DAITEM 155-21X User manual

Upgraded for e-Nova applications

94
GB
Contents
1. Introduction ................... 94
1.1 ow the detector
works......................... 94
1.2 Description................ 95
2. Power supply................. 96
3. Recognition
programming................. 96
4. Installing the detector .. 97
4.1 Choosing the best
place.......................... 97
4.2 Testing the radio
range at the chosen
location ..................... 98
4.3 Fixing the detector
in place...................... 97
4.4 Installing several
detectors
in a network ............ 100
5. Testing the detector.... 100
6. Manually disabling
the detector ................. 103
7. Indications ................... 104
7.1 Alerts ...................... 104
7.2 Faults ...................... 104
8. Maintenance................ 105
8.1 Servicing the
detection head........ 105
8.2 Changing
the battery .............. 106
8.3 During DIY work ..... 106
9. Technical data ............. 107
10. User sheet.................. 109
1. Introduction
1.1 How the detector works
The heat detector detects rises in temperature that trigger an
alarm in the following cases:
• when the room temperature rises at an abnormal speed,
or
• when the room temperature reaches between 54°C and
70°C,
(also refer to the table in the Technical Data section).
The heat detector is especially suitable for detecting fires that
spread quickly or at an average speed and in places where an
optical smoke detector cannot be used:
• in a kitchen where there are cooking fumes,
• in uninhabited places where there is a smoky atmosphere or
a lot of dust (e.g. garages).
The heat detector can be:
• used as a stand-alone unit,
• integrated into a Daitem alarm system,
• interconnected in a hard-wired network of up to 40
detectors (heat or smoke).
IMPORTANT: the heat detector is not supposed to replace
smoke or gas detectors to ensure the safety of people
against smoke or gas, and notably in rooms such as
bedrooms, playrooms and other living areas.
IMPORTANT: the heat detector is designed to protect
homes or the private areas of buildings. It is not designed
for public assembly buildings or buildings housing workers.

95
GB
Red LED indicating detector status
Test button
White LED
(safety lighting
when heat is
detected) rogramming
key 0 Lithium
battery
connector
roduct
replacement
date
Guarantee sticker
In stand-alone mode, the heat detector responds as follows during the heat detection period:
uarantee sticker: remove the pre-cut part of the sticker and stick it to the guarantee
certificate in the user manual supplied with the control panel. If you are adding the siren to
an existing system, use the guarantee sticker provided with this product.
Heat detector
transmitting the heat
detection signal
Other hard-wired
interconnected heat
detectors
the LED flashes
quickly
-
a built-in modulated alarm
sounds on a continuous
basis (85 dB(A) at 3m)
a safety
halo lights
up
a safety
halo lights
up
Red LED indicating
detector status White LED Sounding
1.2 Description
a built-in modulated alarm
sounds on a discontinuous
basis (85 dB(A) at 3m)
When connected to a Daitem
alarm system the detector
responds as follows when it
detects heat:
• triggering of the control
panel and security system
wireless sirens in fire
sounding mode for 5 min.,
• triggering of the telephone
dialler.
IMPORTANT: the heat detector should be replaced every
ten years.

96
GB
10 s max.
Press *then #on the
control panel keypad Press & hold the programming key 0 for 10 sec.
until the control panel responds
Carry out the programming sequence described below:
)))))
“beep, fire detector n° X”
You can record a personalised message to identify the fire detector by voice (see the
control panel installation manual, § on Voice identification message).
Connect the lithium battery making sure it is the right way round.
ÒThe red LED flashes for 15 sec, then once every 10 sec to indicate that the detector is
working normally.
2. Power supply
3. Recognition programming
IMPORTANT: during recognition programming, the product to be programmed for use with
the control panel does not need to be placed next to it. In fact, we recommend you place
the product at a short distance from the control panel (at least 2 m away).
Programming enables the heat detector to be recognised by the control panel.
To programme the heat detector, the control panel must be in installation mode. If it is not,
press:
then press:
master code engineer installer code
then

