manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. DSC
  6. •
  7. Control Unit
  8. •
  9. DSC PowerSeries Neo V1.2 User manual

DSC PowerSeries Neo V1.2 User manual

Other DSC Control Unit manuals

DSC RXL2-433 User manual

DSC

DSC RXL2-433 User manual

DSC PC5928 User manual

DSC

DSC PC5928 User manual

DSC PC5108 User manual

DSC

DSC PC5108 User manual

DSC PC5200 User manual

DSC

DSC PC5200 User manual

DSC Maxsys PC4937 User manual

DSC

DSC Maxsys PC4937 User manual

DSC PC5700 User manual

DSC

DSC PC5700 User manual

DSC Misterhouse PC5401 User manual

DSC

DSC Misterhouse PC5401 User manual

DSC Maxsys PC4116 User manual

DSC

DSC Maxsys PC4116 User manual

DSC PowerSeries User manual

DSC

DSC PowerSeries User manual

DSC ESCORT558OTC User manual

DSC

DSC ESCORT558OTC User manual

DSC IT-100 User manual

DSC

DSC IT-100 User manual

DSC PC6216 User manual

DSC

DSC PC6216 User manual

DSC MAXSYS PC4851 User manual

DSC

DSC MAXSYS PC4851 User manual

DSC PowerSeries PC585 User manual

DSC

DSC PowerSeries PC585 User manual

DSC PCL422 User manual

DSC

DSC PCL422 User manual

DSC Power 832 User manual

DSC

DSC Power 832 User manual

DSC AMP-704 User manual

DSC

DSC AMP-704 User manual

DSC MAXSYS  PC4850 User manual

DSC

DSC MAXSYS PC4850 User manual

DSC Downlook DLM-7 User manual

DSC

DSC Downlook DLM-7 User manual

DSC Power Series PC5904 User manual

DSC

DSC Power Series PC5904 User manual

DSC PC5400 User manual

DSC

DSC PC5400 User manual

DSC PowerSeries User manual

DSC

DSC PowerSeries User manual

DSC PC6216 User manual

DSC

DSC PC6216 User manual

DSC Misterhouse PC5401 User manual

DSC

DSC Misterhouse PC5401 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Quick Setup
1Plan Plan the installation including all alarm detection devices,
zone expanders, keypads and other required modules.
2Mount Decide on a location for the alarm panel and secure it to the
wall using suitable mounting hardware.
3Wire Complete all wiring including modules, zones, bells/sirens,
telephone line connections and ground connections. Record
module serial numbers on page 19.
4Power Connect the battery and power up the system. The battery
must be connected.
5Enroll
First
Keypad
Hardwired: Wire the keypad to the Corbus, power up the
alarm panel then press any button on the keypad. Wireless:
Wire the HSM2Host to the Corbus, then power up the alarm
panel and a wireless keypad. Press any button on the keypad to
enroll it. The HSM2Host is then enrolled on the alarm panel.
Alternately, enroll an RF keypad.
6Enroll
modules
[*][8][Installer Code][902] subsection [000]. Press [*] to
begin auto-enrollment. Module slots are automatically
assigned. Use scroll keys to view slots. Change slot by typing a
2-digit number.
7Enroll
wireless
devices
[*][8][Installer Code][804] subsection [000]. Note: An
HSM2HOST or RF keypad must be enrolled first.
8Program Basic programming: [*][8][installer code] [001]/[002]> Zone
Type/Zone Attribute [005]>[001] Partition 1 Timers: – Entry
Delay 1 – Entry Delay 2 – Exit Delay [301]>[001] Phone #1
[310]>[000] System Account Code.
9Test Test the panel completely to ensure that all features and
functions operate as programmed. – [901] Walk Test – [904]
[000] Wireless Placement Test.
Compatible Devices
Throughout this document, x in the model number represents the
operating frequency of the device as follows: 9 (912-919 MHz), 8
(868MHz), 4 (433MHz).
Note: Only models operating in the band 912-919 MHz are UL/ULC
listed where indicated. Only UL approved devices are to be used with
UL/ULC listed systems.
Table 1-1 Compatible Devices
Modules
Wireless keypads: HS2LCDWFxUL
HS2LCDWFPxUL
HS2LCDWFPVxUL
Hardwired keypads with 2-way wireless
integration module:
HS2LCDRFxUL
HS2LCDRFPxUL
HS2ICNRFxUL
HS2ICNRFPxUL
Hardwired keypads: HS2LCDUL
HS2LCDPUL
HS2ICNUL
HS2ICNPUL
HS2LEDUL
Touchscreen Keypad HS2TCHP
Note: For ULC-s559 Listed applications the
HS2TCHP touch screen keypad is for
supplementary use only.
2-way wireless integration module: HSM2HOSTxUL
8-zone expander: HSM2108UL
8-output expander: HSM2208UL
Power supply: HSM2300UL
4 high current output expander: HSM2204UL
Alternate communicator: 3G2080UL
3G2080RUL
TL280UL
TL280RUL
TL2803GUL
TL2803GRUL
PCL-422UL
