Delta DAC-1600 User manual

I
NSTALLATION
G
UIDE
UL 864 DAC-1600 Installation Guide
Document Edition 1.4
Updated November 17, 2015
Document Edition 1.4
Product Description
The Delta 16 Input Controller is a Native BACnet Application
Controller that is fully programmable (via GCL+) and
communicates on an RS-485 LAN using the MS/TP BACnet
protocol. The controller includes an easy to mount enclosure
and is designed for a wide range of monitoring applications
requiring no more than 16 inputs. A secondary LINKnet
network is also supported for up to 4 Delta BACstats or other
Delta LINKnet devices.
The 16 universal inputs are jumper configurable.
Important Information
ORCAview OWS and controller firmware must all be of the same version number to be
compatible. When upgrading any of these products from older versions (i.e. 3.22 or 3.30), you
must upgrade all the remaining products. Exception: UL 864 model, DAC-1600-UL864 can be
used with V3.33 and V3.40 firmware.
Package Contents
Product: DAC-1600 (Rev. 1.1)
DAC-1600 (Rev.1.1) Installation Guide
Related Documents
Delta Controls Wiring Guidelines
ORCAview Operator Guide
ORCAview Technical Reference Manual
Release Notes for related Firmware

Delta Controls
Page 2 of 12
UL864 Specific Considerations
Wiring to and from the device shall be through power-limited circuits.
Use only Core Components transformer, Model No. 120-024-100-2TF-CB, by Lectro
Components Inc. to power the device. (Delta Part # 440008)
Use only UL Listed Class 2 Power Supplies for auxiliary field devices.
Use only UL Recognized Ethernet Switch, 571-580, by Siemens for Smoke Control Systems
that utilize Ethernet communications.
Impedance value for which ground faults are detected is zero ohms.
Cautions or Warnings
This controller is an Electro-statically sensitive device. Proper ESD protection (ground strap)
should be used when installing this product so that damage to the product does not occur.
Equipment damage or loss of data may occur if these procedures are not followed as specified.
Installations requiring CE conformance: All wiring for CE rated products must use an extra low
voltage (SELV) or protective extra low voltage (PELV) transformer. Use safety-isolating
transformers, (Class II transformer) per EN61558. The transformer must be rated for 100% duty
cycle.

Document Edition 1.4
Page 3 of 12
Mounting
The DAC-1600 includes a plastic enclosure that can be quickly mounted with two screws (not provided). This
controller should be mounted in an appropriate location within packaged equipment or another enclosure that
meets code requirements.

Delta Controls
Page 4 of 12
Board Layout

Document Edition 1.4
Page 5 of 12
Controller Configuration
Derived Network Addressing
The DNA jumper comes ON by default. This allows the controller to
automatically configure a BACnet controller address. This should NOT be
removed unless you are assigning a BACnet controller number through
software. The BACnet controller number should not be confused with the DIP
switch setting, and each controller must still have a unique dip switch address
even when using software to define the controller number.
DNA
Controller Addressing
The Dip Switch is a binary switch. Each individual DIP switch represents a
unique value, which forms the controller address when added together.
To set the address, simply move the switches that add up to the controllers
desired address to the ON position.
Example: If the controller is to be address 5 on the network, set the switch
numbered 4 and the switch numbered 1 (equals 5) to the On position.
Note: Each controller on the same MS/TP segment must have a unique DIP
switch address.