97
GB
4.1 Choosing the best place
The detector must be placed:
• in rooms where there is a risk of fires
spreading quickly or at an average speed,
• in rooms with an aggressive or difficult
environment such as kitchens (cooking
fumes), garages (smoky atmosphere), and
other unoccupied premises or rooms where
there is often a lot of dust,
• preferably at the centre of the ceiling but
positioned so that it is affected by any
abnormal rises in temperature,
• if the detector cannot be installed in the
centre of the ceiling, install it more than 50
cm away from the corners of the room (Fig.
1 and Fig. 2),
• far away from ventilation grilles that may
spread the heat,
• more than 50 cm away from obstacles
(walls, partitions, beams, etc.),
• at either end of corridors more than 8 m
long,
• far away from potential sources of electrical
interference (electricity meter, metal cabinet,
etc.),
• if it is to be installed on a metal wall, insert a
shim made of non-magnetic material (wood
or plastic).
The detector must not be placed:
• in rooms where a sudden and considerable
rise in the room temperature would cause
untimely triggering of the alarms (e.g.
sudden sunlight),
• in rooms where there is a need to protect
people against smoke or gas(bedrooms,
children’s playrooms, converted cellars,
occupied lofts, emergency exits, etc.),
• near fluorescent tubes,
• directly on a metal surface,
• in a room where the temperature could drop
below -10°C or rise above +55°C, as this
will prevent the detector from operating
properly,
4. Installing the detector
Make sure there is a distance of at least 2 m between each product, except between two
detectors.
IMPORTANT: the heat detector is not supposed to replace smoke or gas detectors to
ensure the safety of people against smoke or gas, and notably in rooms such as bedrooms,
playrooms and other living areas. The heat detector is designed to detect fires in places
where an optical smoke detector cannot be used. For basic protection, a smoke detector
should be installed in at least each bedroom (refer to smoke detector manual).

98
GB
4.2 Testing the radio range
at the chosen location
1. old down the detector programming key
0 or the test button until the built-in
sounding can be heard:
• correct: the control panel confirms the
radio link with a voice message “beep,
fire detector n° X”,
• incorrect: if there is no voice message,
move the heat detector closer to the
control panel.le.
2. Put the control panel back in user mode by
pressing:
• in rooms where the relative humidity might
rise above 95% (without condensation),
• close to heating, cooling or air vents.
Mounting examples:
Recommended
location
d > 50 cm
plafond
Fig. 1
d > 50 cm
Fig. 2
IMPORTANT: the control panel must be in
installation mode to perform this test (see
Recognition programming).
engineer installer code

99
GB
IMPORTANT: to be able
to thread the cables for
surface mounting,
remove the 2 fixing
spacers and insert them
between the ceiling and
the mounting base by
covering the 2 selected
fixing holes.
IMPORTANT: opening
will now be possible
only by means of a flat
blade screwdriver.
4.3 Fixing the detector in place
Standard fixing method
1. Install the base in the desired location, then mark the
position of the 2 fixing holes (marked or ) using a
pencil.
2. Drill holes using a 5 mm Ø drill bit.
3. Fix the base using appropriate plugs and screws.
Fixing with flush-mounting box
1. For 60 mm diameter boxes: use holes marked .
2. For 85 mm diameter boxes: use holes marked .
3. Fix the base using suitable screws.
60 85
60
85
Optional locking of the detector on the mounting base
Optional locking is designed to prevent unauthorized
dismounting of the detector.
Using cutting pliers, cut the locking nipple.
Locking nipple
v
Align the 2 locating arrows
marked on the mounting
base and the detector, then
lock the unit by turning
clockwise.
IMPORTANT: the detector
cannot be fixed to the base
if the battery is not properly
connected.
Do not use force.
Diameter 60 fixing holes
Diameter 85 fixing holes
Fixing
spacers
Test button
alignment
marker

100
GB
4.4 Installing several detectors in a network
It is possible to interconnect up to 40 detectors to enable alarm activation over the whole
range of smoke and fire detectors installed in the home.
Signal Earth N
Cable
terminals
Not used
IMPORTANT: 155-21X heat detectors can only be connected with the same type of
detectors: e.g. a 155-21X can be connected with 155-21X heat detectors or 151-21X smoke
detectors.
For 15 mm2wires, the overall network length must not exceed 400 m.
3. Clip the connector block back in place.
4. Lock the detector onto the base (see Fixing the detector in place).
You can therefore be sure of being warned if smoke is detected in a room far away from the
room in which you are in.
1. Once the detector’s base has been fixed in place (see Fixing the detector in place),
unclip the connector block.
2. Then wire as follows:
Connector block

