Circutor RGU-10 MT User manual

Code Type Sensivity (A) Tripping delay (s) Communications
P24642 RGU - 10 MT
0,03-0,1-0,3-0,5-1-3
by direct adjustment
5-10-30 by SETUP
INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1
by direct adjustment
3-5-10 by SETUP
No Available
P 2 X X X X 0 0 X
Código
Code
Código interno
Internal code
Tensión de
alimentación
Power supply
230 V a.c.
110 V a.c.
0
1
RGU-10 MT Electronic earth leakage protection relay with self-reclosing system
For instance, RGU-10 MT supplied by 110 V a.c.
GENERAL DESCRIPTION
- Device with programmable differential relay with self-reclosing system. Symbol in LCD.
- It has 2 independents outputs by relays. Trip and locked by reclosing.
- It has 1 input for external Trip/Reclose. This input is not opto - coupled.
- Mounting in Rail DIN 46277 (EN 50022) or panel 72x72 by mean accessory (M5ZZF1)
- Associated to a WG/WGS Series external , toroidal current transformer.
- It must be asociated to a MCB motorized with or without a trip coil.
- It verifies connection with differential transformer WG/WGS by means inductive test.
- Leakage detection and measurement is via calculating its true efective value (TRMS).
- Display settings values and instant residual current to its accociated units.
DESCRIPTION LED AND BUTTONS.
- Shows equipment status via a display and 2 LED.
- 5 button equipment setup and setting.
- 2 button equipment TEST and RESET.
INDICATION BY LED AND DISPLAY.
- TRIP RELAY. LED and display signals a change
of status by changing from green to red.l
Display event type messages or values.
- BETWEN RECLOSURES.
The yellow LED is blinking. Red Display shows the
tripp cause fluctuating with partial reclosures No
- LOCKED BY RECLOSURES.
The yellow LED is fixed. The equipment arrives al
maximun number of reclosures established by the
self-reclosing sequence. Red display shows the cause.
- No OF RECLOSURES. By short press on PROG the display shows the number of reclosures by
earth leakage, short ciruit-overload faults and total number. The partial number are floating pages
In these pages it can configure the self-reclosing sequence by press REC button.
RECLOSING THE EQUIPMENT.
- BY TRIP / LOCKED BY RECLOSURES
1. Automathic (earth leakage, short ciruit-overload faults or manual). Enabled.
2. Manual reclose by pushing button RESET
3. External reclose sytem by remote or communications signal. When it forces a trip by remote
signal, only it can reclose by another remote signal.
4. Manual reclose circuit breaker associated.
In the case 2 and 3 the all partial counters of reclosures returns to a zero.
RELAY PARAMETERS SETTING ( t, I y std/+ )
d d
- , t.
d
SETTING TRIP DELAY The message and two values appear on the screen after
pressing the button. The lowest value indicates the current set value and the highest is the td
values to be configured which are displayed by pressing The selected value to be saved is .
displayed by showing the message SAVE.
- , I. I. .
dd
SENSITIVITY SETTING The same operation as above setting is carried out by pressing