Delta Controls
Page 6 of 12
Wiring General
All wiring must conform to NEC and local codes and regulations. Use earth ground isolating step-down Class 2
transformers. Do not use autotransformers. Determine supply transformer rating by summing total VA of product
and output loads.
Risk of Electric Shock or Fire
More than one disconnect switch may be required to de-energize the
equipment before servicing.
Input Class 2 Power Supplies are interconnected. Use only Class 2
sources suitable for interconnections.
All terminals are acceptable for Class 2 Circuit connections only
Use copper conductors only
Apply minimum 6.0 lb-in torque for tightening field wires into the terminal
blocks
Power
This product is designed to use a 24 VAC, Class 2 power supply. The proper specified cabling must be used.
(18 – 16 AWG, 2-conductor wire)
A single transformer may be used to power multiple controllers and/or auxiliary field devices (actuators, etc.)
provided the following conditions are met:
All devices MUST be ½ wave rectified. Mixing power between ½ wave and full wave rectified devices
will damage both the transformer and connected equipment.
The transformer is properly sized, including line losses for the total VA requirements.
Polarity is observed between controllers (with respect to 24~ and Gnd).
Each controller is grounded as shown in the diagram below. This is important to protect equipment and
ensure a common ground reference for RS-485 communications.
The transformer secondary is fused for its maximum rated load (4A max for Class 2 circuits).

Document Edition 1.4
Page 7 of 12
Network Communication
The controller communicates on an RS-485 LAN using the BACnet MS/TP protocol. Refer to Delta Controls
Wiring Guidelines for further details.
MS/TP (RS-485) Wiring
For detailed information on MS/TP and LINKnet wiring refer to Delta Controls Wiring Guidelines.
The proper specified cabling must be used to ensure reliable communications. (22 AWG twisted
pair, 100-120 ohms impedance, 17 pF/ft or lower capacitance, with a braided or aluminum foil
shield.)
Controllers should always be wired together in a daisy-chain fashion. Attempting to connect them
using a starred or bus configuration will cause problems on the network.
Networks with a total length greater than 4000 ft or with more than 50 controllers require a
repeater (RPT-768).
LINKnet networks that have only 1-2 controllers, and have less then 100 ft of cable length do not
require network terminators.

Delta Controls
Page 8 of 12
Input Wiring
Inputs on the DAC-1600 controller follow the same general wiring requirements as other Delta Controls
products. Recommended cable types should be used as listed below. Refer to the Delta Controls Wiring
Guidelines for more details.
Recommended Cable Type
Where to Use
2 Conductor, 18 AWG, Unshielded
4-20mA, 10KΩ, and 10V input types
2 Conductor, 22 AWG, Shielded
Inputs configured for 5V
Input Configuration
The input must be configured to accept the signal used by
the input device. Place the jumper for each input in the
correct location on the Input Type Selector Block. The
diagram to the right shows the factory default selection of
10 KΩ.
4-20mA For sensors that use a 4 to 20 mA signal.
10K For 10 KΩThermistor temperature
sensors, as well as Dry Contact binary
inputs.
5V For sensors that use a 0 - 5 VDC signal.
10V For sensors that use a 0 -10 VDC signal.

Document Edition 1.4
Page 9 of 12
Indicators
LED Function Description
Power Controller Power
Indicator This yellow LED turns on to indicate that the controller has power
applied.
Scan CPU Scan Indicator This red LED flashes at a rate relative to the CPU scan rate.
Network
(NET1) MS/TP (RS485)
Communication
Status Indicators
The green LED flashes to indicate when the controller is
transmitting out the port, and the red LED flashes to indicate when
the controller is receiving data through the port. If communication
is good, both LEDs will flash at a high rate.
Network
(NET2) MS/TP (RS485)
Communication
Status Indicators
The green LED flashes to indicate when the controller is
transmitting out the port, and the red LED flashes to indicate when
the controller is receiving data through the port. If communication
is good, both LEDs will flash at a high rate.
Inputs
(IP1 – IP16) Input Status
Indicators A corresponding red LED varies in intensity and is brightly lit when
the associated input is receiving a low voltage input signal (i.e. a
closed contact, 0 VDC, 0mA or a high temperature reading or low
resistance).