101
GB
Although alarm sounding is reduced during a
manual test of a heat detector, it is advisable
to inform neighbours beforehand and to use
all suitable hearing protection devices.
Testing the detector using the test button:
When you press on the “TEST” key for
10 sec., the detector performs an automatic
functional self-test. Among other things, it
examines the state of the heat sensor located
behind the detection head slots and thus
detects any defects linked to temperature
measurement. If the heat sensor is faulty, the
heat detector indicates that there is a
technical fault (see Indications section). There
is therefore no need to test the detector using
a source of heat.
5. esting the detector
IMPORTANT: you can recognise this heat
detector by the white slots in the detection
head. Unlike the smoke detector, the
smoke test spray (ref. TESTFUM) is not
suitable for testing heat detector operation.
IMPORTANT: so as not to cause a fire and
damage the mechanical parts and the
design of the device, never test it:
• using a naked flame,
• by moving it too close to a source of
burning heat (e.g. a paint stripper, hair
dryer, etc.).
Detection
head slot

102
GB
To test the heat detector, press on the test button (for roughly 10 sec.) until the built-in
sounding is triggered. As long as the button is held down, the detector responds as follows:
As soon as the test button is pressed for more than 10 sec, and when connected to a
Daitem alarm system, the detector causes the following:
• triggering of the control panel and security system sirens in fire sounding mode for 5 minutes,
• triggering of the telephone dialler.
Stop the sirens and check that the control panel has memorised the alarm (see Indications
section).
IMPORTANT: these tests should be carried out at least
once a month and notably when you have been away for a
long time.
Heat detector
transmitting
the heat
detection signal
Other hard-wired
Interconnected
heat detectors
the LED flashes
quickly
the LED flashes
quickly
the alarm sounds
for 1 sec (75 dB(A)
at 3 m) and then
stops for 1 sec
a safety
halo lights up
every second
a safety
halo lights up
every second
Red LED indicating
detector status White LED Sounding
the alarm sounds
for 1 sec (75 dB(A)
at 3 m) and then
stops for 2 sec

103
GB
It is possible to disable the detector for a 15 min period:
• prior to activities likely to generate abnormal heat (fast rise in
temperature or increase in room temperature above 54°C,
e.g. during DIY work) and hence cause untimely triggering
of the alarm,
• to stop alarm sounding if non-dangerous heat is detected
(e.g. sudden sunshine), (only possible with the detector
having triggered the heat signal and which can be
recognised by its flashing red LED).
In order to disable the detector, press the test button until the
1st beep sounds or until the detector stops its built-in
sounding.
The LED indicating the status of the detector flashes every
2 sec.
Following the 15 min disable period, the detector is
automatically reset to normal operation with the detector
status LED flashing every 10 sec.
Disabled heat
detector
Other hard-wired
Interconnected heat
detectors
the LED flashes
every 2 sec.
the LED flashes
every 10 sec.
-
-
-
-
Red LED indicating
detector status White LED Sounding
6. Manually disabling the detector
IMPORTANT: during the
15 min disable period, the
detector will not detect any
smoke or sound the alarm.
IMPORTANT: to exit the disable mode before the end of the 15 min period, press the Test
button until you hear the built-in sounding (see response description in the Testing the
detector section).

104
GB
... alerts
When your alarm system is disarmed, the control panel will report the problem with the voice
message “beep, date, time, fire alarm, detector n° X”.
... faults
Battery fault on the detector
If the sound indication of the battery fault occurs at an inappropriate time, it is possible to
postpone its occurrence for an 8-hour delay over a maximum 7-day period by pressing the
test button until you hear the 1st beep. This is the time period available for replacing the
Lithium battery.
Battery fault on the control panel
Following a system command, the control panel issues the following voice message: “beep,
fault, battery, detector n° X”.
7. Indications...
IMPORTANT: in order not to wake you up, audible alarms resulting from power problems
or technical problems are shut down during the night. Any faults are indicated either
after daybreak for a period of more than 10 minutes or 12 hours after their occurrence.
IMPORTANT: when a
battery fault occurs, the
detector continues to
function perfectly for
30 days. Nevertheless,
it is advisable to replace
the battery as soon as
possible.
Heat detector transmitting
the fault signal
Other hard-wired
interconnected heat
detectors
the LED flashes
every 5 sec.
-
2 fast beeps
every 60 sec.
-
-
-
Red LED indicating
detector status White LED Sounding

105
GB
Technical fault
If this fault appears, replace the heat detector.
Radio fault on the control panel
Following a system command, the control panel issues the following voice message: “beep,
fault, radio, detector n° X”.
8.1 Servicing the detector head
You should vacuum-clean the detection head slots if there is a lot of dust in the room.
8. Maintenance
Heat detector transmitting
the fault signal
Other hard-wired
Interconnected heat
detectors
the LED flashes
8 times every 8 sec.
-
8 fast beeps
every 58 sec.
-
-
-
Red LED indicating
detector status White LED Sounding
Detection head slot IMPORTANT: we advise
you to clean the detector
using a soft cloth.
Never use alcohol or
acetone to clean it.

