DSC Power632 User manual

Installation
Manual
WARNING
This manual contains information on limitations regarding product use and function and information on the
limitations as to liability of the manufacturer. The entire manual should be carefully read.
This panel will not operate if installed outside of North America. See section 1.1 for details.
PC1555MX
Software Version 2.3
DLS-3 v1.3 and higher
See Back Cover for New Features

WARNING Please Read Carefully
Note to Installers
This warning contains vital information. As the only individual in contact with system users, it is your respon-
sibility to bring each item in this warning to the attention of the users of this system.
System Failures
This system has been carefully designed to be as effective as possible. There are circumstances, however,
involving fire, burglary, or other types of emergencies where it may not provide protection. Any alarm system
of any type may be compromised deliberately or may fail to operate as expected for a variety of reasons. Some
but not all of these reasons may be:
■ Inadequate Installation
A security system must be installed properly in order to provide adequate protection. Every installation should
be evaluated by a security professional to ensure that all access points and areas are covered. Locks and latches
on windows and doors must be secure and operate as intended. Windows, doors, walls, ceilings and other
building materials must be of sufficient strength and construction to provide the level of protection expected. A
reevaluation must be done during and after any construction activity. An evaluation by the fire and/or police
department is highly recommended if this service is available.
■Criminal Knowledge
This system contains security features which were known to be effective at the time of manufacture. It is pos-
sible for persons with criminal intent to develop techniques which reduce the effectiveness of these features. It
is important that a security system be reviewed periodically to ensure that its features remain effective and that
it be updated or replaced if it is found that it does not provide the protection expected.
■Access by Intruders
Intruders may enter through an unprotected access point, circumvent a sensing device, evade detection by
moving through an area of insufficient coverage, disconnect a warning device, or interfere with or prevent the
proper operation of the system.
■Power Failure
Control units, intrusion detectors, smoke detectors and many other security devices require an adequate power
supply for proper operation. If a device operates from batteries, it is possible for the batteries to fail. Even if the
batteries have not failed, they must be charged, in good condition and installed correctly. If a device operates
only by AC power, any interruption, however brief, will render that device inoperative while it does not have
power. Power interruptions of any length are often accompanied by voltage fluctuations which may damage
electronic equipment such as a security system. After a power interruption has occurred, immediately conduct
a complete system test to ensure that the system operates as intended.
■Failure of Replaceable Batteries
This system’s wireless transmitters have been designed to provide several years of battery life under normal
conditions. The expected battery life is a function of the device environment, usage and type. Ambient condi-
tions such as high humidity, high or low temperatures, or large temperature fluctuations may reduce the
expected battery life. While each transmitting device has a low battery monitor which identifies when the bat-
teries need to be replaced, this monitor may fail to operate as expected. Regular testing and maintenance will
keep the system in good operating condition.
■Compromise of Radio Frequency (Wireless) Devices
Signals may not reach the receiver under all circumstances which could include metal objects placed on or near
the radio path or deliberate jamming or other inadvertent radio signal interference.
■System Users
A user may not be able to operate a panic or emergency switch possibly due to permanent or temporary physi-
cal disability, inability to reach the device in time, or unfamiliarity with the correct operation. It is important
that all system users be trained in the correct operation of the alarm system and that they know how to respond
when the system indicates an alarm.
■Smoke Detectors
Smoke detectors that are a part of this system may not properly alert occupants of a fire for a number of rea-
sons, some of which follow. The smoke detectors may have been improperly installed or positioned. Smoke
may not be able to reach the smoke detectors, such as when the fire is in a chimney, walls or roofs, or on the
other side of closed doors. Smoke detectors may not detect smoke from fires on another level of the residence
or building.
Every fire is different in the amount of smoke produced and the rate of burning. Smoke detectors cannot sense
all types of fires equally well. Smoke detectors may not provide timely warning of fires caused by carelessness
or safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage of flammable
materials, overloaded electrical circuits, children playing with matches or arson.
Even if the smoke detector operates as intended, there may be circumstances when there is insufficient warning
to allow all occupants to escape in time to avoid injury or death.
■Motion Detectors
Motion detectors can only detect motion within the designated areas as shown in their respective installation
instructions. They cannot discriminate between intruders and intended occupants. Motion detectors do not pro-
vide volumetric area protection. They have multiple beams of detection and motion can only be detected in
unobstructed areas covered by these beams. They cannot detect motion which occurs behind walls, ceilings,
floor, closed doors, glass partitions, glass doors or windows. Any type of tampering whether intentional or
unintentional such as masking, painting, or spraying of any material on the lenses, mirrors, windows or any
other part of the detection system will impair its proper operation.
Passive infrared motion detectors operate by sensing changes in temperature. However their effectiveness can
be reduced when the ambient temperature rises near or above body temperature or if there are intentional or
unintentional sources of heat in or near the detection area. Some of these heat sources could be heaters, radia-
tors, stoves, barbeques, fireplaces, sunlight, steam vents, lighting and so on.
■Warning Devices
Warning devices such as sirens, bells, horns, or strobes may not warn people or waken someone sleeping if
there is an intervening wall or door. If warning devices are located on a different level of the residence or
premise, then it is less likely that the occupants will be alerted or awakened. Audible warning devices may be
interfered with by other noise sources such as stereos, radios, televisions, air conditioners or other appliances,
or passing traffic. Audible warning devices, however loud, may not be heard by a hearing-impaired person.
■Telephone Lines
If telephone lines are used to transmit alarms, they may be out of service or busy for certain periods of time.
Also an intruder may cut the telephone line or defeat its operation by more sophisticated means which may be
difficult to detect.
■Insufficient Time
There may be circumstances when the system will operate as intended, yet the occupants will not be protected
from the emergency due to their inability to respond to the warnings in a timely manner. If the system is moni-
tored, the response may not occur in time to protect the occupants or their belongings.
■Component Failure
Although every effort has been made to make this system as reliable as possible, the system may fail to func-
tion as intended due to the failure of a component.
■Inadequate Testing
Most problems that would prevent an alarm system from operating as intended can be found by regular testing
and maintenance. The complete system should be tested weekly and immediately after a break-in, an attempted
break-in, a fire, a storm, an earthquake, an accident, or any kind of construction activity inside or outside the
premises. The testing should include all sensing devices, keypads, consoles, alarm indicating devices and any
other operational devices that are part of the system.
■Security and Insurance
Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm sys-
tem also is not a substitute for property owners, renters, or other occupants to act prudently to prevent or mini-
mize the harmful effects of an emergency situation.
Limited Warranty
Digital Security Controls Ltd. warrants the original purchaser that for a period of twelve months from the date
of purchase, the product shall be free of defects in materials and workmanship under normal use. During the
warranty period, Digital Security Controls Ltd. shall, at its option, repair or replace any defective product upon
return of the product to its factory, at no charge for labour and materials. Any replacement and/or repaired parts
are warranted for the remainder of the original warranty or ninety (90) days, whichever is longer. The original
purchaser must promptly notify Digital Security Controls Ltd. in writing that there is defect in material or
workmanship, such written notice to be received in all events prior to expiration of the warranty period. There
is absolutely no warranty on software and all software products are sold as a user license under the terms of the
software license agreement included with the product. The Customer assumes all responsibility for the proper
selection, installation, operation and maintenance of any products purchased from DSC. Custom products are
only warranted to the extent that they do not function upon delivery. In such cases, DSC can replace or credit
at its option.
International Warranty
The warranty for international customers is the same as for any customer within Canada and the United States,
with the exception that Digital Security Controls Ltd. shall not be responsible for any customs fees, taxes, or
VAT that may be due.
Warranty Procedure
To obtain service under this warranty, please return the item(s) in question to the point of purchase. All autho-
rized distributors and dealers have a warranty program. Anyone returning goods to Digital Security Controls
Ltd. must first obtain an authorization number. Digital Security Controls Ltd. will not accept any shipment
whatsoever for which prior authorization has not been obtained.
Conditions to Void Warranty
This warranty applies only to defects in parts and workmanship relating to normal use. It does not cover:
• damage incurred in shipping or handling;
• damage caused by disaster such as fire, flood, wind, earthquake or lightning;
• damage due to causes beyond the control of Digital Security Controls Ltd. such as excessive voltage,
mechanical shock or water damage;
• damage caused by unauthorized attachment, alterations, modifications or foreign objects;
• damage caused by peripherals (unless such peripherals were supplied by Digital Security Controls Ltd.);
• defects caused by failure to provide a suitable installation environment for the products;
• damage caused by use of the products for purposes other than those for which it was designed;
• damage from improper maintenance;
• damage arising out of any other abuse, mishandling or improper application of the products.
Items Not Covered by Warranty
In addition to the items which void the Warranty, the following items shall not be covered by Warranty: (i)
freight cost to the repair centre; (ii) products which are not identified with DSC's product label and lot number
or serial number; (iii) products disassembled or repaired in such a manner as to adversely affect performance
or prevent adequate inspection or testing to verify any warranty claim. Access cards or tags returned for
replacement under warranty will be credited or replaced at DSC's option. Products not covered by this war-
ranty, or otherwise out of warranty due to age, misuse, or damage shall be evaluated, and a repair estimate shall
be provided. No repair work will be performed until a valid purchase order is received from the Customer and
a Return Merchandise Authorisation number (RMA) is issued by DSC's Customer Service.
Digital Security Controls Ltd.’s liability for failure to repair the product under this warranty after a reasonable
number of attempts will be limited to a replacement of the product, as the exclusive remedy for breach of war-
ranty. Under no circumstances shall Digital Security Controls Ltd. be liable for any special, incidental, or con-
sequential damages based upon breach of warranty, breach of contract, negligence, strict liability, or any other
legal theory. Such damages include, but are not limited to, loss of profits, loss of the product or any associated
equipment, cost of capital, cost of substitute or replacement equipment, facilities or services, down time, pur-
chaser’s time, the claims of third parties, including customers, and injury to property. The laws of some juris-
dictions limit or do not allow the disclaimer of consequential damages. If the laws of such a jurisdiction apply
to any claim by or against DSC, the limitations and disclaimers contained here shall be to the greatest extent
permitted by law. Some states do not allow the exclusion or limitation of incidental or consequential damages,
so that the above may not apply to you.
Disclaimer of Warranties
This warranty contains the entire warranty and shall be in lieu of any and all other warranties, whether expressed
or implied (including all implied warranties of merchantability or fitness for a particular purpose) And of all other
obligations or liabilities on the part of Digital Security Controls Ltd. Digital Security Controls Ltd. neither
assumes responsibility for, nor authorizes any other person purporting to act on its behalf to modify or to change
this warranty, nor to assume for it any other warranty or liability concerning this product.
This disclaimer of warranties and limited warranty are governed by the laws of the province of Ontario, Canada.
WARNING: Digital Security Controls Ltd. recommends that the entire system be completely tested on a reg-
ular basis. However, despite frequent testing, and due to, but not limited to, criminal tampering or electrical
disruption, it is possible for this product to fail to perform as expected.
Installer’s Lockout
Any products returned to DSC which have the Installer’s Lockout option enabled and exhibit no other prob-
lems will be subject to a service charge.
Out of Warranty Repairs
Digital Security Controls Ltd. will at its option repair or replace out-of-warranty products which are returned
to its factory according to the following conditions. Anyone returning goods to Digital Security Controls Ltd.
must first obtain an authorization number. Digital Security Controls Ltd. will not accept any shipment whatso-
ever for which prior authorization has not been obtained.
Products which Digital Security Controls Ltd. determines to be repairable will be repaired and returned. A set
fee which Digital Security Controls Ltd. has predetermined and which may be revised from time to time, will
be charged for each unit repaired.
Products which Digital Security Controls Ltd. determines not to be repairable will be replaced by the nearest
equivalent product available at that time. The current market price of the replacement product will be charged
for each replacement unit.
NOTICE: The Industry Canada label identifies certified equipment. This certification means that the equip-
ment meets certain telecommunications network protective, operational and safety requirements. Industry
Canada does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of
the local telecommunications company. The equipment must also be installed using an acceptable method
of connection. The customer should be aware that compliance with the above conditions may not prevent
degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated
by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions,
may give the telecommunications company cause to request the user to disconnect the equipment.
User should ensure for their own protection that the electrical ground connections of the power utility, tele-
phone lines and internal metallic water pipe system, if present, are connected together. This precaution may
be particularly important in rural areas.
CAUTION: Users should not attempt to make such connections themselves, but should contact the appropri-
ate electric inspection authority, or electrician, as appropriate.
The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be con-
nected to a telephone loop which is used by the device, to prevent overloading. The termination on a loop
may consist of any combination of devices subject only to the requirement that the total of the Load Num-
bers of all the devices does not exceed 100.
The Load Number of this unit is 0.1B.