Hardwired Devices
2-wire smoke detectors: FSA-210xUL
FSA-210xTUL
FSA-210xSUL
FSA-210xSTUL
FSA-210xLSTUL
FSA-210xRUL
FSA-210xRTUL
FSA-210xRSUL
FSA-210xRSTUL
FSA-210xLRSTUL
y= A, B, or C
A: ULC listed models
B: UL listed models
C: European and Australian models
4-wire smoke detectors: FSA-410xUL
FSA-410xTUL
FSA-410xSUL
FSA-410xSTUL
FSA-410xLSTUL
FSA-410xRUL
FSA-410xRTUL
FSA-410xRSUL
FSA-410xRSTUL
FSA-410xLRSTUL
y= A, B, or C
A: ULC listed models
B: UL listed models
C: European and Australian models
CO detectors: CO-12/24UL
12-24SIRUL
FW-CO12UL
FW-CO1224UL
CO1224UL
Wireless Devices
Wireless PG smoke detectors PGx926UL
Wireless PG smoke and heat detector PGx916UL
Wireless PG CO detector: PGx913UL
Wireless PG PIR motion detectors: PGx904(P)UL
Wireless PG PIR + camera motion detector PGx934(P)UL
Wireless PG curtain motion detector PGx924UL
Wireless PG dual tech motion detector PGx984(P)
Wireless PG mirror motion detector PGx974(P)UL
Wireless PG outdoor motion detector PGx994UL
Wireless PG glass break detector: PGx912, PGx922
Wireless PG shock detector: PGx935UL
Wireless PG flood detector: PGx985UL
Wireless PG temperature detector (indoor use): PGx905UL
Outdoor temperature probe (requires PGx905) PGTEMP-PROBE
Wireless PG keys: PGx939UL
PGx929UL
Wireless PG panic key PGx938UL
Wireless PG 2-button key PGx949UL
Wireless PG sirens: PGx901UL
PGx911UL
Wireless PG repeater: PGx920UL
Wireless PG door/window contacts: PGx975UL
Wireless PG door/window contact w/ AUX PGx945UL
Central Station Receivers
SG-System I, II, III, IV, 5
Enclosures
PC5003C, PC4050CR (ULC Fire Monitoring), PC4050CAR (UL Commercial Burg), CMC-1(UL
Commercial Burg), PC4051C. Other enclosures are available to suit a variety of system configurations.
WARNING: This manual contains information on limitations regarding product use and function and information on
the limitations as to liability of the manufacturer. The entire manual should be carefully read.
To download the full installation and user manuals and register your product, please visit:
www.DSC.com/m/29009529 or scan the QR code to the right.
PowerSeries Neo V1.2 Alarm Control Installation Guide
PowerSeries Neo Installation Guide
Safety Instructions for Service Personnel
Warning: When using equipment connected to the telephone network, always follow the
basic safety instructions provided with this product. Save these instructions for future
reference. Inform the end-user of the safety precautions that must be observed when
operating this equipment.
Before Installing The Equipment
Ensure your package includes the following items:
lInstallation and User manuals, including the SAFETY INSTRUCTIONS.
READ and SAVE these instructions!
Follow all WARNINGS AND INSTRUCTIONS specified within this
document and/or on the equipment.
lHS2016/HS2016/2032/2064/2128 alarm controller
lPower Supply, direct plug-in
lMounting hardware
Selecting A Suitable Location For The Alarm Controller
Use the following list as a guide to find a suitable location to install this equipment:
lLocate near a telephone socket and power outlet.
lSelect a location free from vibration and shock.
lPlace alarm controller on a flat, stable surface and follow the installation
instructions.
Do NOT locate this product where people may walk on the secondary circuit
cable(s).
Do NOT connect alarm controller to electrical the same circuit as large
appliances.
Do NOT select a location that exposes your alarm controller to direct
sunlight, excessive heat, moisture, vapors, chemicals or dust.
Do NOT install this equipment near water. (e.g., bath tub, kitchen/laundry
sink, wet basement, near a swimming pool).
Do NOT install this equipment and accessories in areas where risk of
explosion exists.
Do NOT connect this equipment to electrical outlets controlled by wall
switches or automatic timers.
AVOID interference sources.
AVOID installing equipment near heaters, air conditioners, ventilators, and
refrigerators.
AVOID locating equipment close to or on top of large metal objects (e.g., wall
studs).
See "Locating Detectors and Escape Plan" on page 20 for information on locating smoke
and CO detectors.
SAFETY Precautions Required During Installation
lNEVER install this equipment and/or telephone wiring during a lightning
storm.