106
GB
v
v
8.3 During DIY work
The detector must not be
painted. If work is to be
carried out in the room where
the detector is installed,
completely cover the
detector using the plastic
cover.
IMPORTANT: do not forget
to remove the plastic cover
when the work is finished.
• The lithium battery pack must be replaced by the same type of pack with the same
technical characteristics, i.e. (3.6 V - 4 Ah).
• We advise you to use the DAITEM BatLi26 pack available in the catalogue
in order to guarantee individual safety and equipment reliability.
• Dispose of the waste lithium power pack in an appropriate recycling bin.
8.2 Changing the battery
If the optional opening
of the detector is not
locked (see Fixing…)
1. Remove the detector from
its base by turning it
counter clockwise until
you hear a click.
If the optional opening
of the detector is locked
(see Fixing…)
1. Insert a flat blade
screwdriver into this notch.
2. Replace the worn battery.
3. Lock the detector back
onto its base (see
Fixing...).
4. Carry out a test (see
Testing the detector).
2. Remove the detector from
its base by turning it
counter clockwise until
you hear a click.
3. Replace the worn battery.
4. Lock the detector back
onto its base (see
Fixing...).
5. Carry out a test (see
Testing the detector).
Li

107
GB
Technical data Wireless heat detector
Type of detection heat detector able to detect:
• temperature rise speed
• reaching of temperatures between 54 and 70°C (see next page)
Average coverage 30 m2
eight of support 4.5 m max
Use indoor
Power supply 3.6 V lithium battery (BatLi 26)
Battery life approximately 5 years in normal conditions of use
Red indication LED • detector status
• alerts triggered
• faults
White LED safety lighting in case of detection
Built-in sounding • > 85 dB at 3 m in case of detection
• > 75 dB at 3 m during testing or fault indication
ard-wired interconnection 40 detectors maximum
Network length 400 m maximum
Cable diameter 1.5 mm2maximum
Radio link TwinBand®800/400 M z
Operating temperature - 10°C to + 55°C (+75°C for a short duration)
Storage temperature - 10°C to + 55°C / 95% relative humidity max. (without condensation)
Degree of mechanical protection IP 32
Dimensions (Ø x ) 125 x 48 mm
Weight 210 g
155-21X
9. echnical data

108
GB
The heat detector will trigger an alarm:
• if the temperature falls within the range given in the table below:
(A2 class detector, response time according to EN 54-5, chapter 4.2)
Minimum static response temperature 54 °C
Maximum static response temperature 70 °C
Air temperature Response time Response time
rise speed lower limits upper limits
° C per minute Minute (minimum) Minute (maximum)
1 29:00 46:00
3 7:13 16:00
5 4:09 10:00
10 2:00 5:30
20 1:00 3:13
30 0:40 2:25
or
• depending on the temperature rise speed
(A2 class detector, response time according to EN 54-5, chapter 5.4.3)
Examples:
• if the temperature increases by 1 °C per minute then the heat detector should not trigger
an alarm before 29 minutes have passed and should then trigger an alarm between
29 minutes and 46 minutes.
• if the temperature increases by 30 °C per minute then the heat detector should not trigger
an alarm before 40 seconds have passed and should then trigger an alarm between
40 seconds and 2 minutes and 25 seconds.

GB
"
Summary of your detector’s responses
and indications
Normal operation
Detector test (2)
(1) The alarm will sound as long as abnormal heat is detected.
(2) Responses when the test button is pressed for longer than 10 sec and
until the key is released.
Be prepared for a fire
• Plan an evacuation route.
• Prepare an evacuation plan
for every room.
• The least smoke is near the
ground: crawl out of the
house.
• When the alarm sounds,
wake everyone up.
• Prearrange a muster point
outside the house.
• Avoid going into the house
unnecessarily if there is a
fire.
• Call the fire brigade.
During DIY work
The detector must not be
painted. If work is to be
carried out in the room where
the detector is installed,
completely cover the
detector using the plastic
cover provided.
10. User sheet (pull-out sheet for the user)
Do not forget to remove
the plastic cover when
the work is finished.
Heat detection (1)
All heat detectors the LED flashes
once every 10 sec.
-
-
Red LED indicating
detector status White LED Sounding
Heat detector
transmitting
the heat
detection signal
Other hard-wired
Interconnected
heat detectors
the LED flashes
quickly
the LED flashes
quickly
the alarm sounds
for 1 sec (75 dB(A)
at 3 m) and then
stops for 1 sec
a safety
halo lights up
every second
a safety
halo lights up
every second
Red LED indicating
detector status White LED Sounding
the alarm sounds
for 1 sec (75 dB(A)
at 3 m) and then
stops for 2 sec
Heat detector
transmitting the heat
detection signal
Other hard-wired
interconnected heat
detectors
the LED flashes
quickly
-
a built-in modulated alarm
sounds on a continuous
basis (85 dB(A) at 3m)
a safety
halo lights
up
a safety
halo lights
up
Red LED indicating
detector status White LED Sounding
a built-in modulated alarm
sounds on a discontinuous
basis (85 dB(A) at 3m)