i
Table of Contents
Section 1: System Introduction 1
1.1 Specifications ........................................................................1
1.2 Additional Devices ..............................................................2
1.3 Out of the Box .......................................................................3
Section 2: Getting Started 4
2.1 Installation Steps ..................................................................4
2.2 Terminal Descriptions .........................................................4
2.3 Wire Routing for Power & Non-Power Limited .............5
2.4 Keybus Operation & Wiring ..............................................5
2.5 Current Ratings – Modules & Accessories .......................6
2.6 Keypad Assignment ............................................................6
2.7 Supervision ...........................................................................6
2.8 Removing Modules ..............................................................6
2.9 Fire Zone Wiring ..................................................................6
2.10 24-Hr Auxiliary Input Wiring (PGM2) ............................7
2.11 Zone Wiring ..........................................................................7
2.12 LINKS Zone Wiring .............................................................8
2.13 Keypad Zones .......................................................................8
Section 3: Keypad Commands 9
3.1 Arming and Disarming .......................................................9
3.2 Auto Bypass – Stay Arming ...............................................9
3.3 Automatic Arming ...............................................................9
3.4 [*] Commands .......................................................................9
3.5 Function Keys .....................................................................12
3.6 Features Available for the LCD5500Z .............................13
Section 4: How to Program 14
4.1 Installer’s Programming ...................................................14
4.2 Programming Decimal Data .............................................14
4.3 Programming HEX Data ...................................................14
4.4 Programming Toggle Option Sections ............................15
4.5 Viewing Programming ......................................................15
Section 5: Program Descriptions 16
5.1 Programming Security Codes ..........................................16
5.2 Zone Programming ........................................................... 16
5.3 Zone Attributes .................................................................. 17
5.4 Assigning Keypad Zones ................................................. 18
5.5 Communicator – Dialing .................................................. 18
5.6 Communicator – Account Numbers .............................. 18
5.7 Communicator – Telephone Numbers ........................... 18
5.8 Communicator – Reporting Codes ................................. 18
5.9 Communicator – Reporting Formats .............................. 19
5.10 Downloading ..................................................................... 21
5.11 PGM Output Options ....................................................... 21
5.12 Telephone Line Monitor (TLM) ...................................... 23
5.13 Bell ....................................................................................... 23
5.14 Test Transmission .............................................................. 24
5.15 Transmission Delay .......................................................... 24
5.16 Fire, Auxiliary and Panic Keys ........................................ 24
5.17 Arming/Disarming Options ........................................... 24
5.18 Entry/Exit Delay Options ................................................ 25
5.19 Swinger Shutdown ............................................................ 25
5.20 Event Buffer ....................................................................... 25
5.21 Keypad Lockout Options ................................................. 25
5.22 Keypad Blanking ............................................................... 26
5.23 Keypad Backlighting ........................................................ 26
5.24 Loop Response ................................................................... 26
5.25 Keypad Tampers ............................................................... 26
5.26 LINKS1000 Cellular Communicator ............................... 26
5.27 Additional System Modules* .......................................... 27
5.28 Resetting Factory Defaults* ............................................. 27
5.29 Installer’s Lockout ............................................................. 27
5.30 Walk Test (Installer) .......................................................... 27
Section 6: Programming Worksheets 28
Appendix A: Reporting Codes 43
Appendix B: Programming LCD Keypads 45
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved by Digital Security Controls Ltd.
could void your authority to use this equipment.
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause harmful inter-
ference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following
measures:
• Re-orient the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
• Consult the dealer or an experienced radio/television technician for help.
The user may find the following booklet prepared by the FCC useful: “How to Identify and
Resolve Radio/Television Interference Problems”. This booklet is available from the U.S. Gov-
ernment Printing Office, Washington D.C. 20402, Stock # 004-000-00345-4.
IMPORTANT INFORMATION
This equipment complies with Part 68 of the FCC Rules. On the side of this equipment is a label
that contains, among other information, the FCC registration number of this equipment.
Notification to Telephone Company The customer shall notify the telephone company of the
particular line to which the connection will be made, and provide the FCC registration number
and the ringer equivalence of the protective circuit.
FCC Registration Number: F53CAN-32028-AL-E
Facility Interface Code: 02LS2
Ringer Equivalence Number: 0.1B
Service Order Code: 9.0F
USOC Jack: RJ-31X
Telephone Connection Requirements Except for the telephone company provided ringers,
all connections to the telephone network shall be made through standard plugs and telephone
company provided jacks, or equivalent, in such a manner as to allow for easy, immediate discon-
nection of the terminal equipment. Standard jacks shall be so arranged that, if the plug connected
thereto is withdrawn, no interference to the operation of the equipment at the customer’s pre-
mises which remains connected to the telephone network shall occur by reason of such with-
drawal.
Incidence of Harm Should terminal equipment or protective circuitry cause harm to the tele-
phone network, the telephone company shall, where practicable, notify the customer that tempo-
rary disconnection of service may be required; however, where prior notice is not practicable, the
telephone company may temporarily discontinue service if such action is deemed reasonable in
the circumstances. In the case of such temporary discontinuance, the telephone company shall
promptly notify the customer and will be given the opportunity to correct the situation.
Additional Telephone Company Information The security control panel must be properly
connected to the telephone line with a USOC RJ-31X telephone jack.
The FCC prohibits customer-provided terminal equipment be connected to party lines or to be
used in conjunction with coin telephone service. Interconnect rules may vary from state to state.
Changes in Telephone Company Equipment or Facilities The telephone company may
make changes in its communications facilities, equipment, operations or procedures, where such
actions are reasonably required and proper in its business. Should any such changes render the
customer’s terminal equipment incompatible with the telephone company facilities the customer
shall be given adequate notice to the effect modifications to maintain uninterrupted service.
Ringer Equivalence Number (REN) The REN is useful to determine the quantity of devices
that you may connect to your telephone line and still have all of those devices ring when your
telephone number is called. In most, but not all areas, the sum of the RENs of all devices con-
nected to one line should not exceed five (5.0). To be certain of the number of devices that you
may connect to your line, you may want to contact your local telephone company.
Equipment Maintenance Facility If you experience trouble with this telephone equipment,
please contact the facility indicated below for information on obtaining service or repairs. The
telephone company may ask that you disconnect this equipment from the network until the prob-
lem has been corrected or until you are sure that the equipment is not malfunctioning.
Digital Security Controls Ltd. 160 Washburn St., Lockport, NY 14094

ii
PC1555MX Wiring Diagram
LCD5500Z
LCD5501Z
PC1555RKZ
LCD5501Z32
PC5502Z2
PC5506
PC5508Z
PC5516Z
PC5532Z
SL-8

