McGraw-Edison VR-32 Regulator and CL-5 Series Control
1-11
a. The metering and operation is based upon the
RMS value of the fundamental power line
frequency. Thus, the metered values exclude the
influences of harmonic voltages which are
probably present on the line. A true-RMS meter
however, will include these harmonic voltages in
its calculations of the RMS voltage. This does
not present a problem with either metering
device, since each device uses a different
approach to metering.
b. The calibration of the voltmeter being used for
measurement is probably not exact. Even a
very good meter with a basic accuracy of 0.5%
could be in error by as much as 0.6 V (out of
120 V), and still be considered to be “in-
calibration.” The control is calibrated using a
conditioned power supply and reference
voltmeters which are periodically calibration-
checked, traceable to the National Bureau
of Standards.
NOTE: The control is designed to perform ratio correc-
tion in software. Through the use of the ratio correcting
transformer (RCT) located on the back panel, the
voltage brought to the front panel is usually already
corrected to the 120 V base voltage. However, there are
some ratings in which this voltage is not fully corrected
by the RCT. Column 6 in Table 1-10 or 1-11, page 1-21
gives a general indication of these voltages, however,
always refer to the nameplate which provides the
specific information for the particular regulator.
Whatever voltage results from dividing the nominal
system voltage, FC43, by the overall P.T. ratio, FC44, is
considered by the control to be the nominal voltage.
Therefore, when that voltage appears at the input of the
control, 120 volts will be reported as the output voltage,
FC6 (whether the nominal is actually 120 or not).
Likewise, the compensated voltage, FC8, and input
voltage, FC7, will be scaled accordingly. If the regulator
is equipped and programmed for reverse power
operation, the voltage displayed at Function Code 8 will
be correct even during reverse power conditions.
The load voltage, FC10, source voltage, FC11, and
calculated parameters such as the kVA, kW and kvar are
not scaled similar to FCs 6 and 8. Instead, they reflect
the true value of line voltage.
NOTE: The voltage measured at the test terminals
during reverse power flow is the new source voltage at
the L bushing of the regulator.
Removal From Service
Determining Neutral Position
Return the regulator to neutral. The regulator can be
safely removed from service without interrupting load
continuity only in the neutral position. It is recommended
to use more than one method to determine whether a
regulator is on neutral.
To Return the Regulator to Neutral
1. Use Raise/Lower switch to bring regulator to neutral
position.
2. When in neutral, neutral light will light continuously
and position indicator will point to zero.
WARNING: In order to prevent possible
damage to equipment and injury to personnel,
prior to bypass switching being attempted, the
following must be accomplished: 1) The regulator
must be placed in the neutral position; 2) action must
be taken to prevent tap changer operation while the
bypassing is being performed.
If the regulator is in any position other than
neutral, part of the series winding will be shorted
if bypass switch is closed. This results in high
circulating current which can severely damage
the regulator. If catastrophic failure occurs, it
could pose a threat of injury or death to operating
personnel.
WARNING: A regulator should be bypassed
with the line energized only if both the position
indicator and the neutral light indicate neutral. If both do
not indicate neutral, the line should be de-energized to
avoid shorting part of the series winding.
WARNING: Always use the control switch
(labeled AUTO/REMOTE-OFF-MANUAL) to
operate the regulator, not the power switch. Failure to
do so may result in the tap changer stepping off
of neutral immediately upon being energized.
WARNING: To stop the regulator on the
neutral position, the control switch should be
turned to OFF during the switching operation from
positions “1” or “-1” to position zero. Switching to
OFF prior to reaching the neutral position prevents
overshoot.