1.
1.6 Safe Operation
When operating the unit, use the operating guide and programming guide for guidance and safety instructions.
The drive is not suitable as the only safety device in the system. Make sure that additional monitoring and protection devices on
drives, motors, and accessories are installed according to the regional safety guidelines and accident prevention regulations.
Keep all doors, covers, and terminal boxes closed and securely fastened during operation.
1.7 Verifying the Shipment and the Contents
Make sure that the items supplied and the information on the product label correspond to the order confirmation. The product
label is located on the exterior of the drive.
NOTICE
The type code is used in the fuse table. Write down the type code (T/C) and serial number (S/N) for future reference.
CHASSIS/ IP20 Tamb. 50°C/122°F IE2 1.8%
P/N: 134F9368 S/N: 302224G431
IN: 3x380-480V 50/60Hz 42/36A
OUT: 3x0-Vin 0-590Hz 44/40A
See manual for special condition/mains fuse
voir manual de conditions speclales/fusibles
Stored charge, wait 4 min.
Charge residuelle, attendez 4 min.
T/C: CDS303P18KT4E20H2XXXXXXSXXXXAXBXCXXXXDX
Listed 76X1 E134261 IND. CONT. EQ.
Danfoss A/S
6430 Nordborg
Denmark
134F9368302224G431 ecosmart.danfoss.com
Illustration 1: Example of the Type Code on the Product Label
Part number and serial number
Input voltage, frequency, and current
Ouput voltage, frequency, and current
Enclosure protection rating
1.8 EMC-compliant Installation
For more information, refer to the product-specific operating guide.
Use shielded cables for motor (unshielded cables in metal conduit are acceptable), brake, DC, and control wiring.
Ensure that motor, brake, and DC cables are as short as possible to reduce the interference level from the entire system. Provide
a minimum space of 200 mm (7.9 in) between mains input, motor cables, and control cables.
Convey the currents back to the drive using a metal mounting plate. Ensure good electrical contact from the mounting plate
through the mounting screws to the metal frame of the enclosure.
If the shield connection points have a voltage potential difference, connect a low impedance equalizing wire parallel to the
shielded cable.
When using relays, control cables, a signal interface, fieldbus, or brake, connect the shield to the enclosure at both ends. If the
ground path has high impedance, is noisy, or is carrying current, break the shield connection on 1 end to avoid ground current
loops.
1.9 Installing the Drive
Installation location is very important. Full output current is available when the following installation conditions are met:
Maximum surrounding air temperature is 45 °C (113 °F) average over 24 hours and 50 °C (122 °F) for 1 hour.
Minimum surrounding air temperature is 0 °C (32 °F).
Altitude is less than 1000 m (3280 ft) above sea level.
For temperatures and altitudes outside this range, consult the operating guide.
Procedure
Identify the drive. See 1.1.7 Verifying the Shipment and the Contents.
AN39643481725001-000101 / 130R1233 8 | Danfoss A/S © 2022.09
Instructions
VLT® Compressor Drives
Installation Guide