1
Section 1: System Introduction
1.1 Specifications
Downloading Software Support
• PC1555MX v2.3 uses DLS-3 v1.3 and higher.
Flexible Zone Configuration
• Six fully programmable zones
• System expandable to 32 zones using:
• up to 8 keypad zone inputs and/or
• up to 32 wireless zones with the PC5132 wireless expan-
sion module
• 38 access codes: one master code, one maintenance
code, two duress codes, two supervision codes and 32
general access codes
• 27 zone types; 8 programmable zone attributes
• Normally closed, single EOL and double EOL zone wiring
Audible Alarm Output
• 700mA supervised bell output (current limited at 3A),
12VDC
• Steady or pulsed output
EEPROM Memory
• Does not lose programming or system status on complete
AC and battery failure
Programmable Outputs
• One programmable voltage output and one programmable
voltage output/input; 23 programmable options
• PGM1 = 50mA; PGM2 = 300mA (50/300 products)
• PGM2 = 50mA; PGM2 = 50mA (50/50 products)
• Eight additional low current (50mA) outputs available using
the PC5208 module
• Four additional high current (300mA) outputs available
using the PC5204 module; one PC5204 output fully super-
vised for siren
Powerful 1.5 Amp Regulated Power Supply
• 550 mA auxiliary supply, 12 VDC
• Positive Temperature Coefficient (PTC) components
replace fuses
• Supervision for loss of AC power, low battery
• Internal clock locked to AC power frequency
Power Requirements
• Transformer = 16.5 VAC, 40VA
• Battery = 12 volt 4Ah minimum rechargeable sealed lead
acid battery
• For household fire and burglary installations, two 7Ah bat-
teries in parallel must be used, providing 24 hours of
standby power and 4 minutes of alarm output power.
• For commercial burglary installations, a 4Ah (or larger) bat-
tery must be used, providing at least 4 hours of standby
power and 4 minutes of alarm output power.
NOTE: Do not install this panel outside of North America. By
design, this panel will not work if the AC line frequency drops
below 55.5Hz.
Remote Keypad Specifications
• Keypads available:
- PC5502Z2 2-zone LED keypad with 2-zone inputs
- PC5506 six zone LED keypad with zone input
- PC5508Z eight zone LED keypad with zone input
- PC5516Z sixteen zone LED keypad with zone input
- PC5532Z thirty-two zone LED keypad with zone input
- LCD5500Z alphanumeric keypad with zone input
- LCD5501Z fixed message LCD keypad with zone input
- LCD5501Z32 keypad / receiver
- SL-8 Slimline 8 zone LED keypad
• All keypads have five programmable function keys
• Connect up to eight keypads
• 4-wire (Quad) connection to Keybus
• Built in piezoelectric buzzer
Digital Communicator Specifications*
• Supports major communication formats including SIA and
Contact ID
• Digital communicator compatible receivers and their for-
mats:
Silent Knight Model 9000: 3/1, 4/1, 4/2 non-extended, 3/1
extended, 20 bps, 1400 Hz handshake.
Ademco Model 685: 3/1, 4/1, 4/2 non-extended, 3/1
extended, 20 bps, 1400 Hz handshake, Contact ID.
Sescoa Model 3000: 3/1, 4/1, 4/2 non-extended, 3/1
extended, 20 bps, 1400 Hz handshake.
Radionics Model D6500: 3/1, 4/2 non-extended, 3/1
extended, with or without parity, 1400 and 2300 Hz hand-
shake. Sur-Gard Model MLR2-DG: 3/1, 4/1, 4/2, without
parity, 20 bps, 1400 and 2300 Hz handshake, Contact ID,
SIA.
• Event-initiated personal paging
• Three programmable telephone numbers
• Two account numbers
• Supports LINKS1000 cellular communication
• Supports LINKS2X50 long range radio transmitter
• Supports Skyroute transceiver
• DTMF and pulse dialing
• DPDT line seizure
• Anti-jam feature
• Split reporting of selected transmissions to each telephone
number
System Supervision Features
The PC1555MX continuously monitors a number of possible
trouble conditions including:
• AC power failure• AUX Power Supply Trouble
• Fault by zone• Loss of internal clock
• Tamper by zone• Bell output trouble
• Fire trouble• Telephone line trouble
• Failure to communicate• Low battery condition (panel)
• Low battery by zone (wireless)
• Module fault (supervisory or tamper)
False Alarm Prevention Features
• Audible Exit Delay• Quick Exit
• Audible Exit Fault • Cross Zone Burglary Alarm
• Communication Delay• Rotating Keypress Buffer
• Urgency on Entry Delay• One Restart of Exit Delay
Additional Features
• Auto Arm at specified time
• Keypad-activated alarm output and communicator test
• All modules connect to the system via a four wire Keybus
up to 1000’/305m from main panel
• An event buffer which records the past 128 events with
both the time and date at which they occurred; buffer can
be printed using PC5400 serial interface module, or
viewed with the LCD5500Z keypad and DLS-3 software
• Supports the addition of the PC5132 wireless receiver for
integration of wireless devices
• Uploading and downloading capability
• Local downloading capability through the use of the
PC-Link adaptor
• Supports the Escort5580 Voice Prompt Module with auto-
mation/lighting control
• Supports the addition of the PC5928 Audio Interface Mod-
ule to integrate intercom stations
*LINKS2X50 has not been investigated by UL.

2
• Added Keybus fault protection: clock and data outputs
have been programmed to withstand shorts to +12v to pre-
vent control panel damage
1.2 Additional Devices
In addition to the information below, see the back cover for a
DSC module compatibility table.
PC5132 Wireless Receiver
The PC5132 wireless receiver can be used to connect up to
32 wireless devices to the system. All devices are fully super-
vised which use standard alkaline or lithium batteries.
The devices available are as follows:
WLS904 Wireless Motion Detector: Adds wireless space
protection to your system.
WLS904P Wireless [Pet Immune] Motion Detector: The
WLS904P detector provides effective immunity to single or
multiple pets whose total combined weight does not exceed
60 lbs.
WLS906 Wireless Smoke Detector: Adds smoke detection
to your system.
WLS907 Wireless Slimline Universal Transmitter: A smaller
wireless door or window contact.
WLS907T Wireless Low Temperature Sensor: Adds low
temperature detection to your system.
WLS908 Wireless Panic Pendant: Adds personal protection
to the system. When used, the unit will indicate a non-medical
emergency to the central station.
WLS909 Wireless Key: Adds a simple and mobile method of
arming and disarming to the system, as well as one-button
access to several programmable functions.
WLS912 Glassbreak Detector: This is a battery-operated
glassbreak sensor, designed to detect the sound produced by
the shattering of framed glass.
WLS914 Dual PIR Motion Detector: Provides superior intru-
sion detection, using a specially designed lens which enables
the detector to discriminate between humans and small to
mid-sized pets.
WLS919 Wireless Key: The WLS919 wireless key allows you
to arm and disarm your system, as well as perform other key-
pad functions, from a unit small enough to keep in your pocket.
WLS925L Mini Door/Window Contact: Adds wireless win-
dow or door contacts to your system.
WLS935L Mini Door/Window Contact: Adds wireless win-
dow or door contacts to your system.
PC5400 Printer Module
The PC5400 Printer Module allows the panel to print out all
events that occur on the system to any serial printer. The print-
out will contain the time, date and the event that occurred.
PC5204 Power Supply Output Module
The PC5204 can provide up to 1 Amp of additional power for
modules or devices connected to the control panel. The mod-
ule requires a 16.5 volt AC 40 VA transformer and 4 AH bat-
tery. In addition, the module provides 4 programmable high
current voltage outputs. Each output is individually program-
mable (see 5.11“PGM Output Options” ) (see PC5204 Installa-
tion Instructions Sheet).
PC5208 Eight Low Current Output Module
Adds eight low current outputs (50 mA) to the control. Each
output is individually programmable. (see 5.11“PGM Output
Options” ) (See PC5208 Installation Instructions Sheet.)
Escort5580(TC) Module
This Escort5580(TC) module will turn any touch tone phone into
a fully functional keypad. The module also includes a built-in
interface to control up to 32 line carrier type devices for lighting
and temperature control (See Escort5580(TC) Installation Man-
ual).
PC5928/PC5936 Audio Interface Modules
The Audio Interface module is a simple way to incorporate
paging, intercom, baby listen-in and door answer to the
PC1555MX control panel . The modules have built-in talk/listen
voice capability for central station. Four additional devices are
available:
PC5921 Intercom Audio Station
Used in conjunction with the PC5928 Audio Interface Module.
PC5921 EXT Door Box Audio Station
Used in conjunction with the PC5928 Audio Interface Module.
PC5921 EXT/R Door Box Audio Station
Used in conjunction with the PC5928 Audio Interface Module. The
door box contains a relay so the normal door bell can be used
instead of the internal one generated by the PC5928 module.
PC5904 Central Station Talk/Listen Module
Used in conjunction with the PC5928 audio interface module
for talk/listen-in purposes. This station provides an added
level of volume to the central station operator’s voice.
Each station has a separate microphone and speaker. Each
station must be home-run to the interface module using
shielded 22 gauge, 4 conductor wire. All stations can be used
to sound an alarm follower.
LINKS1000 Cellular Communicator
The LINKS1000 cellular communicator can be used three dif-
ferent ways: as the sole communicator for the panel, as a
backup for either or both telephone numbers or as a redun-
dant backup to the land line communicator where the panel
will call both the land line and via the LINKS.
LINKS2X50*
Either the LINKS2150 or LINKS2450 may be used to transmit
alarm information over a long range radio network.
Skyroute Transceiver
The Skyroute transceiver offers a new wireless method of
communication for the transmission of events using cellemetry
service.
Cabinets
Several different cabinets are available for the PC1555MX
modules. They are as follows:
PC500C Cabinet (Household Burglary)
Control panel enclosure. Dimensions 203.5mm x 229mm x
78mm / 8.0”x 9.0”x 3.0”approximately.
PC5003C Cabinet (Household Fire & Burglary)
Main control cabinet for the PC1555MX main panel. Dimen-
sions 288mm x 298mm x 78mm / 11.3”x 11.7”x 3”approxi-
mately.
PC5004C Cabinet
Cabinet to house the PC5400 Printer Module. Dimensions
229mm x 178mm x 65mm / 9”x 7”x 2.6”approximately.
CMC-1 Cabinet (Commercial Burglary)
Control panel enclosure. Dimensions 303.3mm x 293.1mm x
78mm /11.9”x 11.5”x 3.0”approximately.
Backplates
There are two different backplates available for keypads
which enables to locate an audio station next to the keypad:
*LINKS2X50 has not been investigated by UL.

3
PC55BP1 Backplate
This backplate is to be used when an audio station is to be
located next to a keypad. Dimensions 208mm x 115mm x
18mm / 8.2”x 4.5”x 0.25”approximately.
PC55BP2 Backplate
This backplate is to be used when an audio station is to be
located next to a keypad. In addition the backplate will allow
you to mount a PC5208 8 low current output module. Dimen-
sions 208mm x 115mm x 18mm / 8.2”x 4.5”x 0.7”approxi-
mately.
1.3 Out of the Box
Please verify that the following components are included in
your system:
•one main control cabinet
•one PC1555MX main control circuit board
•one Power keypad with zone input
•one Installation Manual with programming worksheets
•one Instruction Manual for the end user
•one hardware pack consisting of:
- one mylar cabinet label
- four plastic circuit board standoffs
- sixteen 5600Ω(5.6K) resistors
- one 2200Ω(2.2K) resistor
- one 1000Ω(1K) resistor
- ground connection assembly
- one cabinet door plug (if required)