- SIGNALLING CONTACTS RELAY STATE, std/+ . Select the default position of the relay contacts
7-8-9 that indicates the situation of locked by reclosures of the device . In (Std) 8-7 NA / 8-9 NC
and (+) 8-7 NC / 8-9 NA and appears the symbol in display.
- SELF-RECLOSING SYSTEM, REC. In reclosure partial numbers by press REC button we
configure the self-reclosing sequence referred at the page which it’s showing us. By default is
configured nº10 by earth leakage protection and nº5 by short-circuit/overload protection.
Tripping cause Message display
Test
Remote signal trip/reclose
Earth leakage fault
Short circuit / Overload fault
TESt
EXT
DIF / valor
MAG
PROG
+
Others MESSAGES by display
SAVE
EXIT
OVR
ERRt
Enter setting values
Exits setting mode
Value reading off scale
Poor toroidal conection
M98205801-03-21A
P24642001
PARAMETERS BY
DIRECT ADJUSTMENT
-DELAY SETTING
-SETUP ROTATION
-SENSIVITY SETTING
-CONTACTS SETTING NO/NC
-ENABLE/DISABLE
SELF-RECLOSING SYSTEM
REC
SREC No RECLOSURES TIME SEQUENCES RESET TIME
RECLOSE SEQUENCES BY EARTH LEAKAGE CURRENT FAULT
SREC No RECLOSURES TIME SEQUENCE RESET TIME
RECLOSE SEQUENCE BY SHORTCIRCUIT/OVERLOAD FAULT
- Tipo Relay type: Electronic class A. High frequency current filtering.
- Rated power supply voltage: 230 o 110 Va.c. (+/- 20%) 50/60 Hz, 6 VA
- :Connections
2
0,127 - 2,082 mmPermissible cable section:
- Reclosing type: Authomatic, RESET button or by cutting power supply.
- : -10ºC / 50ºCOperating temperature
Recommended tightening torque: 0.5-0.6 Nm
TECHNICAL FEATURES
: 250/230 V a.c.Rated voltage/Maximum switching voltage
Maximun Voltage: 275 Va.c.
- 13-14-15, 7-8-9 and 5-6Switch Output contact features
: 6/10 A a.c.Rated current/Maximum instant current
Length of cable to strip: 7 mm
AC: 2,500 V·ARated load in
Input not using optocoupler
-Characteristics input remote Trip/Reclose 1-2
Contacts protected by varistor
- Varistor Features
REC
REC
MT
WARNING: The reclosing sequences marked by are only for motorized circuit breakers with or
without trip coil. I >63 A.
N
Capacity:
Maximun DC Load Breaking
Maximun opening current
Electrical useful life for AC
loads: No of cycles
MAG
¡ IMPORTANT !
The relay only self-recloses before a trip by earth leakage, short-circuit/overload current fault. The Test (red button) only
verifies the relay trips the protection. It recloses only by manual pressing RESET button.
0 DISABLED
1 2 1 minute 30 minutes
2 2 1 minute 60 minutes
3 2 90 s 30 minutes
4 2 90 s 60 minutes
5 2 3 minutes 30 minutes
6 ... ... ...
7 ... ... ...
8 ... ... ...
0 DISABLED
1 6 8, 16, 30, 59, 115 and 224 s 15 minutes
2 30 20, 40 s and 5 min. to the end 15 minutes
3 8 30 s, 1, 2, 3, 4, 5, 6 and 7 min 15 minutes
4 6 10, 20, 30, 60, 130 and 600 s 15 minutes
5 6 2, 4 y 8 min. to the end 15 minutes
6 7 30 s, 1, 2, 3, 4, 8 and 16 min 30 minutes
7 10 1 min 30 minutes
8 10 90 s 30 minutes
9 8 2, 4 y 6 minutes to the rest 15 minutes
10 10 3 minutes 30 minutes
11 7 2, 4, 8, 16, 32, 32 and 32 minutes 15 minutes