lNEVER touch uninsulated telephone wires or terminals unless the telephone
line has been disconnected at the network interface.
lPosition cables so that accidents can not occur. Connected cables must NOT
be subject to excessive mechanical strain.
lUse only the power supply provided with this equipment. Use of unau-
thorized power supplies may cause damage.
lFor direct plug-in versions, use the transformer supplied with the device.
WARNING: THIS EQUIPMENT HAS NO MAINS ON/OFF SWITCH. THE PLUG OF
THE DIRECT PLUG-IN POWER SUPPLY IS INTENDED TO SERVE AS THE
DISCONNECTING DEVICE IF THE EQUIPMENT MUST BE QUICKLY
DISCONNECTED. IT IS IMPERATIVE THAT ACCESS TO THE MAINS PLUG AND
ASSOCIATED MAINS SOCKET/OUTLET IS NEVER OBSTRUCTED.
IMPORTANT NOTE FORNORTHAMERICA!
This alarm system must be installed and used within an environment that provides the
pollution degree max 2 and over-voltages category II NON-HAZARDOUS
LOCATIONS, indoor only. The equipment is DIRECT PLUG-IN (external transformer)
and is designed to be installed, serviced and/or repaired by service persons only;
[service person is defined as a person having the appropriate technical training and
experience necessary to be aware of hazards to which that person may be exposed in
performing a task and of measures to minimize the risks to that person or other persons].
This equipment has no mains on/off switch; if the equipment must be quickly
disconnected, the plug of the direct plug-in power supply is intended to serve as the
disconnecting device; it is imperative that access to the mains plug and associated mains
socket/outlet, is never obstructed. There are no parts replaceable by the end-user within
this equipment. The wiring (cables) used for installation of the alarm system and
accessories, shall be insulated with PVC, TFE, PTFE, FEP, Neoprene or Polyamide.
(a) The equipment enclosure must be secured to the building structure before operation.
(b) Internal wiring must be routed in a manner that prevents:
- Excessive strain or loosening of wire on terminal connections;
- Damage of conductor insulation
(c) Disposal of used batteries must be made in accordance with local waste recovery and
recycling regulations.
(d) Before servicing, DISCONNECT the power and telephone connection.
(e) DO NOT route any wiring over circuit boards.
(f) The installer is responsible to ensure that a readily accessible disconnect device is
incorporated in the building for permanently connected installations.
The power supply must be Class II, FAIL SAFE with double or reinforced insulation
between the PRIMARY and SECONDARY CIRCUIT/ENCLOSURE and be an approved
type acceptable to the local authorities. All national wiring rules must be observed.
Installation
Mounting the Enclosure
Locate the panel in a dry area, preferably near an unswitched AC power
source and the incoming telephone line. Complete all wiring before
applying AC or connecting the battery.
Terminal Descriptions
The following terminals are available on the PowerSeries Neo alarm
controller.
Terminal Description
BAT+,
BAT-
Battery terminals. Use to provide backup power and additional current
when system demands exceed the power output of the transformer, such
as when the system is in alarm.
Do not connect the battery until all other wiring is complete.
AC Power terminals.
Connect the battery before connecting the AC. Do not connect the battery
or transformer until all other wiring is complete.
AUX+,
AUX-
Auxiliary terminals. Use to power modules, detectors, relays, LEDs, etc.
(700mA MAX). Connect the positive side of device to AUX+, the
negative side to AUX-.
BELL+,
BELL-
Bell/Siren power (700mA MAX). Connect the positive side of any alarm
warning device to BELL+, the negative side to BELL-.
RED, BLK,
YEL, GRN
Corbus terminals. Use to provide communication between the alarm
controller and connected modules. Each module has four Corbus
terminals that must be connected to the Corbus.
PGM1 to
PGM4
Programmable output terminals. Use to activate devices such as LEDs.
(PGM1, PGM3, and PGM4: 50mA PGM2: 300mA or can be configured
as an input)
Z1 to Z8
COM
Zone input terminals. Ideally, each zone should have one detection
device; however, multiple detection devices can be wired to the same
zone.
EGND Earth ground connection.
