CASPR MEDIK User manual

Caution: Read manual carefully for proper procedures and operation.
OWNER’S MANUAL
Specications ● Installation ● Maintenance
CASPR MEDIK TM
CONTINUOUS HVAC DISINFECTANT TECHNOLOGY

2
Congratulations
on your purchase of the CASPR MEDIKcontinuous disinfection Solution.
This unit is designed to be installed into an existing HVAC system and used
as a virtually maintenance free enhanced system for providing low levels
of oxidizing molecules that will reduce microburden on all the surfaces of
the targeted area.
Please read and follow all service procedures outlined in this manual.
Contents
Indications of Use .........................................2
Product Contents ..........................................3
Installation Hardware .......................................3
Replacement Parts .........................................3
About CASPR MEDIK .......................................4
Specications .............................................4
Recommended Installation Tools ................................5
Installation Requirements ....................................5
Installation.............................................6 - 8
Maintenance/UV Lamp Indicator ................................ 9
Changing the NCC Cell...................................10 - 11
Warranty Information ...................................12 - 13
Indications of Use
CASPR MEDIK is an innovative no-touch disinfection technology-based
device that works without an operator to provide continuous reduction of
micro-burdens facility-wide. Proven in independent lab test to effectively
reduce clinically relevant pathogens like MRSA, Norovirus, Aspergillus
Niger, VRE, C. difcile and more, before they spread. Moreover. it has been
found to be:
• Safe to use in occupied spaces
• Works on all surfaces, including oors
• No operator or maintenance required
• Affordable for facility-wide use
• Strategic enough for unit specic targeting
• Easily & affordably installed in the existing HVAC

3
Product Contents
Installation Hardware
(4) Self-tapping Screws
(2) Cell Mounting Screws
Replacement Parts
Bulbs:
9” Bulb Part Number: BULB-HV-9-002-CASPR
14” Bulb Part Number: BULB-HV-14-002-CASPR
Cells(which includes bulbs):
9” NCC Cell Part Number: CELL-HV-9-002-CASPR
14” NCC Cell Part Number: CELL-HV-14-002-CASPR
NCC cell UV Bulb Ballast
Adhesive Gasket

4
Warnings
FEATURES:
• Replaceable NCC Cell
ELECTRICAL:
• 120-277 VAC
• 9” Unit - 47W (start-up), 36.8W (Operation)
• 14” Unit - 73W (start-up), 59.5W (Operation)
MECHANICAL:
• Distribution via air handler
About CASPR MEDIK
CASPR MEDIK is an enhanced “no touch” continuous disinfection device designed to
supplement normal cleaning and disinfection protocols.
CASPR MEDIKuses Natural Catalytic Conversion (NCC) to generate safe, low levels
of hydrogen peroxide. NCC technology replicates natural purifying processes by
using a high intensity light to activate a proprietary metal catalytic coating, converting
water vapor into hydrogen peroxide. Hydrogen peroxide acts as an oxidizer
inactivating surface and air pathogens. It can compromise cellular integrity by
disrupting cell walls, or internal molecular structures, rendering contaminants
harmless.
Specifications
To reduce the risk of electric shock, this equipment may have a grounding type plug that has a third
(grounding) pin. This plug will only t into a grounding type power outlet. If the plug will only t into a
grounding type power outlet. If the plug does not t into the outlet, contact qualied personnel to install
the proper outlet. Do not alter the plug in any way.
WARNING! - Unit should be mounted at least 24 inches from the heat exchanger or heating element.
Placing the photocatalytic cell too close to the heating element can cause the photocatalytic matrix
to combust.
WARNING! - UV light in operation. Disconnect unit from power supply before servicing.
Failure to follow warnings may result in severe eye damage.
!
!
SIZE: (HxWxD)
• 9” Unit: 9¾” x 9¾” x 11”
• 14” Unit: 9¾” x 9¾” x 16.75”
WEIGHT:
• 9” Unit: 3.5 lb
• 14” Unit: 3.7 lb

5
Recommended Installation Tools
Installation Requirement
1. Unit may be installed up or down stream of the
air handler in the HVAC system as long as it is
behind the filter.
2. The ductwork around the installation area
should be cleaned and dry to insure proper
adhesion of the gasket materials and any tape
used.
3. One circular opening, measuring
approximately 4.5”, will need to be cut into the
existing duct work to install the unit properly.
Electrical Requirement
Hardwiring Requirement
To use the 120V plug, be sure to locate the unit within 6 ft. of a standard 120V
grounded outlet. Long term use on an extension cord is not recommended due to
safety considerations.
Permanent wiring of the unit into your HVAC system should be done by a licensed HVAC
Installer or Electrical Contractor only.
For 110-277V: Black = L1, White = Neutral, Green - Ground
For International Applications: Brown = L1, Blue = L2, Green/Yellow = Ground
A
A - 4.5” Hole Saw Bit
B - 3/8” Drill Bit
C - Drill/Power Driver
B C D E F
D - Utility Knife
E - STET
F - Phillips Head Screwdriver

6
Installation
1. Find a suitable location to mount your
CASPR MEDIK Unit.
2. If necessary, cut away insulation for your
plate to adhere to the duct.
3. Using the Adhesive Gasket Plate, trace the
hole location onto the duct.
4. Use the Hole Saw and Drill to cut out the
marked hole.