4
Section 2: Getting Started
The following sections provide a thorough description of how
to wire and configure devices and zones.
2.1 Installation Steps
Read this section completely before you begin. Once you
have an overall understanding of the installation process,
carefully work through each step.
Step 1: Create a Layout
Draw a rough sketch of the building to get an idea of where all
alarm detection devices, keypads and other modules are to
be located.
Step 2: Mounting the Panel
Mount the panel in a dry area close to an unswitched AC
power source and the incoming telephone line. Before attach-
ing the cabinet to the wall, be sure to press the four circuit
board mounting studs into the cabinet from the back.
NOTE: You must complete all wiring before connecting the bat-
tery, or applying AC to the panel.
Step 3: Wiring the Keybus (Section 2.3)
Wire the Keybus to each of the modules following the guide-
lines provided in Section 2.3 of this manual.
Step 4: Zone Wiring (Section 2.8)
You must power down the control panel to complete all zone
wiring. Please refer to 2.11 “Zone Wiring” when connecting
zones using normally closed loops, single EOL resistors, dou-
ble EOL resistors, Fire zones and Keyswitch Arming zones.
Step 5: Complete Wiring (Section 2.2)
Complete all other wiring including bells or sirens, telephone
line connections, and ground connections following the guide-
lines provided in Section 2.2 (“Terminal Descriptions”).
Step 6: Power up the Control
Once all zone and Keybus wiring is complete, power up the
control panel. First, connect the red battery lead to the posi-
tive terminal and the black lead to negative. Then, connect the
AC.
NOTE: Connect the battery before connecting the AC. You
must apply AC power to the panel for at least 10 seconds, or
the panel will not function. The panel will not power up on the
battery connection alone.
Step 7: Keypad Assignment (Section 2.6)
In order for keypads to be properly supervised, each must be
assigned to a different slot. Please follow the guidelines pro-
vided in Section 2.5 when assigning keypads.
Step 8: Supervision (Section 2.7)
The supervision of each module by the panel is automatically
enabled upon power up. Please verify that all modules appear
on the system according to the instructions in Section 2.6.
Step 9: Programming the System (Sections 4 & 5)
Section 4 explains how to program the panel. Section 5 con-
tains a complete description of the various programmable fea-
tures, which options are available and how they function. Fill
out the Programming Worksheets completely before attempt-
ing to program the system.
Step 10: Testing the System
Test the panel thoroughly to ensure that all features and func-
tions are operating as programmed.
2.2 Terminal Descriptions
Battery Connection
A 12V 4Ah rechargeable battery is used as a backup source
of power in the event of an AC power failure. The battery also
provides additional current when the panel’s demands exceed
the power output of the transformer, such as when the panel is
in alarm.
NOTE: Do not connect the battery until all other wiring is com-
plete. Connect the battery before connecting the AC.
Connect the RED battery lead to the positive battery terminal;
connect the BLACK lead to negative.
AC Terminals – AC
The panel requires a 16.5VAC, 40VA transformer. Connect the
transformer to an unswitched AC source and connect the
transformer to these terminals.
NOTE: Do not connect the transformer until all other wiring is
complete.
Auxiliary Power Terminals – AUX+ and AUX-
These terminals provide up to 550 mA of additional current at
12 VDC for devices requiring power. Connect the positive side
of any device requiring power to the AUX+ terminal, the nega-
tive side to AUX- (ground). The AUX output is protected. This
means that if too much current is drawn from these terminals
(such as a wiring short), the panel will temporarily shut off the
output until the problem is corrected.
Bell Output Terminals – BELL+ and BELL-
These terminals provide up to 700 mA of continuous current at
12 VDC for powering bells, sirens, strobes, etc. Connect the
positive side of any alarm warning device to BELL+, the nega-
tive side to BELL–. Please note that the bell output is pro-
tected: if too much current is drawn from these terminals (such
as a wiring short), the bell PTC will open. Three Amps can be
drawn for short periods only.
The bell output is supervised. If no alarm warning devices are
in use, connect a 1000Ωresistor across BELL+ and BELL–to
prevent the panel from displaying a trouble condition. For
more information, please refer to “[*][2] Trouble Display” ).
For UL installations, when a bell or
siren is used for fire signaling with a
pulsed cadence, it must be con-
nected between the AUX+ and
BELL- terminals. To maintain bell cir-
cuit supervision, do not connect
more than one device to the bell ter-
minal. A fire bell or siren used for
this application must be UL Listed and have a current con-
sumption of 700mA or less (e.g., Wheelock MT-12/24-R).
Keybus Terminals – AUX+, AUX-, YEL, GRN
The Keybus is used by the panel to communicate with mod-
ules and vice versa. Each module has four Keybus terminals
that must be connected to the four Keybus terminals on the
panel. For more information, see section 2.4 “Keybus Opera-
tion & Wiring” .

Getting Started: 2.3 Wire Routing for Power & Non-Power Limited
5
Programmable Output Terminals – PGM1 and PGM2
Each PGM output is designed so that when activated by the
panel, the terminal will switch to ground
PGM1 can sink up to 50mA of
current. Connect the positive
side of the LED or buzzer to
AUX+, the negative side to
PGM1. PGM2 operates similarly
to PGM1. However, PGM2 can
sink up to 300mA of current. If
more than 300mA of current are
required, a relay must be used.
NOTE: For the 50/50 version of
this panel, PGM2 can sink up to
50mA. If more current is
required, a relay must be used.
Please study PGM wiring in the
accompanying diagram. For a
list of the programmable output options, please see section
5.11 “PGM Output Options” .
Zone Input Terminals – Z1 to Z6
Each detection device must be connected to a zone on the
control panel. We suggest that one detection device be con-
nected to each zone; wiring multiple detection devices to a
single zone, however, is possible. For zone wiring specifics,
please see section 2.11 “Zone Wiring” .
Telephone Connection Terminals – TIP, RING, T-1, R-1
If a telephone line is required for central station communica-
tion or downloading, connect an RJ-31X telephone jack in the
following manner:
Connect the PC1555MX and modules which use the tele-
phone line(s) in the following order:
For example, if you are installing a PC1555MX with a
LINKS1000 and a PC5928 Intercom module, connect the
incoming line to the LINKS1000, then from the LINKS1000 to
the PC1555MX, then from the PC1555MX to the PC5928 Inter-
com and then from the PC5928 to the house telephones.
NOTE: Please ensure that all plugs and jacks meet the dimen-
sion, tolerance and metallic plating requirements of 47 C.F.R.
Part 68, SubPart F. For proper operation, no other telephone
equipment should be connected between the control panel and
the telephone company facilities. Do not connect the alarm
panel communicator to telephone lines intended for use with a
fax machine. These lines may incorporate a voice filter which
disconnects the line if anything other than fax signals is
detected, resulting in incomplete transmissions.
2.3 Wire Routing for Power & Non-Power
Limited
All wiring entry points are designated by the arrows. All cir-
cuits are classified UL installation power limited except for the
battery leads which are not power limited.
A minimum ¼” (6.4mm) separation must be maintained at all
points between power limited and non-power limited wiring
and connections.
NOTE: Wire entry for power limited wiring must be separated
by a different entry access from non-power limited wiring.
2.4 Keybus Operation & Wiring
The keybus is used by the panel to communicate with all con-
nected modules and vice versa. The red (AUX+) and black
(AUX-) terminals are used to provide power, while the yellow
(YEL) and green (GRN) terminals are clock and data respec-
tively.
NOTE: The four Keybus terminals of the panel must be con-
nected to the four Keybus terminals or wires of all modules.
The following restrictions apply to keybus wiring:
•Keybus should be run in minimum 22-gauge quad
(0.5mm); two pair twisted is preferred.
•The modules should be home-run to the panel but can be
connected in series or T-tapped.
•Any module can be connected anywhere along the key-
bus. You do not need to run a separate keybus wire for
keypads, etc.
•No module can be more than 1,000'/305m (in wire length)
from the panel.
•Shielded wire should not be used.
Example of Keybus Wiring
NOTE: Module (A) is cor-
rectly wired within 1,000'/
305m from the panel. Module
(B) is correctly wired within
1,000'/305m of wire from the
panel. Module (C) is NOT
wired correctly as it is further
than 1,000'/305m from the
panel, in wire distance.
2.5 Current Ratings – Modules &
Accessories
In order for the PC1555MX system to operate properly, the
power output capabilities of the main control and the expan-
Keybus
NOTE: A minimum 1/4" (6.4mm) separation
must be maintained at all points between
power limited and non-power limited wiring
and connections.

6
sion devices must not be exceeded. Use the data presented
below to ensure that no part of the system is overloaded and
that all parts can function properly.
PC1555MX (12 VDC)
AUX+: ........ 550mA: Subtract the listed rating for each key-
pad, expansion module and accessory con-
nected to AUX+ or Keybus.
BELL:......... 700mA continuous rating; 3.0A short term. Avail-
able only with standby battery connected.
PC1555MX Device Ratings (at 12 VDC)
•Escort5580(TC) Audio Assistant: 65mA standby/130mA
on-line
•LCD5500Z Keypad: 85mA max.
•LCD5501Z Keypad: 45mA standby, 90mA max.
•LCD5501Z32 Keypad and Receiver: 260mA max.
•PC5502Z2 Keypad: 25mA max.
•PC1555RKZ Keypad: 85mA max.
•PC5102 Wireless Receiver: 50mA, 200mA
•PC5132 Wireless Receiver: 125mA
•PC5200 Power Supply Module: 20mA
•PC5204 High Current Output module: 20mA
•PC5208 Low Current Output module: 50mA
•PC5400 Serial Module: 65mA
•PC5508Z Keypad: 80mA
•PC5516Z Keypad: 90mA
•PC5532Z Keypad: 120mA
•PC5921/EXT Door Box Audio Station: 20mA
•PC59X1EXT/R Door Box Audio Station: 35mA
•PC5904 Central Station Talk/Listen Module: 30mA standby,
130mA max.
•PC5928 Audio Interface module: 65mA
Other Devices
Please read the manufacturer’s literature carefully to deter-
mine the maximum current requirements for each device—
during activation or alarm—and include the proper values for
loading calculations. Connected devices must not exceed
system capabilities during any possible operational mode.
2.6 Keypad Assignment
There are eight available slots for keypads. LED/LCD5501Z
keypads by default are always assigned to slot 1. LCD5500Z
keypads are always assigned to slot 8. You will need to assign
each keypad to its own slot (1 to 8). Keypad assignment is
required, as it tells the panel which slots are occupied. The
panel can then generate a fault when a keypad supervisory is
not present.
NOTE: One LCD keypad must be assigned to slot 8 in order to
upload keypad programming using DLS-3 software.
How to Assign Keypads
Do the following at each keypad installed on the system:
1. Enter [*][8][Installer’s Code] to go to Installer Programming
2. Enter [000] for keypad programming
3. Enter [0] for slot assignment
4. Enter a two digit number (11-18) to specify which supervi-
sory slot the keypad will occupy.
5. Press [#] twice to exit installer programming.
After assigning all keypads, perform a supervisory reset by
entering section [902] in Installer’s Programming. The panel
will now supervise all assigned keypads and enrolled modules
on the system.
How to Program Function Keys
By default, the 5 function keys on each keypad are pro-
grammed as Stay arm (03), Away arm (04), Chime (06), Sen-
sor Reset (14) and Quick Exit (16). You can change the
function of each key on every keypad:
1. Go to the keypad where you want to change the function
key programming and enter installer programming.
2. Press [000] for keypad programming.
3. Enter [1] to [5] to select a function key to program.
4. Enter the 2 digit number, [00] to [21] to select the feature
you want the function key to have. For a complete list of
function key options see section 3.5 “Function Keys” .
5. Continue from step 3 until all function keys are pro-
grammed.
6. To exit Installer Programming, press [#] twice.
2.7 Supervision
By default, all modules are supervised upon installation.
Supervision is enabled at all times so that the panel can indi-
cate a trouble if a module is removed from the system.
To check which modules are currently connected and super-
vised, enter programming section [903] from installer pro-
gramming. The LCD keypad will allow you to scroll through the
display of connected modules. A connected module which
does not show as being present will appear as a trouble con-
dition and the Trouble light on the keypad will turn ON. This
condition may be due to one or more of the following reasons:
•the module is not connected to the Keybus
•there is a Keybus wiring problem
•the module is more than 1,000'/305m from the panel
•the module does not have enough power
For more information regarding module supervision troubles,
please refer to “[*][2] Trouble Display” .
2.8 Removing Modules
The panel must be instructed to no longer supervise a module
being removed from the system. To remove the module, discon-
nect it from the Keybus and reset the supervision field by enter-
ing [902] in installer programming. The panel will be reset to
recognize and supervise all existing modules on the system.
2.9 Fire Zone Wiring
4-Wire Smoke Detectors
All fire zones must be wired according to the following diagram:
2-Wire Smoke Detectors (50/300 only)
If PGM2 has been programmed for a 2-wire smoke detector
connection, the detectors must be wired according to the fol-
lowing diagram:

Getting Started: 2.10 24-Hr Auxiliary Input Wiring (PGM2)
7
NOTE: See the Wiring Diagram Compatibility Chart for a list of
compatible 2-wire smoke detectors.
NOTE: If PGM2 is programmed for 2-wire smoke support, the
connector JP1 on the main board must be removed.
NOTE: 2-wire smoke detectors are not supported on the 50/50
version of the panel.
2.10 24-Hr Auxiliary Input Wiring (PGM2)
If PGM2 has been programmed for 24-hour operation, the
zone must be wired according to the following diagram:
NOTE: If PGM2 is pro-
grammed for 24-hr auxil-
iary input support, the
connector JP1 on the main
board must be removed.
2.11Zone Wiring
For a complete description of the operation of all zone types,
please refer to 5.2 “Zone Programming” .
There are several different ways in which zones may be wired,
depending on which programming options have been
selected. The panel can be programmed to supervise nor-
mally closed, end of line, or double end of line loops. Please
refer to the following diagrams to study each type of individu-
ally supervised zone wiring.
NOTE: Any zone programmed for fire or 24 hour supervisory
must be wired with a single end of line (EOL) resistor regard-
less of the type of zone wiring supervision selected for the
panel (section [013]: [1] -[2]). see 5.2“Zone Programming”
NOTE: If you change the zone supervision options from DEOL
to EOL or from NC to DEOL (section [013], options [1] or [2]),
you should power down the system completely, and then
power it back up. If you do not, the zones may not work cor-
rectly.
Normally Closed (NC) Loops
To enable normally closed loops, programming section [013],
option [1] must be ON.
NOTE: This option should only be selected if normally closed
(NC) detection devices or contacts are being used.
Single End Of Line (EOL) Resistors (5600Ω)
To enable panel detection of single end of line resistors, pro-
gramming section [013], Options [1] and [2] must be OFF.
NOTE: This option should be selected if either normally closed
(NC) or normally open (NO) detection devices or contacts are
being used.
Double End of Line (DEOL) Resistors
Double end of line resistors allow the panel to determine if the
zone is in alarm, tampered or faulted.
To enable panel detection of double end of line resistors, pro-
gramming section [013], option [1] must be OFF and option
[2] must be ON.
NOTE: If the double EOL supervision option is enabled, all
hardwire zones on the main panel must be wired for double
EOL resistors, except for fire and 24 Hour supervisory zones.
NOTE: Do not wire DEOL resistors on keypad zones.
NOTE: Do not use DEOL resistors for fire zones or 24 hour
supervisory zones. Do not wire fire zones to keypad zone ter-
minals if the DEOL supervision option is selected.
NOTE: This option can only be selected if normally closed
(NC) detection devices or contacts are being used.
NOTE: Only one NC contact can be connected to each zone.
Wiring multiple detection devices or contacts on a single loop
is not allowed.
The following chart shows zone status under certain conditions:
Loop Resistance Loop Status
0Ω(shorted wire, loop shorted) Fault
5600Ω(contact closed) Secure
Infinite (broken wire, loop open) Tamper
11200Ω(contact open) Violated
End-of-Line Resistors. . . . . . . . . . . . . . . . . .Section [013]: [1]
Double End-of-Line Resistors . . . . . . . . . . .Section [013]: [2]
ANY Z
TERMINAL
ANY COM
TERMINAL
ANY Z
TERMINAL
ANY COM
TERMINAL

8
2.12 LINKS Zone Wiring
LINKS Support
When using the LINKS1000
cellular communicator, con-
nect the LINKS to the main
panel according to the fol-
lowing diagram:
LINKS Supervision (24 Hour Supervisory)
When using the
LINKS1000 cellular com-
municator, any main board
zone may be configured
for LINKS supervision. Pro-
gram this zone as zone
type [09], 24 hour supervi-
sory in section [001].
With a LINKS supervisory
zone, if the LINKS1000
experiences a trouble, the
zone will be violated, caus-
ing the panel to report the event to the central station. This
type of zone always requires a single EOL resistor (5600Ω).
Wire this zone according to the above diagram.
LINKS Answer
When using the LINKS1000
cellular communicator, any
main board zone may be
configured for LINKS
Answer.
A zone configured for
LINKS Answer allows down-
loading to be performed in
the event of telephone line
failure. When the LINKS
receives a telephone call, it
will activate the RING termi-
nal on the LINKS circuit board. The zone programmed as
LINKS Answer always requires a single EOL resistor (5600Ω).
Wire the LINKS Answer zone according to the above diagram.
NOTE: The LINKS Answer zone is only required for download-
ing to the panel via the LINKS.
NOTE: When using the LINKS, Busy Tone Detection must not
be used.
NOTE: Keypad zones cannot be used for 24 hour supervisory
or LINKS Answer.
2.13 Keypad Zones
Each ‘Z’keypad on the system has a zone input to which a
device - such as a door contact - can be connected. This
eliminates the need to run wires back to the control panel for
every device.
To install the keypad, open the keypad plastic by removing the
screw at the bottom of the unit. Locate the five terminals on
the keypad circuit board. Connect the four Keybus wires from
the control panel: the red wire to R, the black to B, the yellow
to Y and the green to G.
To connect the zone, run one wire to the Z terminal and the
other to B. For powered devices, use red and black to supply
power to the device. Run the red wire to the R (positive) termi-
nal and the black wire to the B (negative) terminal.
When using end of line supervision, connect the zone accord-
ing to one of the configurations outlined in section 2.11 “Zone
Wiring”. End of line resistors must be placed on the device
end of the loop, not at the keypad.
NOTE: Keypad zones do not support DEOL resistors.
NOTE: Only non 24-hr burglary type zones can be configured
as keypad zones for UL Listed products.
Assigning Keypad Zones
When using keypad zone inputs, each input used must be
assigned a zone number in installer programming.
First, ensure that you have enrolled all installed keypads into
the desired slots. (see 2.6“Keypad Assignment” )
Next, enter programming section [020] to assign the zones.
There are eight programming locations in this section, one for
each keypad slot. Enter a 2-digit zone number for each of the
keypad zones. This number must be entered in the location
corresponding to the keypad to which each zone is con-
nected.
Example: The zone on an LCD5500Z keypad in slot 8 is to be
assigned zone 3. In section [020], scroll to option [8] and
enter (03).
NOTE: Keypad zones 1-6 will replace zone terminals Z1-Z6 on
the control panel.
NOTE: Once the keypad zones are assigned, you must also
program zone definitions and zone attributes. (See also 5.4
“Assigning Keypad Zones” ).
NOTE: Keypad zones can only be used for household bur-
glary-initiated devices. Devices attached to keypad zones
should be placed as close as possible to the keypad, and must
be wired as EOL loops. The keypad zone must be tested
weekly.