GB
Manual disabling of the detector
It is possible to disable the detector for a 15 min period:
• prior to activities likely to generate abnormal heat (sudden rise in temperature or rise in room
temperature of above 54°C, e.g. during DIY work), and cause unwanted alarm activation,
• to stop the alarm when the heat generated is not dangerous (e.g. sudden sunshine), (only
possible with the detector having detected the rise in temperature and which can be
recognised owing to the flashing of its red LED).
In order to disable the detector, press the test button until the 1st beep sounds or until the
detector stops its built-in audible alarm. The LED indicating
the status of the detector flashes every 2 sec.
Battery fault indication
Technical fault indication
To prevent users from being
disturbed at inconvenient times,
audible indications of a battery
fault or technical fault can be
delayed for 8 hours over a
maximum period of 7 days by
holding the test button pressed
until the first beep sounds. You
should contact your installation
engineer within this same period
in order to rectify the problem.
Following the 15 min disable
period, the detector is
automatically reset to normal
operation and its indication
LED flashes every 10 sec.
In order not to wake you up,
audible indications of a battery
fault or a technical fault are shut
down during the night. Any faults
are reported either after
daybreak for a period of over
10 min or 12 hours after their
occurrence.
During this 15 min. period,
the detector will be unable to
recognise heat or generate
alarms.
Disabled heat
detector
Other hard-wired
Interconnected heat
detectors
the LED flashes
every 2 sec.
the LED flashes
every 10 sec.
-
-
-
-
Red LED indicating
detector status White LED Sounding
Heat detector transmitting
the fault signal
Other hard-wired
interconnected heat
detectors
the LED flashes
every 5 sec.
-
2 fast beeps
every 60 sec.
-
-
-
Red LED indicating
detector status White LED Sounding
Heat detector transmitting
the fault signal
Other hard-wired
Interconnected heat
detectors
the LED flashes
8 times every 8 sec.
-
8 fast beeps
every 58 sec.
-
-
-
Red LED indicating
detector status White LED Sounding

111
GB
Non-binding document that may be modified without notification.
DECLARATION OF CONFORMITY
Manufacturer: Hager Security SAS
Address: F-38926 Crolles Cedex - France
Product type: Wireless heat detector
Trade mark: Daitem
We declare under our sole responsibility that the product to which this declaration
relates is compliant with the essential requirements of the following directives:
• R&TTE Directive: 99/5/EEC
• Low voltage directive: 2006/95/EC
in compliance with the following harmonised European standards:
This product can be used in all EU, EEA Countries and Switzerland.
Crolles, 02.01.2013 Signature :
Patrick Bernard
Director of Research and Development
Products code 155-21X
EN 300 220-2 V2.1.2 X
EN 50130-4 (95) + A1 (98) + A2 (2002) X
EN 60950 (2006) X
EN 301 489-1 V1.8.1 X
To obtain advice when installing your system or before returning equipment, please contact the Daitem
technical support team (see telephone number at the back of the alarm system installation manual).
A team of qualified technicians will tell you what to do.
ATRAL SYSTEM - F-38926 CROLLES CEDEX
www.daitem.co.uk
13

2280612004 - 01.2013
Table of contents
Other DAITEM Security Sensor manuals

DAITEM
DAITEM SH271AX User manual

DAITEM
DAITEM SH273AX User manual

DAITEM
DAITEM 145-21X User manual

DAITEM
DAITEM DP1101 User manual

DAITEM
DAITEM SH195AX User manual

DAITEM
DAITEM SH273AX User manual

DAITEM
DAITEM SH271AX User manual

DAITEM
DAITEM SH148AX User manual

DAITEM
DAITEM DP1201 User manual

DAITEM
DAITEM 191-21X User manual