B2, B3, B4
Input
ON digital input
OFF NTC
Input B5, B6
B1 B2 B3 B4 B5 B6
NTC NTC digital input
ON
OFF
ON
OFF
NTCdigital
input
GB
Analog inputs
analog conversion 10 bit A/D converter, built-in CPU
type passive: CAREL NTC temp. probe sensor, (-50T90 °C; R/T 10 kΩat 25 °C), (input B5, B6, B7,B8)
or free contact digital input (5 mA), that can be selected via dip-switch (B5, B6)
universal: CAREL NTC temp. probe (see passive type), voltage: 0 to 1 Vdc or 0 to 5 Vdc,
current: 0 to 20 mA or 4 to 20 mA, that can be selected via dip-switch (B1, B2, B3, B4 inputs)
max. number 6, 8, on SMALL, MEDIUM, boards respectively
time constant for each input 1 s
0 to 20 mA inputs internal resistance 100Ω
WARNING: for powering any active probe, it is possible to use the 24 Vdc placed on +Vdc terminal; the max. current that can be delivered is 100
mA thermally protected against short circuits. Unlike pCOBthe signal 0 to 1Vdc is limited to the restricted range 0 to 1 V, so it is not always compati-
ble with the standard signal 10 mV/°C of CAREL probes (if the temperature is below zero or higher than 100 °C, it can cause probe alarm). So, for
the temperature signals use 4 to 20 mA or NTC).
Digital inputs
type optoinsulated
max. number 8, 14 on SMALL and MEDIUM boards respectively according to the combinations shown below:
No. of optoins. inputs at 24 Vac No. of optoins. inputs at 24 Vac/Vdc total inputs
50 to 60 Hz or 24 Vdc or 230 Vac (50/60 Hz)
SMALL 8 none 8
MEDIUM 8 + 4 2 14
WARNING: - 230 Vac 50/60 Hz (10/-15 %)
- the two 230/24Vac inputs have the same common pole, so they both will be at 24 Vac or 230 Vac. The insulation is principal.
- please keep probe and digital input leads as far as possible from power cables to avoid possible electromagnetic noise.
Analog outputs
type and max. number 2 outputs (Y1 and Y2) optoinsulated 0 to 10 Vdc and 2 outputs (Y3 and Y4) PWM phase-cutting with impulse at
5 V programmable duration
power supply 24 Vac/Vdc external
resolution 8 bit
max. load 1kΩ(10 mA) for 0 to 10V and 470Ω(10 mA) for PWM
Digital outputs
max. number 8, 13, on SMALL, MEDIUM boards respectively, type relay
They are grouped in 3 with two common pole termin. in order to assemble the common poles easily. Be careful to the current flowing in common
termin., because it must not exceed the rated current of each single termin., that is: 8 A for removable-screw terminals. The relays are divided into
groups, according to the insulat. distance. Inside each group the relays have their single own main insulat., so they must be exposed to the same
voltage (in general 24 Vac or 230 Vac). Among the groups there is double-insulat., therefore the groups can be of different voltage.
Anyway the double-insulat. does exist towards the rest of the control. and its presence is guaranteed among digital output termin.
groups: 1, 2, 3, 4, 5, 6 - 7 - 8 (alarm relay) - 9, 10, 11, 12, 13.
changeover contacts: 1,3 respectively on the SMALL, MEDIUM versions
commutable power: 2000 VA, 250 Vac, 8 A resistive, 2 A FLA, 12 A LRA according to UL873, (30,000 cycles)
2 A resistive, 2 A inductive, cosϕ= 0,6, 2(2) A according to EN 60730-1, (100,000 cycles)
outputs at SSR: 2 instead of the rel. no˚ 7 and 8 (SMALL), 4 instead of the rel. no˚ 7, 8, 12 and 13 (MEDIUM);
24 Vac/Vdc, Pmax=10W
Connection to the user terminal
type asynchronous 2-lead half duplex dedicated
connector for terminal 6-way telephone cable
connector for pLAN 3-way plug-in connector
driver CMR 7V balanced differential (type RS485)
The maximum distances between the terminal and pCO1 are described in the following table:
with telephone-type cable with AWG24 shielded cable
cable resistance (Ω/m) max. distance (m) cable resistance (≤/m) max. distance (m)
≤0.14 600 ≤0.078 600
≤0.25 400
* Note: unlike pCOBand pCO2the pLAN addressing doesn’t take place through dip switch but through operation sequences on the display. With
regards to this, please refer to the software manual.
Other specifications
storage conditions -20T70, 90 %r.H. non-condensing
operating conditions -10T60, 90 %r.H. non-condensing
index of protection IP20, IP40 (front panel only)
environmental pollution 2
classification according to protection against electric shock should be integrated into Class I and/or II devices
PTI of insulating materials PCB: PTI 250; insulation material PTI 175