9
Section 3: Keypad Commands
Use any system keypad to enter commands and/or program
the PC1555MX security system. The LED keypad uses func-
tion and zone indicator lights to represent alarm functions and
status. The LCD keypad provides a written description on the
liquid crystal display and uses function indicator lights to
communicate alarm status to the user.
The PC1555MX Instruction Manual provides basic directions
for arming and disarming the system, bypassing zones and
performing user functions from the keypads. The following
sections provide additional details on these functions.
3.1 Arming and Disarming
For a description of basic arming and disarming, please see
the PC1555MX Instruction Manual. For other methods of arm-
ing, please refer to “[*][0] Quick Arm”,“[*][9] Arming Without
Entry Delay” and 3.5 “Function Keys” .
NOTE: The event buffer will log “Armed in Stay Mode” or
“Armed in Away Mode” whenever the system is armed.
In an attempt to prevent false alarms, the Audible Exit Fault
will notify the user of an improper exit when they arm their sys-
tem. If a non force-arming Delay 1 or Delay 2 type zone is left
open at the end of the exit delay, the entry delay will begin
immediately and the bell or siren will sound a steady alarm for
the entry delay period. At the end of the entry delay period, if
the system has not been disarmed it will go into alarm. This
feature can be turned OFF in programming section [013],
option [6]. (see 5.17“Arming/Disarming Options” )
3.2 Auto Bypass – Stay Arming
Stay Arming allows the user to arm the system without leaving
the premises. All zones programmed as Stay/Away will be
bypassed when the user stay arms the system, so that the
user does not have to bypass interior zones manually (see
5.2“Zone Programming” ).
When the system is armed using a valid access code, if any
zones on the system have been programmed as Stay/Away
zones, the Bypass light will turn ON. The panel will then moni-
tor all zones programmed as Delay 1 and Delay 2 zones, such
as designated entry/exit doors. If a delay zone is not violated
by the end of the exit delay, the panel will bypass all Stay/
Away zones. The Bypass light will remain on to inform the user
that the interior zones have been automatically bypassed by
the panel. If a delay zone is violated during the exit delay, the
system will arm in Away mode and all Stay/Away zones will be
active after the exit delay expires.
The user can arm the stay/away zones at any time by entering
the [*][1] keypad command (see “[*][1] Bypassing and Acti-
vating Stay/Away Zones” ). Stay Arming can also be initiated
by pressing and holding the Stay function key for two seconds
on the PC5508Z and LCD5500Z keypads, if programmed by
the installer. For more information regarding Stay arming,
please see 3.5 “Function Keys” .
3.3 Automatic Arming
The system can be programmed to auto-arm at a specific time
every day if it is in the disarmed condition. In order for the
auto-arm function to work properly, you must program the cor-
rect time of day. For programming the clock and auto-arm
times, see “[*][6] User Functions” .
When the system’s internal clock matches the auto-arm time,
the panel will check the system status. If the system is armed,
the panel will do nothing until the next day at the auto-arm
time, when it will check the system again. If the system is dis-
armed at the auto-arm time, the panel will sound the buzzer of
all keypads for one minute. If the Bell Squawk During Auto
Arm option is enabled (section [014], option [2]), the bell will
squawk once every 10 seconds while the system is auto-arm-
ing. If a valid access code is entered, auto-arming will be
aborted.
NOTE: If auto-arm is cancelled, the number of the user who
cancelled the auto-arm will be logged in the event buffer.
If no code is entered, the panel will auto-arm. If a zone is vio-
lated, the panel will transmit a Partial Closing reporting code –
if programmed –to indicate to the central station that the sys-
tem is not secure. If the zone is restored, the panel will add the
zone back into the system.
NOTE: Auto-arming can only be cancelled by entering a valid
access code at any keypad.
3.4 [*] Commands
The [*] key commands provide an easy way for the user to
access basic system programming –such as programming
access codes or bypassing zones. The user can also use the
[*] key commands to check on the system’s status, including
viewing trouble conditions and displaying the event buffer on
the LCD keypad.
The [*] key commands can be performed from both LCD and
LED keypads. The LED keypad uses the zone indicator lights
to display command information. The LCD display provides
written information, guiding the user through each command.
The commands in this section are explained as viewed from
an LED keypad. When using an LCD keypad, use the arrow
keys (< >) to scroll through information provided. Otherwise,
the functions remain the same for both keypad types.
[*][1] Bypassing and Activating Stay/Away Zones
Use the [*][1] keypad command to bypass individual zones. A
bypassed zone will not cause an alarm.
NOTE: Zones can only be bypassed when the system is not
armed.
If the Code Required for Bypass option is enabled (section
[015], option [5]), only access codes with the bypass attribute
enabled will be able to bypass zones. (see 5.1“Programming
Security Codes” )
If the Bypass Status Displayed While Armed option is cho-
sen, the Bypass light will be ON while the system is armed to
indicate any bypassed zones see 5.17“Arming/Disarming
Options” ).
NOTE: When you disarm the system, all manually bypassed
zones will be unbypassed.
Activate Stay/Away Zones
If the system is armed in Stay mode, the [*][1] command can
be used to activate the Stay/Away zones.
[*][2] Trouble Display
The panel constantly monitors itself for several different trou-
ble conditions. If a trouble condition is present, the Trouble
light will be on and the keypad will beep twice every 10 sec-
onds. The trouble beep can be silenced by pressing any key

10
on any keypad. If Bell Squawk on Trouble is enabled (sec-
tion [014], option [5]), the bell will squawk every 10 seconds
when a trouble condition is present.
To view trouble conditions from an LED or a Fixed Mes-
sage LCD keypad:
1. Press [*][2].
2. The keypad will flash the Trouble light. The zone indicator
lights corresponding to the present trouble conditions will
be ON.
When using an LCD keypad, the trouble conditions will be
listed on the display. Use the arrow (< >) keys to scroll through
the list of present trouble conditions.
NOTE: Troubles can be viewed while armed using the LCD
keypad, provided the keypad is version 2.0 or later. Older key-
pads will incorrectly display “Fire Trouble”. If using older LCD
keypads, programming section [013], option [3] as OFF will
ensure troubles are displayed correctly.
The various troubles are described below:
[*][3] Alarm Memory
The Memory light will be on if any alarm occurred during the
last armed period or –in the case of 24 hour zones –if an
alarm occurred while the panel was disarmed.
To view alarm memory, press [*][3]. The keypad will flash the
Memory light and the zone indicator lights corresponding to
the alarm or tamper conditions which occurred during or since
the last armed period. To clear the Memory light, arm and dis-
arm the system.
[*][4] Door Chime On/Off
The door chime feature is used to sound a tone from the key-
pad whenever a zone programmed as a chime zone is acti-
Light Trouble
1Service Required: Press [1] to determine the specific trouble. Lights 1 - 8 will light up to indicate the trouble:
•Light [1] Low Battery: Main panel backup battery charge is low (below 11.5 volts under load). Trouble is restored
when the battery charges over 12.5 volts.
•Light [2] Bell Circuit Trouble: The bell circuit is open (see section 5.13 “Bell” ).
•Light [3] General System Trouble: The PC5204 Power Supply module has an AUX failure, PC5204 Output #1 Trouble,
Home Automation Trouble, or a printer connected to the PC5400 Printer module has a fault and is off-line.
•Light [4] General System Tamper: Tamper has been detected in a module.
•Light [5] General System Supervisory: The panel has lost communication with a module connected to the Keybus
(see section 2.7 “Supervision” ). The event buffer will log the event.
NOTE: All tamper conditions must be physically restored before the trouble condition will clear.
•Light [6] –Not used
•Light [7] PC5204 Low Battery: The PC5204 module has a low backup battery.
•Light [8] PC5204 AC Failure: The PC5204 module has lost AC power.
NOTE: If you remove and then restore power to the main panel in order to service any PC5204 module, or
any module being powered by a PC5204, you must also remove and then restore power to the PC5204 and
any connected modules. This ensures that any troubles present on the module are correctly logged and/or
annunciated.
2AC Failure: AC power is no longer being supplied to the control panel. The Trouble light will flash if an AC Failure is
present, if the Trouble Light Flashes if AC Fails option is programmed (section [016], option [2]). This trouble will not
be displayed if the AC Trouble Displayed option is disabled (section [016], option [1]). See section 5.8 “Communica-
tor – Reporting Codes” for information on AC trouble reporting.
3Telephone Line Monitoring Trouble (TLM): There is a problem with the telephone line (See section 5.12 “Tele-
phone Line Monitor (TLM)” .)
4Failure to Communicate (FTC): The communicator failed to communicate with any of the programmed telephone
numbers (see section 5.5 “Communicator – Dialing” ).
5Zone Fault (including Fire Zone): A zone on the system is experiencing trouble, meaning that a zone could not
transmit an alarm to the panel if required to do so (e.g., a fire zone is open, or there is a short on a DEOL zone, or a
supervisory fault on a wireless zone). When a zone fault trouble condition occurs, the keypad(s) on the system will start
to beep. Press [5] while in Trouble mode to view the affected zones.
NOTE: A Fire zone trouble will be generated and displayed in the armed state.
6Zone Tamper: A zone configured for double end of line resistor supervision has a tamper condition, or the tamper switch
is open on a wireless device. When a tamper condition occurs, the keypad(s) will start to beep. Press [6] while in the Trou-
ble mode to view the affected zones. If a zone is tampered or faulted, it must be fully restored to clear the trouble.
NOTE: By enabling Tampers/Faults Do Not Show as Open in section [013], option [4], Faults and
Tampers will not show as open on the keypad, and will be hidden from the end user. If the option is disabled,
Faults and Tampers will be displayed on the keypad
NOTE: Once a zone is tampered or faulted, it must be completely restored before the trouble condition will
clear.
7Device Low Battery: A wireless device has a low battery condition. Press [7] one, two, or three times to view which
devices are experiencing battery failure. An LED keypad will indicate battery failure using zone lights 1 to 8. The follow-
ing will occur:
Keypad beeps: Keypad displays:
Press [7] 1 Zones with low batteries (LED keypad - zone lights 1 to 32)
Press [7] again 2 Handheld keypads with low batteries (LED keypad - zone lights 1 to 4)
Press [7] again 3 Wireless keys with low batteries (LED keypad - zone lights 1 to 8)
To view the battery conditions of wireless keys 9 through 16, you must use an LCD keypad.
8Loss of System Time: When the panel is powered up, the internal clock needs to be set to the correct time. This
trouble is cleared when an attempt is made to reset the clock.

Keypad Commands: 3.4 [*] Commands
11
vated. (see 5.3“Zone Attributes” ) If the door chime feature is
enabled, the keypad will emit five short beeps whenever a
chime zone is activated. Designated entry/exit doors are often
defined as chime zones. The feature can be turned on or off
while the system is armed or disarmed.
[*][5] Programming Access Codes
There are 37 access codes available to the user. They are:
Access code (40)......................One master code
Access codes (01)-(32).............32 general access codes
Access codes (33)-(34).............Two duress codes
Access codes (41)-(42).............Two supervisor codes
All access codes have the ability to arm or disarm the system
and can activate the PGM Outputs using the [*][7] com-
mands.
For a description of how to program access codes from LCD
or LED keypads, see the PC1555MX Instruction Manual.
Master Code – Access Code (40)
This code can be used to program all access codes. The
master code has all access code attributes enabled by
default, so that the master code can be used to perform any
keypad function. Master code attributes cannot be changed.
If the Master Code Not Changeable option is enabled, (sec-
tion [015], option [6]) the master code can only be changed
by the installer.
General Access Codes – Access Codes (01) to (32)
General access codes can arm and disarm the system. When
the Code Required for Bypassing option is enabled, users
will need to enter a valid access code when bypassing zones.
Individual access codes can have the Zone Bypassing
attribute disabled under Access Code Attribute programming.
For more information regarding access code options, please
see 5.1 “Programming Security Codes” .
Duress Code – Access Code (33) and (34)
Duress codes will send a duress reporting code to the central
station when entered.
NOTE: If a duress code is programmed, when it is used the
panel will always send a reporting code to the central station,
even if the attributes of the duress code are turned off.
Supervisor Codes – Access Code (41) and (42)
These codes can be used to program general access and
duress codes. The two supervisor codes have all attributes on
by default. These settings can be changed.
Access Code Attributes
There are four access code attributes which can be pro-
grammed for each code.
To program each attribute, enter [*][5][Master Code][9] to
enter the attribute programming mode. Then enter the code
number [01-32,33,34,41,42]. Enter the attribute number:
Attribute [1].......... User-enabled for arming, disarming, alarm
reset, [*][7][1-4] options, auto arm cancel-
lation
Attribute [2].......... Not used
Attribute [3].......... Zone bypassing enabled
Attribute [4].......... Escort5580(TC) access enabled
Attribute [5]-[6].... Not used
Attribute [7].......... Bell squawk on access code entry
Example: You can use the arm/disarm bell squawk attribute to
have wireless key access codes squawk the bell, while other
codes are silent. To do this, enable attribute [7] on all access
codes associated with wireless keys.
NOTE: If you enable the Bell Squawk on Arming/Disarming
(section [014], option [1]), the bell will sound arm/disarm bell
squawks for all access codes, regardless of the programming
for attribute [7]. see 5.17“Arming/Disarming Options”
NOTE: Master code attributes cannot be changed.
[*][6] User Functions
This command can be used to program several different func-
tions:
To program user functions:
1. Press [*][6][Master Code]. The Program light will flash.
2. Press the number [1] to [7] for the item to be programmed.
•[1] –Time and Date
The time and date must be accurate for the auto-arm or
test transmission functions to work properly and for the
event buffer to time and date-stamp all events.
- Enter the time (hour and minute) using 24hr format [HH
MM] from 0000 to 2359.
- Enter the date by month, day and year [MM DD YY].
•[2] –Auto-Arm Enable/Disable
To enable or disable auto-arming, press [2]. The keypad
will sound three short beeps when auto-arm is enabled
and one long beep when disabled. For more information,
see 3.3 “Automatic Arming” .
•[3] –Auto-Arm Time
The system can be programmed to arm automatically at a
pre-set time. When programming the auto-arm time, enter
the time (hour and minute) using 24hr format [HH MM]. For
more information, see 3.3 “Automatic Arming” .
•[4] –System Test
When [4] is pressed the panel will test the bell output, key-
pad lights and the communicator for two seconds. The
panel will also send a system test reporting code, if pro-
grammed. (see 5.8“Communicator – Reporting Codes” )
•[5] –Enable DLS (Downloading)
When [5] is pressed, the panel will enable the downloading
option for six hours. During this time, the panel will answer
incoming downloading calls. (see 5.10“Downloading” )
•[6] –User-Initiated Call-Up
When [6] is pressed, the panel will initiate a call to the
downloading computer.
•[7] –Enable Background Music
If enabled on the PC59XX audio interface module, when
[7] is pressed, the user can turn background music ON or
OFF.
Additional Features Available from the LCD Keypad
Additional features, including access to the event buffer, are
available using the LCD keypad. Use the arrow keys (< >) to
scroll through the [*][6] menu and press the [*] key to select
the following commands:
Viewing the Event Buffer from an LCD Keypad
Select “View Event Buffer”from the [*][6] menu. The keypad
will display the event, event number, time and date along with
the zone number and access code, if applicable. Press [*] to
toggle between this information and the event itself. Use the
arrow keys (<>) to scroll through the events in the buffer.
When you have finished viewing the event buffer, press [#] to
exit.
Brightness Control
You can select from 10 different backlighting levels. Use the
arrow keys (< >) to scroll to the desired backlighting level.
Press [#] to exit.
Contrast Control
You can select from 10 different display contrast levels. Use
the arrow keys (< >) to scroll to the desired contrast level.
Press [#] to exit.