7
Alternative Cutting Method
1. Using the Adhesive Gasket Plate, trace the
hole location onto the duct.
2. Drill holes around the outside edges of the
prviously marked hole but inside the outer
holes of the Adhesive Gasket Plate.
3. Use the Tin Snips to cut out the space
around the marked hole.

8
Installation
5. Remove the plastic backing on
your Adhesive Gasket Plate.
6. Press the Adhesive Gasket Plate
onto the duct. Secure with the
(8) Self-Tapping Screws.
7. Connect the Cell to the Ballast using
the two (2) cell mounting screws.
8. Place the unit and cell through the
opening and align the four studs
with the four holes in the ballast.
Secure the unit by twisting
clockwise to lock into place.
9. Plug the Unit Power Cable
into the receptacle or have a
Licensed Electrician or HVAC
Installer hardwire the unit
directly into the HVAC system.

9
Maintenance / UV Lamp Indicator
Your CASPR MEDIK requires no periodic maintenance beyond normal
replacement of the bulb at 18 months and the NCC cell with bulb every
3 years.
Note: Proper Operation of the unit is shown with a Red or Green LED
light on the face of the unit (color variants do not affect Functionality of
Unit). If the Ballast fails, or if power to the unit has been powered off/
disconnected, the UV light will be off. If the UV lamp fails, the Red or
Green LED light will also be off.
Disposal Of The NCC Cell
Please do not throw the used NCC Cells in the garbage.
The special germicidal UV bulb used in the CASPR MEDIK contains
some insignificant amount of mercury. Contact your local Waste
Management Center for a proper disposal procedure.

10
Changing The NCC Cell
1. Remove the Unit Power Cable from the
receptacle or ensure the unit isn’t powered.
2. Twist the Ballast Housing counter-clockwise
to unlock the unit from the mounting plate.
Pull the unit from the duct.
3. Remove the (2) Screws holding the NCC
Cell in place and remove the NCC Cell
from the Unit Cover.
WARNING: While removing the old bulb, be cautious about "rocking"
it back and forth as that may damage the ceramic bulb socket. To
avoid damage, pull the bulb straight out without any lateral motion.

11
Changing The NCC Cell
4. Exchange the Old NCC Cell with the new
NCC Cell and replace the (2) Screws that
hold it in place.
5. Replace the Unit in the duct and turn
clockwise to lock in place.
6. Place the Unit Power Cable back into the
receptacle or repower your unit.

12
Warranty Information
NDS Sales LLC d/b/a CASPR Technologies (as “Seller”) offers the following
Express Limited Warranty to a buying customer (a “Buyer”)
of a CASPR product (the “Product”):
Seller warrants to Buyer that (a) the Product will be free from defects caused by
faulty workmanship or materials for three years from date
of purchase when operated under normal conditions and in accordance with
Seller’s recommended use (the “Product Warranty Period),”
and that (b) the Components (comprised of a bulb and a cell) will be free from
defects caused by faulty workmanship or materials for one
year from date of purchase when operated under normal conditions and in
accordance with Seller’s recommended use (the “Components
Warranty Period).”
SELLER EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES, WHETHER
EXPRESS OR IMPLIED.
Should Buyer discover a covered defect within the Product Warranty Period or
the Components Warranty Period, Seller will repair or replace (at Seller’s cost)
the Product and/or the Components. Buyer’s sole and exclusive remedy for
Product or Components defects is limited to repair or replacement.
To confirm coverage or to schedule repair or replacement under this Express
Limited Warranty, Buyer should contact Seller at www.casprtech.com/warranty
and provide the serial number located on the Product and proof of purchase.
Absence of a serial number or proof of purchase may void the Express Limited
Warranty.
This Express Limited Warranty does not extend to or cover Product damage
caused by accident, fire, flooding, exposure to temperature extremes, abuse,
misuse, improper or unauthorized installation, modification, misapplication, or
repairs performed by persons other than Seller. Repairs performed by persons
other than Seller or Seller’s authorized representative will void the Express
Limited Warranty.
This Express Limited Warranty does not extend to or cover incidental or
consequential damages incurred by Buyer arising from, related
to, or in connection with, any Product or Components defects, including but not
limited to downtime costs, loss of use, loss of revenue,
and/or loss of profits.
SALES THROUGH DISTRIBUTOR OR RESELLER
To the extent the Product is purchased by Buyer from an authorized CASPR
distributor or reseller, this Express Limited Warranty passes
through to Buyer.

FOR U.S. APPLICATION ONLY
Product warranties are governed by state and federal laws and may vary from
state to state. This Express Limited Warranty provides
Buyer with specific assurances regarding repair or replacement of the Product.
Other warranties are expressly negated.
FOR CANADIAN APPLICATION ONLY
Canadian, provincial, and territorial sales laws may govern implied warranties.
This Express Limited Warranty provides Buyer with
specific assurances regarding repair or replacement of the Product. Other
warranties are expressly negated. Should there be a difference
between this Express Limited Warranty and Canadian law regarding implied
warranties, Canadian law will control.
13

www.casprTech.com
V.IN-M-MED-03-08012023
Corporate Office
1343 W. Causeway
Approach
Mandeville, LA
US 70471
1-844-717-8819
Table of contents
Other CASPR Air Cleaner manuals