period of electric stress across insulating parts long
type of actions 1C
type of disconnection or microinterruption microinterruption
category of resistance to heat and fire D (UL94 - V0) category
immunity against voltage surges category II
ageing period (operating hours) 80,000
no. of automatic operating cycles 100,000 (EN 60730-1) 30,000 (UL873)
software Class and structure Class A
The device is not intended to be hand-held.
Warning: for applications subject to strong vibrations (1.5 mm pk-pk 10/55 Hz), we suggest you to fasten, through fastening clamps, the cables
connected to the pCO1at about 3 cm of distance from the connectrors. The application program can be downloaded from the flash memory
through the key “PCO100KEY0” or a PC using the program “WINLOAD32” to be required to CAREL.
IMPORTANT WARNINGS: The CAREL product is a state-of-the-art device, whose operation is specified in the technical documentation supplied with the product or can be down-
loaded, even prior to purchase, from the website www.carel.com. The customer (manufacturer, developer or installer of the final equipment) accepts all liability and risk relating
to the configuration of the product in order to reach the expected results in relation to the specific installation and/or equipment. The failure to complete such phase, which is
required/indicated in the user manual, may cause the final product to malfunction; CAREL accepts no liability in such cases. The customer must use the product only in the
manner described in the documentation relating to the product. The liability of CAREL in relation to its products is specified in the CAREL general contract conditions, available on
the website www.carel.com and/or by specific agreements with customers.
CAREL si riserva la possibilità di apportare modifiche o cambiamenti ai propri prodotti senza alcun preavviso. /
CAREL reserves the right to alter the features of its products without prior notice.
315
60
110
227.5
cod. +050003220 rel. 1.5 - 13.10.2008
Dip-switch per selezionare il tipo di sonda / Dip-switch for selecting the probe type
pCO1versione MEDIUM 18 moduli DIN/ pCO1MEDIUM model 18 DIN modules
pCO1versione SMALL 13 moduli DIN/ pCO1SMALL model
Fig. 2
Fig. 3
Fig. 4
Ingressi analogici
conversione analogica A/D converter a 10 bit CPU built-in
tipo passivo: sensore di temp. NTC CAREL, (-50T90 °C; R/T 10 kΩa 25 °C) (ingressi B5, B6, B7, B8) o input
digitale da contatto pulito (5 mA), selezionabili via dip-switch (B5, B6)
universale: sensore di temp. NTC CAREL (vedi tipo passivo), tensione: 0…1 Vdc o 0…5 Vdc,
corrente: 0…20 mA o 4…20 mA, selezionabili via dip-switch (ingressi B1, B2, B3, B4)
numero massimo 6, 8, rispettivamente sulle schede SMALL, MEDIUM
costante di tempo ingressi 1 s
resistenza interna ingressi 0…20 mA 100 Ω
AVVERTENZA: per l’alimentazione di eventuali sonde attive, è possibile utilizzare i 24 Vdc disponibili sul morsetto +Vdc, la corrente massima ero-
gabile è di 100 mA protetta contro i corti circuiti. A differenza del pCOBil segnale 0…1 Vdc è da intendersi limitato al range ristretto 0…1 V e non è
quindi sempre compatibile con il segnale standard 10 mV/°C delle sonde CAREL (per temperature negative e superiori a 100 °C può generare allarme
sonda), per i segnali in temperatura usare quindi 4…20 mA o NTC).
Ingressi digitali
tipo optoisolati
numero massimo 8, 14, rispettivamente sulle schede: SMALL e MEDIUM, secondo le combinazioni riportate qui sotto:
N. ing. optois. a 24 Vac 50/60 Hz o 24 Vdc N. ing. optois. a 24 Vac/Vdc o 230 Vac (50/60 Hz) tot. ing.
SMALL 8 nessuno 8
MEDIUM 8 + 4 2 14
AVVERTENZE: -230 Vac 50/60 Hz (10/-15 %)
- i due ingressi a 230/24 Vac, hanno il medesimo polo comune e quindi saranno entrambi a 24Vac/Vdc o 230 Vac.
L’isolamento è principale.
- separare quanto più possibile i cavi dei segnali delle sonde e degli ingressi digitali dai cavi relativi ai carichi induttivi e di
potenza, per evitare possibili disturbi elettromagnetici.
Uscite analogiche
tipo e N. max. 2 uscite (Y1 e Y2) 0…10Vdc optois. e 2 uscite (Y3 e Y4) PWM taglio di fase con impulso a 5V di durata programmab.
alimentazione esterna 24 Vac/Vdc
risoluzione 8 bit
carico massimo 1 kΩ(10 mA) per 0…10 V e 470 Ω(10 mA) per PWM
Uscite digitali
numero massimo 8, 13, rispettivamente sulle schede: SMALL, MEDIUM; tipo a relè
