
Trouble Shooting
www.climatecenter.co.uk
Daikin Trouble Shooting Guide
Past & Current Models
Daikin Fault Codes
Indoor Fault Codes
Fault Code Definition Supposed Causes Split Skyair VRV Package
A0 External protection active External protection wired to T1-T2 active •••
A1 Failure of indoor PCB Defect of PCB or noise ••••
A3 High water level Float switch open circuit •••
A5 HP control in heating or freeze
protection in cooling
Poor airflow, short circuit, EEV, refrigerant charge,
indoor coil sensor incorrect value
•
A6 Fan motor failure Locked, over current, over load ••••
A7 Failure of louvre motor Louvre motor/indoor PCB failed • •
A8 Failure of power supply Over current of AC input, defect of supply • •
A9 EEV failure Defect of EEV motor, indoor PCB • •
AF High water level Float switch open circuit while thermo off • •
AH Failure of dust collector Defect of dust collecting element, PCB •••
AJ Capacity setting error Capacity setting adaptor missing •••
C1 Communication failure. Between
main-sub PCB
Failure of communication fan motor
control driver
• •
C4 Indoor coil sensor Open/short circuit ••••
C5 Suction pipe sensor Open/short circuit • • •
C6 Failure of fan motor driver Defect of fan motor sensor, control driver • •
C7 Front panel driving motor fault Defect of limit switch, front panel driving motor •
C9 Return air sensor fault Return air sensor open/short circuit ••••
CA Discharge air sensor fault Discharge air sensor open/short circuit • •
CC Failure of humidity sensor Failed humidity sensor • •
CJ Failure of remote sensor Defect of remote controller sensor • •
Daikin Fault Codes
Outdoor Fault Codes
Fault Code Definition Supposed Causes Split Skyair VRV Package
E0 Protection devices tripped Outdoor safety device tripped •••
E1 Failure of outdoor PCB Defect of PCB or noise ••••
E3 High pressure High pressure switch tripped •••
E4 Low pressure Low pressure switch tripped •••
E5 Inverter compressor lock Inverter compressor locked •••
E5 Inverter compressor to hot Compressor windings too hot •
E6 DOL compressor locked High current draw ••••
E7 Fan motor failure Failed fan motor, PCB ••••
E8 Inv compressor high current Compressor, PCB •••
E9 EEV motor failure EEV motor, PCB •••
EA 4-way valve failure Defect of valve, PCB, sensor •
EC Inlet water temperature Abnormal water temperature •
EF Thermal storage unit defect Thermal storage EEV, PCB, sensor •
F3 High discharge temperature Discharge temperature over 110°C ••••
F6 High pressure in cooling Detected by outdoor coil sensor •
F6 Over charged Refrigerant over charge • •
H0 Compressor sensor system All sensors disconnected •
H1 Failure of humidifier damper Defect of limit switch/damper •
H3 Failure of hp switch High pressure switch open circuit ••••
H4 Failure of lp switch Low pressure switch open circuit • •
H5 Failure of compressor sensor Defect of compressor overload sensor •
H6 Compressor position failure Position detection error •
H7 Failure of fan motor signal Defect of fan motor, PCB •••
H8 Compressor input error Defect of transistor, PCB, reactor •
H9 Failed ambient sensor Sensor open short circuit ••••
J1 Failed pressure sensor Pressure sensor failed • •
J2 Failed current sensor Defect of current sensor, PCB, compressor •••
J3 Failed discharge pipe sensor Discharge pipe sensor open/short circuit ••••
J4 Failed outdoor coil vapour sensor Sensor open/short circuit • •
J5 Failed suction pipe sensor Sensor open/short circuit ••••
J6 Failed outdoor coil sensor Sensor open/short circuit ••••
J7 Failed liquid pipe sensor Sensor open/short circuit •••
J8 Failed liquid pipe sensor Sensor open/short circuit •
J9 Failed sub cool heat exchanger sensor Sensor open/short circuit ••••
JA Failed high pressure sensor High pressure sensor open/short circuit •••
JC Failed low pressure sensor Low pressure sensor open/short circuit •••
JH Failed oil temperature sensor Open/short circuit •