12 31 2, 4 and 6 minutes to the rest 15 minutes
13 6 8 s 15 minutes
14 ... ... ...
MAG
MAG
MAG
MAG
MAG
MAG
MAG
REC
REC
GREEN LED: ON
RED LED: TRIPPED BY FAULT
SCREENS / SETUP
R
RESET button: It reinitiates the operation of the equipment by any event
that tripps it.evento. It indicates the equipment version.
YELLOW LED: Locked by reclosures (fix)
Betwen reclosures (blinking)
- RST.C, ( ), initiates the partials counters.NO
- TRIP, ( ), breaking element (without trip coil)MA
- FREQ, ( ) frecuency (Hz)50
- LIM,( ), range of values (Id / td)1s, 3A
- SEC. T, ( ),contacts 5-6 [NA/NC]NO
Default values in SETUP
TEST button: It makes a forced firing to verify the protection.
Button
FREQ
LIM
SEC.T
TRIP
Button
60 Hz
10 s, 30 A
RST.C
Mb
Pulsador PROG
PsI
50 Hz
1 s, 3 A
St
MA
YES
NO
SETUP SETTINGS
A long press in activates the SETUP settings. In this operating PROG
mode by pressing buttons and it shows the submenus and the PROG
setting values to modify . With thesePROG new setting values are
validated, the message SAVE is shown by display and exits setting
mode. In case of keypad inactive, it exits setting mode and the message
EXIT is shown by display wihtout changes.
In SEC.T it defines the working mode of outputs contacts relay 5-6. By
default 5-6 is normally open (St )
In TRIP (Circuit Breaker), The value is used when the CB don’t need a
trip coil. The value is used when CB needs one.
(LOCKED SIGNAL)
(See graph)
(See graph)
PROG PROG
REC
REC
BY SHORT-CIRCUIT/OVERLOAD CURRENT
REC
REC
PROG
BY EARTH LEAKAGE CURRENT
879
12
TERMINAL CONNECTIONS DESIGNATIONS DIMENSIONS
10 11
45
52,5 43,5
85
67,9
Fijación carril DIN 46277 (EN 50022)
Vial Sant Jordi s/n
08232 Viladecavalls (Barcelona) SPAIN
Tel: (+34) 93 745 29 00
Fax: (+34) 93 745 29 14
6
5 TRIP COIL. CONTACT NO
MOTORIZED CIRCUIT BREAKER WITH TRIP COIL
CONNECTION RGU-10 MT + WG/WGS + MOTORIZED CIRCUIT BREAKER WITH OR WITHOUT TRIP COIL
POWER SUPPLY
TRIPPING CONTACTS
13
14 15
EXTERNAL TRIP/RECLOSE
SIGNALING CONTACTS LOCKED BY RECLOSURES
SUPPLY A.C.
CARGA
LOAD
NL1 L2 L3
M
U>
NL
C1
C2 OI12
11
1S1
1S2
Type WG
1S11S2
ON / OFF externo
External ON/OFF
Disparo por BOBINA
Trip by TRIP COIL.
7 8
1 2 4 56
10
11
13 14 15
Reset
Test
RGU-10 MT
12
39 CARGA
LOAD
NL1 L2 L3
M
NL
OI12
11
Type WG
1S11S2
ON / OFF externo
External ON/OFF
Disparo por MOTOR OFF
Trip by OFF MOTOR.
7 8
1 2 4 56
10
11
13 14 15
Reset
Test
RGU-10 MT
12
39
1S1
1S2
MT - C- 62/64
MT - C- 62/64
¡ WARNING !
The input 1-2 must be closed. If 1-2 is open the equipmen is tripped and appears the message EXT on red
backlight display
: A1 - A2
34 : 1S2 - 1S1
CORE BALANCE TRANSF.
:COMMON : OFF MOTOR : ON MOTOR
MOTORIZED
CIRCUIT BREAKER
CIRCUIT BREAKER STATUS
12
11 CONTACT NC
OPEN: TRIP
CLOSED : RECLOSE
: COMMON : OUTPUT NO : OUTPUT NC
RGU-10 MT Electronic earth leakage protection relay with self-reclosing system
SUPPLY A.C.
SETTING SETUP
TRIP:
SEC.T: St (in case of shunt coil)
Pt (in case of undervoltage coil)
SETTING SETUP
TRIP:
SELF-RECLOSING SEQUENCES CONFIGURATION
M98205801-03-21A
MT - TSD