Sono raggruppate a 3 con due morsetti di polo comune per un facile assemblaggio dei poli comuni. Prestare attenzione alla corrente circolante nei
morsetti comuni in quanto la stessa non deve superare la corrente nominale di un singolo morsetto, ovvero: 8 A per i morsetti estraibili. I relè sono
divisi in gruppi, a seconda della distanza di isolamento. All’interno di un gruppo, i relè hanno tra loro isolamento principale e quindi devono essere
sottoposti alla medesima tensione (generalmente 24 Vac o 230 Vac). Tra i gruppi c’è il doppio isolamento quindi i gruppi possono essere a tensione
diversa. In ogni caso tra ogni morsetto delle uscite digitali e il resto del controllo esiste il doppio isolamento.
gruppi: 1, 2, 3, 4, 5, 6 - 7 - 8 (relè di allarme) - 9, 10, 11, 12, 13
contatti in scambio: 1,3 rispettivamente sulle versioni SMALL, MEDIUM
potenza commutabile: 2000 VA, 250 Vac, 8 A resistivi, 2 A FLA, 12 A LRA secondo UL873, (30.000 cicli)
2 A resistivi, 2 A induttivi, cosϕ=0,6, 2(2) A secondo EN 60730-1, (100.000 cicli)
uscite a SSR: 2 in alternativa ai relè n˚ 7 e 8 (SMALL), 4 in alternativa ai relè n˚ 7, 8, 12 e 13 (MEDIUM);
24 Vac/Vdc, Pmax= 10 W
Collegamento al terminale utente
tipo asincrono half duplex a 2 fili dedicato
connettore per terminale tipo telefonico 6 vie
connettore per pLAN* connettore estraibile 3 vie
driver differenziale bilanciato CMR 7 V (tipo RS485)
Le distanze massime ammesse tra terminale e pCO1sono quelle riportate nella seguenta tabella:
con cavo telefonico con cavo schermato AWG24
resistenza del cavo (Ω/m) distanza massima (m) resistenza del cavo (Ω/m) distanza massima (m)
0,14 600 ≤0,078 600
0,25 400
* Nota: a differenza del pCOBe pCO2l’indirizzamento pLAN non avviene tramite dip switch ma tramite sequenze di operazioni sul terminale. A tal
proposito consultare il manuale software.
Altre caratteristiche
condizioni di immagazzinamento -20T70, 90 % UR non condensante
condizioni di funzionamento -10T60, 90 % UR non condensante
grado di protezione IP20, IP40 nel solo frontalino
inquinamento ambientale 2
classe secondo la protezione contro le scosse elettriche da integrare su apparecchiature di Classe I e/o II
PTI dei materiali per isolamento PCB: PTI 250; insulation material PTI 175
periodo delle sollecitazioni elettriche delle parti isolanti lungo
tipo azioni 1C
tipo disconnessione o microinterruzione microinterruzione
categoria di resistenza al calore e al fuoco categoria D (UL94 - V0)
immunità contro le sovratensioni categoria II
caratteristiche di invecchiamento (ore di funzionamento) 80.000
n. cicli di manovra operazioni automatiche 100.000 (EN 60730-1); 30.000 (UL 873)
classe e struttura del software Classe A
Il dispositivo non è destinato ad essere tenuto in mano.
Avvertenza: per applicazioni soggette a forte vibrazioni (1,5 mm pk-pk 10/55 Hz) si consiglia di fissare tramite fascette i cavi collegati al pCO1a
circa 3 cm di distanza dai connettori. Il programma applicativo potrà essere scaricato nella memoria flash attraverso la key “PCO100KEY0” o un PC
mediante il programma “WINLOAD32” da richiedere alla CAREL.
AVVERTENZE IMPORTANTI: Il prodotto CAREL è un prodotto avanzato, il cui funzionamento è specificato nella documentazione tecnica fornita col prodotto o scaricabile, anche anterior-
mente all’acquisto, dal sito internet www.Carel.com. Il cliente (costruttore, progettista o installatore dell’equipaggiamento finale) si assume ogni responsabilità e rischio in relazione alla fase di
configurazione del prodotto per il raggiungimento dei risultati previsti in relazione all’installazione e/o equipaggiamento finale specifico. La mancanza di tale fase di studio, la quale
è richiesta/indicata nel manuale d’uso, può generare malfunzionamenti nei prodotti finali di cui CAREL non potrà essere ritenuta responsabile. Il cliente finale deve usare il prodotto solo
nelle modalità descritte nella documentazione relativa al prodotto stesso. La responsabilità di CAREL in relazione al proprio prodotto è regolata dalle condizioni generali di contratto
CAREL editate nel sito www.Carel.com e/o da specifici accordi con i clienti.
L’apparecchiatura (o il prodotto) deve essere oggetto di raccolta separata in conformità alle vigenti normative locali in materia di smaltimento.
The appliance (or the product) must be disposed of separately in compliance with the local legislation in force on waste disposal.