12
Keypad Sounder Control
You can select from 21 different keypad tones. Use the arrow
keys (< >) to scroll to the desired keypad sound level and
press [#] to exit. This feature can be accessed on LED key-
pads by pressing and holding the [*] key.
[*][7] Command Output Functions
The user can activate programmable output functions using
the [*][7][1-4] commands. The outputs can be activated when
the system is either armed or disarmed.
Command Output Options 1-4:
Press [*][7][1-4][Access Code] (if required), to activate out-
puts programmed as PGM output option [19]-[22]. These out-
puts can be used for operating devices such as a garage
door opener, lighting or door strikes.
[*][7][2] – Command Output Option #2:
Press [*][7][2][Access Code, if required] to activate all outputs
programmed as one of PGM output options [03], [04] or [20].
Special Note: Traditionally, [*][7][2] has been reserved for
resetting smoke detectors. Smoke detectors should now be
programmed as output [03] “Sensor Reset”or [04] “2-wire
Smoke”. If using output option [03] or [04], do not program
[20] Command Output Option #2. Please see 5.11 “PGM Out-
put Options” for more information.
[*][8] Installer Programming
Enter [*][8] followed by the Installer’s Code to access
installer’s programming. See sections 4 and 5 for more infor-
mation.
[*][9] Arming Without Entry Delay
When the system is armed with the [*][9] command, the panel
will cancel the entry delay. Delay 1 and Delay 2 type zones will
be instant and Stay/Away zones will be bypassed as soon as
the exit delay has ended (see section 5.2 “Zone Program-
ming” ). The user must enter a valid access code after press-
ing [*][9].
[*][0] Quick Arm
If the Quick Arm option is enabled (section [015], option [4]),
enter [*][0] to arm the panel without an access code. (see
5.17“Arming/Disarming Options” ) If the Quick Arm option is
disabled, users will need to enter an access code after press-
ing a function key.
NOTE: Quick Arm cannot be used to cancel auto-arm.
[*][0] Quick Exit
The Quick Exit function, if enabled, will allow someone to
leave an armed premises through a Delay type zone without
having to disarm and re-arm the system. (see 5.17“Arming/
Disarming Options” )
When [*][0] is entered, the panel will provide a two minute win-
dow for the user to exit the premises. During this time, the
panel will ignore only one activation of a Delay zone. When the
Delay zone is secured, the panel will end the two minute quick
exit delay.
If a second Delay zone is tripped, or if the zone is not restored
after two minutes, the panel will begin entry delay 1.
NOTE: If the Exit Delay is in progress, performing a quick exit
will not extend the Exit Delay.
3.5 Function Keys
There are five function keys on each keypad labelled Stay,
Away, Chime, Reset and Exit. Each of these keys is pro-
grammed by default to perform one of the functions described
below. Press and hold the appropriate key for two seconds to
activate a function.
If the Quick Arm option is disabled (section [015], option [4]),
users will need to enter an access code after pressing a func-
tion key.
“Stay” – (03) Stay Arm
The system will arm in the Stay mode (see 3.2 “Auto Bypass –
Stay Arming” ). Enable the Quick Arm feature (programming
section [015], option [4]) to have this key function without the
need to enter an access code. If Quick Arm is not enabled,
the user will have to enter an access code before the system
will Stay arm.
“Away” – (04) Away Arm
The system will arm in the Away mode (see 3.2 “Auto Bypass –
Stay Arming” ). Enable the Quick Arm feature (programming
section [015], option [4]) to have this key function without the
need to enter an access code. If Quick Arm is not enabled, the
user will have to enter an access code before the system will
Away arm.
When the panel is being Away armed, users can restart the exit
delay once, by pressing the Away button before the exit delay
expires. This will not work if the panel is being Stay armed.
“Chime” – (06) Door Chime On / Off
The Door Chime feature will turn ON or OFF. (see “[*][4] Door
Chime On/Off” )
“Reset” – (14) Sensor Reset or [*][7][2]
The panel will activate all PGM outputs programmed as option
[03] Sensor Reset or [20] Command Output Option #2. (See
“[*][7] Command Output Functions”.)
“Exit” – (16) Activate Quick Exit
The panel will activate the Quick Exit feature (see “[*][0] Quick
Exit” )
Additional Function Key Options
The programming of any function key on any keypad may be
changed to one of the options listed below. (See 2.6 “Keypad
Assignment” for instructions on changing function key pro-
gramming.) Each option is listed according to the program-
ming code, followed by the corresponding [*] key command.
For more information regarding each function, please refer to
the appropriate part of Section 3.4, “[*] Commands”.
[00] Null Key: This key is not used and will perform no
function when pressed.
[01] For Future Use
[02] For Future Use
[03] Stay Arm: As described above.
[04] Away Arm: As described above.
[05] [*][9] No Entry Delay Arm: A valid access code
must also be entered.
[06] [*][4] Door Chime On / Off: As described above.
[07] [*][6][----][4] System Test: A valid master code must
also be entered.
[08] [*][1] Bypass Mode: A valid access code may need
to be entered.
[09] [*][2] Trouble Display
[10] [*][3] Alarm Memory
[11] [*][5] Programming Access Codes: A valid master
code must also be entered.
[12] [*][6] User Functions: A valid master code must also
be entered.
[13] [*][7][1] Command Output Option #1: A valid
access code may need to be entered.
[14] [*][7][2] Reset (Command Output Option #2): As
described above.

13
[15] General Voice Prompt Help: This feature can only
be programmed if the Escort5580(TC) and PC5928
audio matrix module or PC5936 audio interface mod-
ule are being used. The intercoms will perform a Help
page. The user must then press the Page/Answer
button on any intercom station to begin the help ses-
sion with the Escort.
[16] [*][0] Quick Exit: As described above.
[17] [*][1] Reactivate Stay/Away Zones
[18] Identified Voice Prompt Help: Can only be pro-
grammed if both the Escort5580 and the PC5928
audio matrix module or PC5936 audio interface mod-
ule are being used. The Escort will begin a Help ses-
sion from the intercom station closest to the keypad.
You must also program PC5928 Section [802], sub-
section [14] “Keypad Port Assignments.”For more
information, please refer to the PC5928/PC5936
Installation Manual.
NOTE: This function key cannot be programmed for PC55XX
LED keypads with software version 1.0.
[19] [*][7][3] Command Output Option #3: A valid
access code may need to be entered.
[20] For Future Use
[21] [*][7][4] Command Output Option #4: A valid
access code may need to be entered.
3.6 Features Available for the LCD5500Z
These features are only available for LCD5500Z keypads with
zone inputs:
Automatic Scrolling of Alarms in Memory
The LCD5500Z keypad allows automatic scrolling through
alarms in memory while the keypad is idle. This feature, if
enabled, will override the clock display. This option can be
programmed in LCD programming section [66], option [4].
24 Hour Time Display Option
The LCD5500Z can be programmed to display time using a
24 hour clock, instead of a 12 hour, clock. This option can be
programmed in LCD programming section [66], option [3].
Keypad Zones
see 2.13“Keypad Zones”
Viewing Troubles While Armed
See “[*][2] Trouble Display” for information on how to view
troubles.
Backlighting Boost
The LCD5500Z, PC55XXZ, PC5502Z2 and LCD5501Z zone
input keypads will provide extra number pad lighting when
any key is pressed. The backlighting boost will last for 30 sec-
onds after the last keypress.

