and doors close.
4. Activate system into alarm so
electromagnet
s release
the units to return to standby.
Resetting the test switch will allow
will release and the doors will close.
delay, the hold open
electromagnet
of both units
procedure for that unit. After a short time
main closer detector as explained in the test
detectored unit, trip the test switch of the
5. If the closer is used in conjunction with a
3. Advise fire officials prior to testing.
2. Open door so slide block engages with hold
connections. Apply power to units.
1. After installation is completed, recheck all
Final installation and test.
11
open assembly.
14
shut the door.
open and allows the door closer to
contact will open and interrupt current
supply based on unit voltage.
applying, 24VDC/24VAC power
across a normally closed alarm contact
NORMAL- The closer unit's electromagnet will be energized
24VAC 166mA
Maximum input current- 24VDC 166mA
24VAC +10% -15%
Voltage input- 24VDC +10% -15%
ELECTRICAL SPECIFICATION
to the electromagnet which releases the hold
FIRE ALARM- When the alarm sounds, the alarm
OPERATION
AND MAINTENANCE TO RETAIN THE SYSTEM IN
USER IS ALSO RESPONSIBLE FOR THE ADJUSTMENTS
THE TESTING OF THE FIRE ALARM SYSTEM. THE END
THE INITIAL INSTALLATION TEST, IN CONJUNCTION WITH
SYSTEM MUST ALSO BE TESTED PERIODICALLY AFTER
WHEN THE ALARM SYSTEM IS ACTIVATED. THE ENTIRE
THAT THE DOOR CLOSER UNITS FUNCTION PROPERLY
INSTALLATION, BY THE END USER, TO ASSURE
IMPORTANT: THE UNIT MUST BE TESTED AFTER THE
WORKING ORDER.
13
12
WIRE CONNECTION COVER
Improper voltage to unit, will result in damage to unit and void warranty.
CAUTION:
All wiring must comply with national,
NOTE:
state and local electrical codes.
TERMINAL BLOCK 18awg MAX.
THIS CONNECTION IS NOT POLARITY DEPENDENT.
GROUND
BYPASS SWITCH
WIRE CONNECTION COVER
BLOCK
NOTE:
TERMINAL
SCREW
ALARM CONTROL UNIT OR
SMOKE DETECTOR
INCOMING POWER
CONNECTION
U.L. LISTED
BYPASS SWITCH
OPTIONAL:
An auxiliary door stop (by others) must be installed to limit the
maximum degree of door swing. Failure to do so may result in
damage to the unit.
Slide wiring connection cover to allow access. Attach bracket and assemble bypass switch.
Determine power supply and unit voltage type: 24VAC/24VDC. CAUTION (DO NOT CONNECT 120VAC TO A 24 VOLT
UNIT TYPE.) Connect power supply wires, one (1) to terminal block one (1) to bypass switch. connect other bypass switch wire to
terminal block (Terminal Block can be removed for easier access).
Return wiring connection cover to cover wire connections.
INS NO.
PAGE
Rev.
08281020
5 of 5
08/13