Delta Controls
Page 10 of 12
Product Specifications
Power Requirements 24 VAC, 60Hz, Class 2
Power Consumption 8 VA
Ambient Ratings 32° to 131°F (0° to 55°C), 10 to 90% RH (non condensing)
Communication Ports
NET1 BACnet MS/TP (RS-485)
Communication: 9600, 19200, 38400, 76800 bps (Default)
Maximum of 99 controllers
NET2 LINKnet
Communication: 76800 bps
Maximum of 4 LINKnet controllers including up to two DFM
controllers
Service
Port RJ-11 Jack
Used with Delta Controls service tool devices (for example,
CON-768)
Inputs 16 Universal Inputs (10 bit), jumper configurable for the following input
types:
0-5 VDC
0-10 VDC
10 KΩThermistor
Dry Contact (using 10 KΩThermistor jumper setting)
4-20 mA
Technology 32 bit processor
1 MB (8 megabit) Flash Memory
127 KB SRAM memory
Listings UL 916 Listed
BTL Listed
UL 864 Listed (DAC-1600-UL864 model only)
Compliance CE
FCC

Document Edition 1.4
Page 11 of 12
CE - DECLARATION OF CONFORMITY
According to ISO/IEC Guide 22 and EN 45014
Manufacturer's Name:
Delta Controls
Manufacturer's Address:
17850 56th Avenue
Surrey, British Columbia
Canada
V3S 1C7
Declares that the product (s):
Product Name:
Delta Application Controller
Model Numbers:
DAC-1600
Product Options:
All
Conforms to the following Product Specifications:
EN 50081-1:1992
Generic Emission Standard
EN 55022
Radiated and Conducted Emissions
Class B
EN 61000-3-2
Power Line Harmonics
Class A
EN 61000-3-3
Power Line Fluctuations
P
st
< 1, P
lt
< 0.65
EN 50082-1:1997
Generic Immunity Standard
EN 61000-4-2
ESD Immunity
Level A
EN 61000-4-3
RF EMF Immunity
Level A
ENV 50204
RF EMF Immunity (Keyed Carrier)
Level A
EN 61000-4-4
EFT/Burst Immunity
Level A
EN 61000-4-5
Surge Immunity
Level A
EN 61000-4-6
Conducted Immunity
Level A
EN 61000-4-11
Voltage Dips / Interruptions
Level A/A/C
Supplementary Information
The product(s) herewith comply with the requirements of the EMC Directive 89/336/EEC. The
product(s) were tested in a typical configuration.
Lee Dickson
Quality Assurance Manager

Delta Controls
Page 12 of 12
FCC Compliance Information
This equipment has been tested and found to comply with the limits for a Class digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense.
Industry Canada Compliance Statement
ICES-003 This Class digital apparatus meets all requirements of the Canadian Interference-Causing
Equipment Regulations
Cet appareil numérique de la Classe B Respecte toutes les exigences du Règlement sur le matérial
brouiller du Canada.
This product conforms to the following UL requirements:
UL916: Energy Management Equipment
UL864*: Control Units and Accessories for Fire Alarm Systems, 9th Edition
* - Applicable to DAC-1600-UL864 model only
Table of contents
Other Delta Controllers manuals

Delta
Delta RMC70 User guide

Delta
Delta 2SPA User manual

Delta
Delta DVP-10PM User manual

Delta
Delta AH500 series Owner's manual

Delta
Delta NC10EB User manual

Delta
Delta PBC Series User manual

Delta
Delta DT3 Series User manual

Delta
Delta VFD-007B User manual

Delta
Delta 2SP2 User manual

Delta
Delta DVP-PM Series Instructions for use

Delta
Delta C2000 Series User manual

Delta
Delta C2000 Series User manual

Delta
Delta eZV-440 User guide

Delta
Delta DVP30EX2 User manual

Delta
Delta MP1 Series User manual

Delta
Delta DVP-SA2 User manual

Delta
Delta VFD-E User manual

Delta
Delta HMC07-N4 User manual

Delta
Delta RTU-ECAT User manual

Delta
Delta DVP-SA2 User manual