14
Section 4: How to Program
The following section of the manual describes installer pro-
gramming.
NOTE: Read the following section of the manual very carefully
before you begin programming. We also recommend filling out
the Programming Worksheets section before you program the
panel.
For your reference, the corresponding programming sections for
the functions listed are highlighted in text boxes like this one.
4.1 Installer’s Programming
Installer’s Programming is used to program all communicator
and panel options. The Installer’s Code is [5555] by default
but should be changed to prevent unauthorized access to
programming.
Installer’s Code . . . . . . . . . . . . . . . . . . . . . . . . Section [006]
From an LED/Fixed Message LCD Keypad:
1. Enter [*][8][Installer’s Code].
The Program light will flash to indicate that you are in pro-
gramming mode.
The Armed light will turn on to indicate that the panel is
waiting for the three-digit programming section number.
2. Enter the three-digit section number corresponding to the
section you wish to program.
The Armed light will turn off.
The Ready light will turn on to indicate that the panel is
waiting for the information required to complete program-
ming the selected section.
3. Enter the information required to complete section pro-
gramming (i.e.: numbers, HEX data, or ON/OFF options).
NOTE: If the three-digit section number entered is invalid, or if
the module which pertains to the section is not present, the
keypad will sound a two second error tone.
From an LCD Keypad:
1. From any keypad, enter [*][8][Installer’s Code]. The key-
pad will display ‘Enter Section’followed by three dashes.
2. Enter the three-digit number corresponding to the pro-
gramming section number you wish to program. The key-
pad will now display the information required to complete
programming the selected section.
3. Enter the information required to complete section pro-
gramming (i.e., numbers, HEX data, or ON/OFF options).
If you enter information into a section and make a mistake,
press the [#] key to exit the section. Select that section again
and re-enter the information correctly.
NOTE: There must be one digit in each box in the program-
ming section in order for the change to be valid.
4.2 Programming Decimal Data
A set number of programming boxes is allotted for each sec-
tion requiring decimal data (e.g., codes, telephone numbers).
If a digit is entered for each program box, the panel will auto-
matically exit from the selected programming section. The
Ready light will turn OFF and the Armed light will turn ON.
On any keypad, you can also press the [#] key to exit a pro-
gramming section without entering data for every box. This is
handy if you only need to change digits in the first few pro-
gramming boxes. All other digits in the programming section
will remain unchanged.
4.3 Programming HEX Data
On occasion, hexadecimal (HEX) digits may be required. To
program a HEX digit press the [*] key. The panel will enter
HEX programming and Ready light will begin to flash.
The following are the numbers which should be pressed to
enter the appropriate HEX digit:
1 = A 2 = B 3 = C 4 = D 5 = E 6 = F
Once the correct HEX digit has been entered, the Ready light
will continue to flash. If another HEX digit is required, press the
corresponding number. If a decimal digit is required, press the
[*] key again. The Ready light will turn on and the panel will
return to regular decimal programming.
Example:
To enter ‘C1’for a closing by user 1, you would enter:
[*][3][*], [1]:
•[*] to enter Hexadecimal mode (Ready light flashes)
•[3] to enter C
•[*] to return to decimal mode (Ready light is solid)
•[1] to enter digit 1
NOTE: If Ready light is flashing, any number you enter will be
programmed as the HEX equivalent.
If you are using a pulse communications format, a decimal
zero [0] does not transmit. Programming a zero [0] tells the
panel not to send any pulses for that digit. Decimal zero [0] is
a filler digit. To transmit a zero [0], it must be programmed as
a hexadecimal ‘A’.
Example:
For the three digit account number ‘403’, you would enter:
[4], [*][1][*][3], [0]:
•[4] to enter the digit 4
•[*] to enter Hexadecimal mode (Ready light flashes)
•[1] to enter A
•[*] to return to decimal mode (Ready light is solid)
•[3] to enter the digit 3
•[0] to enter the digit 0 as a filler digit.

15
4.4 Programming Toggle Option Sections
Some programming sections contain several toggle options.
The panel will use zone lights 1 through 8 to indicate if the dif-
ferent options are enabled or disabled. Press the number cor-
responding to the option to turn it ON or OFF. Once all the
toggle options have been selected correctly, press the [#] key
to exit the section and save the changes. The Ready light will
turn OFF and the Armed light will turn ON.
Refer to the Programming Worksheets in this manual to deter-
mine what each option represents and whether the light
should be ON or OFF for your application.
4.5 Viewing Programming
LED/Fixed Message LCD Keypads
Any programming section can be viewed from an LED key-
pad. When a programming section is entered, the keypad will
immediately display the first digit of information programmed
in that section.
The keypad displays the information using a binary format,
according to the following chart: See Hex data
entry instructions
Press any of the Emergency keys (Fire, Auxiliary or Panic) to
advance to the next digit. When all the digits in a section have
been viewed, the panel will exit the section; the Ready light
will turn OFF and the Armed light will turn ON, waiting for the
next three-digit programming section number to be entered.
Press the [#] key to exit the section
LCD Keypad
When a programming section is entered, the keypad will
immediately display all the information programmed in that
section. Use the arrow keys (< >) to scroll through the data
being displayed. Scroll past the end of the data displayed or
press the [#] key to exit the section.

16
Section 5: Program Descriptions
The following section explains the operation of all programma-
ble features and options and provides a summary of all corre-
sponding programming locations.
5.1 Programming Security Codes
There are three codes which can be programmed by the
installer in the installer programming function: the Master Code,
the Installer’s Code, and a Maintenance Code. All other access
codes can be programmed through the [*][5] command. (see
“[*][5] Programming Access Codes” )
The master code can also be programmed by the user as
access code (40). If the Master Code Not Changeable option
is enabled, the system master code can only be changed by
the installer.
The maintenance code can only be used to arm and disarm
the system. The maintenance code cannot bypass zones; use
[*][9] to arm the system, cancel auto-arming, or perform [*][7]
command functions. There will be no arm/disarm bell
squawks when the maintenance code is used.
General access codes can arm and disarm the system. When
the Code Required for Bypassing option is enabled, users
will need to enter a valid access code when bypassing zones.
Individual access codes can have the Zone Bypassing
attribute disabled under Access Code Attribute programming.
(see “[*][5] Programming Access Codes” )
If the 6-Digit User Access Codes option is enabled, all the
access codes can be programmed with six digits instead of
four, with the exception of the panel ID code and the down-
loading access code.
Installer’s Code . . . . . . . . . . . . . . . . . . . . . . . . . Section [006]
Master Code . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [007]
Maintenance Code . . . . . . . . . . . . . . . . . . . . . . Section [008]
Master Code Not Changeable . . . . . . . . . .Section [015]: [6]
Code Required for Bypassing . . . . . . . . . .Section [015]: [5]
6-digit User Access Codes . . . . . . . . . . . . .Section [701]: [5]
5.2 Zone Programming
Zones 1-8 are enabled by default. Disable unused zones, or
enable additional zones in programming sections [202] - [205].
The zone definitions describe how each of the zones you use
will operate. Program a two-digit code describing the zone
definition in sections [001] - [004]. Select a definition from the
list below.
In addition, each zone has eight different attributes which can
be programmed in sections [101] to [132]. (see 5.3“Zone
Attributes” )
Zone Definitions
[00] Null Zone
The zone is vacant. Unused zones should be programmed as
Null zones.
[01] Delay 1 Zone
This zone type, normally used for entry/exit doors, can be vio-
lated during the exit delay time without causing an alarm.
Once the exit delay has expired, opening the zone will start
the entry delay timer. During the entry delay time, the keypad
buzzer will sound steadily to advise the user that the system
delay should be disarmed. If the panel is disarmed before the
entry time expires, no alarm will be generated.
[02] Delay 2 Zone
The Delay 2 entry delay time can be set independently of
Delay 1 in programming section [005] (System Times).
[03] Instant Zone
This zone type will cause an instant alarm if it is violated when
the panel is armed. Typically, this zone is used for windows,
patio doors or other perimeter zones, and glassbreak detectors.
[04] Interior Zone
This zone will not cause an alarm if violated during the entry
delay. If the zone is violated before the entry delay has begun,
it will cause an instant alarm. Typically, this zone is used for
interior protection devices, such as motion detectors.
[05] Interior Stay/Away Zone
This zone type works similarly to the Interior zone type, except
that it will be automatically bypassed under the following con-
ditions:
•When the panel is armed in the Stay Mode. (see 3.5“Func-
tion Keys” )
•When the panel is armed without entry delay. (see “[*][9]
Arming Without Entry Delay” )
•When the panel is armed with an access code and a Delay
type zone is NOT tripped during the exit delay.
The automatic bypass prevents the user from having to manu-
ally bypass Interior zones when arming at home. This zone is
typically used for interior protection devices, such as motion
detectors.
[06] Delay Stay/Away Zone
This zone type will operate similarly to Interior Stay/Away
zones, except that it will always provide an entry delay. Typi-
cally, this zone is used for interior protection devices, such as
motion detectors. This zone option will help prevent false
alarms since it always provides an entry delay time for the
user to turn off the panel.
NOTE: Hardwired motion detectors covering entry/exit doors
that are using wireless transmitters must be programmed as
Delay Stay/Away. If not, the panel may see the motion detector
violation before the entry/exit transmitter has time to transmit to
the receiver, causing a false alarm.
[07] Delayed 24 Hour Fire Zone
NOTE: Do not wire Fire zones on keypad zone terminals if the
DEOL supervision option is enabled for the panel (see Pro-
gramming Worksheets, section [013], option [2]).
When this zone is violated, the alarm output will be immedi-
ately activated (pre-alert) but the communicator will be
delayed for 30 seconds. If the user presses any key on any
keypad during this delay, the alarm output and the communi-
cator will be delayed an additional 90 seconds, giving the
user time to correct the problem. If the zone is still violated
after the 90 second delay, the panel will sound the alarm out-
put and delay the communicator for 30 seconds.
If the user does not press a key during the 30 second pre-
alert, the alarm output will latch and the panel will communi-
cate the alarm to the central station. The alarm will sound until
the Bell Cutoff time expires (Section [005] ‘System Times’), or
until a code is entered. (see 5.13“Bell” )
NOTE: If a second fire zone is violated or if the fire keys are
pressed during the delay period, the panel will latch the alarm
output and will immediately communicate the alarm.
Other manuals for Power632
3
Table of contents
Other DSC Control Panel manuals

DSC
DSC Power Series User manual

DSC
DSC Envoy NT9010DMK User manual

DSC
DSC PC1555 CP-01 User manual

DSC
DSC Power Series PC1616 User manual

DSC
DSC PowerSeries PC1616 User manual

DSC
DSC Maxsys PC6010 Owner's manual

DSC
DSC PowerSeries PC1616 User manual

DSC
DSC PowerSeries PC1616 User manual

DSC
DSC PC5020 User manual

DSC
DSC LCD 5500 User manual
Popular Control Panel manuals by other brands

HotSpring
HotSpring IQ 2020 Quick reference guide

CityGrow
CityGrow CG100HHB-SKY user manual

Bosch
Bosch ICP-SOL2-P Quick reference guide

Mitsubishi Heavy Industries
Mitsubishi Heavy Industries SC-SL4-BE3 user manual

Satel
Satel INTEGRA Plus user manual

SJE Rhombus
SJE Rhombus 115 Installation Instructions and Operation