Other manuals for pCO1 series

5

This manual suits for next models

12

Other Carel Controllers manuals

Carel c.pCO sistema User manual

Carel

Carel c.pCO sistema User manual

Carel mchiller compact User manual

Carel

Carel mchiller compact User manual

Carel pCO Series Troubleshooting guide

Carel

Carel pCO Series Troubleshooting guide

Carel PBB2 Series User manual

Carel

Carel PBB2 Series User manual

Carel uChiller User manual

Carel

Carel uChiller User manual

Carel easy User manual

Carel

Carel easy User manual

Carel AT-th Tune Series User manual

Carel

Carel AT-th Tune Series User manual

Carel SmartCella 3PH User manual

Carel

Carel SmartCella 3PH User manual

Carel pCO2 Series User manual

Carel

Carel pCO2 Series User manual

Carel pCO5+ User manual

Carel

Carel pCO5+ User manual

Carel k.Air User manual

Carel

Carel k.Air User manual

Carel HYVC000R0 Series User manual

Carel

Carel HYVC000R0 Series User manual

Carel ir33+ User manual

Carel

Carel ir33+ User manual

Carel compactSteam CHF User manual

Carel

Carel compactSteam CHF User manual

Carel ir32 Universale Guide

Carel

Carel ir32 Universale Guide

Carel MasterAria User manual

Carel

Carel MasterAria User manual

Carel boss Series User manual

Carel

Carel boss Series User manual

Carel pRack PR100 User manual

Carel

Carel pRack PR100 User manual

Carel KITCONT101SP User manual

Carel

Carel KITCONT101SP User manual

Carel pCO5 Manual

Carel

Carel pCO5 Manual

Carel FSC Series User manual

Carel

Carel FSC Series User manual

Carel pCO User manual

Carel

Carel pCO User manual

Carel ir33 Universale Guide

Carel

Carel ir33 Universale Guide

Carel MCH200-03 Series User manual

Carel

Carel MCH200-03 Series User manual

Popular Controllers manuals by other brands

Autoscript WSC-REC/-A user guide

Autoscript

Autoscript WSC-REC/-A user guide

PowerShield VoltGuard PSVG1500 manual

PowerShield

PowerShield VoltGuard PSVG1500 manual

Allen-Bradley Series B manual

Allen-Bradley

Allen-Bradley Series B manual

qtime qtime user manual

qtime

qtime qtime user manual

MICRO-LAM u-lam manual

MICRO-LAM

MICRO-LAM u-lam manual

Jantar REGIS F Series manual

Jantar

Jantar REGIS F Series manual

Mercoid Series MPC Installation and operating manual

Mercoid

Mercoid Series MPC Installation and operating manual

Atmel AT43USB324 manual

Atmel

Atmel AT43USB324 manual

NANOTEC SMCI47-S Technical manual

NANOTEC

NANOTEC SMCI47-S Technical manual

HomLiCon LCH5 Operation

HomLiCon

HomLiCon LCH5 Operation

BIFFI OLGA-H Installation, operation and maintenance manual

BIFFI

BIFFI OLGA-H Installation, operation and maintenance manual

JBL MSC1 owner's manual

JBL

JBL MSC1 owner's manual

emerald alarms EP-SA-CONT-RF user manual

emerald alarms

emerald alarms EP-SA-CONT-RF user manual

Shinko PCD-33A instruction manual

Shinko

Shinko PCD-33A instruction manual

Micro Air Corporation FX2-AH Operation manual

Micro Air Corporation

Micro Air Corporation FX2-AH Operation manual

Jupiter Avionics JA95-N22 Installation and operating manual

Jupiter Avionics

Jupiter Avionics JA95-N22 Installation and operating manual

Regada Rematic STR 1PA Installation, service and maintenance instructions

Regada

Regada Rematic STR 1PA Installation, service and maintenance instructions

ELECTROMEN EM-176A quick start guide

ELECTROMEN

ELECTROMEN EM-176A quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.