Other manuals for RGU-10 MT

2

This manual suits for next models

1

Other Circutor Relay manuals

Circutor RGU-10C User manual

Circutor

Circutor RGU-10C User manual

Circutor P24457 User manual

Circutor

Circutor P24457 User manual

Circutor RGE Series User manual

Circutor

Circutor RGE Series User manual

Circutor CBS-4C-NC User manual

Circutor

Circutor CBS-4C-NC User manual

Circutor RGU-10 RAL User manual

Circutor

Circutor RGU-10 RAL User manual

Circutor RGU-10C User manual

Circutor

Circutor RGU-10C User manual

Circutor RGU-10 MT User manual

Circutor

Circutor RGU-10 MT User manual

Circutor CBS-4 Series User manual

Circutor

Circutor CBS-4 Series User manual

Circutor RGU-10C User manual

Circutor

Circutor RGU-10C User manual

Circutor RGU-100A User manual

Circutor

Circutor RGU-100A User manual

Circutor WRU-10 RAL User manual

Circutor

Circutor WRU-10 RAL User manual

Circutor WRU-10 User manual

Circutor

Circutor WRU-10 User manual

Circutor RGU-10 MT User manual

Circutor

Circutor RGU-10 MT User manual

Circutor RAGK-0.3 User manual

Circutor

Circutor RAGK-0.3 User manual

Circutor RGU-10C User manual

Circutor

Circutor RGU-10C User manual

Circutor RGU-100B User manual

Circutor

Circutor RGU-100B User manual

Circutor RGU-10 User manual

Circutor

Circutor RGU-10 User manual

Circutor CBS-4 Series User manual

Circutor

Circutor CBS-4 Series User manual

Circutor CBS-4C User manual

Circutor

Circutor CBS-4C User manual

Circutor RGU-10 User manual

Circutor

Circutor RGU-10 User manual

Circutor P11941 User manual

Circutor

Circutor P11941 User manual

Circutor CBS-400B User manual

Circutor

Circutor CBS-400B User manual

Circutor RGU-2 User manual

Circutor

Circutor RGU-2 User manual

Circutor RGU-10C User manual

Circutor

Circutor RGU-10C User manual

Popular Relay manuals by other brands

teko ASTRA-BRA user guide

teko

teko ASTRA-BRA user guide

Seg MRIK3 manual

Seg

Seg MRIK3 manual

IFM Electronic ecomat 200 Monitor AL-3 operating instructions

IFM Electronic

IFM Electronic ecomat 200 Monitor AL-3 operating instructions

ABB SPAJ 111 C user manual

ABB

ABB SPAJ 111 C user manual

Basler BE1-50/51B-217 instruction manual

Basler

Basler BE1-50/51B-217 instruction manual

OEZ SE-BD-0040-MTV8 Instructions for use

OEZ

OEZ SE-BD-0040-MTV8 Instructions for use

Kyongbo Electric K-PAM 10 Series user manual

Kyongbo Electric

Kyongbo Electric K-PAM 10 Series user manual

ZIGBEE ENVILAR ZG302 manual

ZIGBEE

ZIGBEE ENVILAR ZG302 manual

Bticino 3584C manual

Bticino

Bticino 3584C manual

Bender CMD420 Installation Bulletin / Reference Guide

Bender

Bender CMD420 Installation Bulletin / Reference Guide

VAMP 50 Operation and Configuration

VAMP

VAMP 50 Operation and Configuration

Rielta IR-RK installation guide

Rielta

Rielta IR-RK installation guide

BECKWITH ELECTRIC M-3520 Instruction book

BECKWITH ELECTRIC

BECKWITH ELECTRIC M-3520 Instruction book

NIVELCO NITIME JEL-111 user manual

NIVELCO

NIVELCO NITIME JEL-111 user manual

KRIWAN INT69 F Diagnose installation instructions

KRIWAN

KRIWAN INT69 F Diagnose installation instructions

ABB RXHL 422 Connection and Settings Guide

ABB

ABB RXHL 422 Connection and Settings Guide

Schrack LSZ0Y001 operating instructions

Schrack

Schrack LSZ0Y001 operating instructions

Phoenix Contact PSR-MM35 Original operating instructions

Phoenix Contact

Phoenix Contact PSR-MM35 Original operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.