TIP, RING,
T-1, R-1
Telephone line terminals.
PCLINK_1 DLS/SA
PCLINK_2 DLS/SA, Alternate Communicator
Corbus Wiring
The RED and BLK Corbus terminals are used to provide power while
YEL and GRN are used for data communications. The 4 Corbus terminals
of the alarm controller must be connected to the 4 Corbus terminals or
wires of each module.
The following conditions apply:
lCorbus should be run with minimum 22 gauge quad, two pair
twisted preferred.
lThe modules can be home run to the panel, connected in series or
- 2 -
PowerSeries Neo Installation Guide
can be T-tapped.
lDo not use shielded wire for Corbus wiring.
Note: Any module can be connected anywhere along the Corbus. Separate
wire runs for keypads, zone expanders etc. are not necessary.
Note: No module can be more than 1,000'/305m (in wire length) from the
panel. Do not use shielded wire for Corbus wiring.
Figure 1-1 Corbus Wiring
Module (A) is wired correctly as it is within 1,000'/305m of the panel, in
wire distance. Module (B) is wired correctly as it is within 1,000'/305m of
the panel, in wire distance. Module (C) is NOT wired correctly as it is
farther than 1,000'/305m from the panel.
Current Ratings
In order for the system to operate properly, the power output of the alarm
controller and power supply modules cannot be exceeded. Use the
following data to ensure that the available current is not exceeded.
Table 1-1 System Output Ratings
Device Output Rating (12VDC)
HS2016
HS2032
HS2064
HS2064 E
HS2128
HS2128 E
AUX: 700mA.Subtract the listed rating for each
keypad, expansion module and accessory
connected to AUX or Corbus. At least 100mA
must be reserved for the Corbus.
BELL: 700mA. Continuous rating.
2.0A. short term. Available only with standby
battery connected. Not for UL/ULC or EN
certified applications.
HSM2208 AUX: 250mA. Continuous rating. Subtract for each
device connected. Subtract the total load on this
terminal from the alarm panel AUX/Corbus
output.
HSM2108 AUX: 100mA. Subtract for each device connected.
Subtract the total load on this terminal from the
panel AUX/Corbus output.
Alarm Control Panel
AUX - 700mA available for devices connected to the AUX and PGM
terminals, and modules connected to Corbus terminals. At least 100mA
must be reserved for the Corbus.
Alarm Controller Current Calculation
Panel Calculation
Maximum (Standby or Alarm)
AUX (700mA max. including PGMs 1-4)
Corbus (700mA max.)***
PCLink+ (Alt. Com.:125mA)
Total (must not exceed 700mA)
*** See "Corbus Current Calculation Chart" on page 3.
For UL, ULC and Commercial Listed applications, the total standby and
alarmcurrent cannot exceed 700mA.
Table 1-2 Corbus Current Calculation Chart
Item Current
(mA)
x Quantity Total
(mA)
HS2016/HS2032/HS2064/HS2064
E/HS2128/HS2128 E
85 X 1 85
HS2LCD 105 x
HS2ICN 105 x
HS2LED 105 x
HS2LCDP 105 x
HS2ICNP 105 x
HS2LCDRF 105 x
HS2ICNRF 105 x
HS2ICNRFP 105 x
HS2TCHP 160 x
Current required for connected devices =
HSM2108* 30 x
AUXoutput current of HSM2108
HSM2208* 40 x
AUXoutput current of HSM2208
HSM2300/2204* 35 x
HSM2HOSTx 35 x
HSM2955** x
3G2080(R)/TL2803G(R)/TL280(R) 125
(PCLINK)
x
Total Corbus Current =
*These units draw current from the Corbus to power devices external to
the module. This current must be added to the total Corbus current. See
manufacturer's specifications for the current draw of each device.
** For HSM2955 current draw refer to HSM2955 installation manual.
Capacitance Limits
An increase in capacitance on the Corbus affects data transmission and
causes the system to slow down. Capacitance increases for every foot of
wire added to the Corbus. The capacitance rating of the wire used will
determine the maximum length of the Corbus.
- 3 -
PowerSeries Neo Installation Guide
Table 1-3 Wire Capacitance
Wire Capacitance per 1000’
(300m)
Total Corbus Wire Length
15nF 5300’/1616m
20nF 4000’/1220m
25nF 3200’/976m
30nF 2666’/810m
35nF 2280’/693m
40nF 2000’/608m
AC (UL Listed Installations)
Primary: 120VAC/60Hz./0.33A
Secondary: 16.5VAC/40VA DSC PTD1640U, DSC PTC1640U Class 2
transformer.
Note: Use DSC PTD1640 for Canadian installations.
Warning: Do not connect the battery or transformer until all other
wiring is complete.
For ULC S559 applications, Standex transformer (Model FTC3716) shall
be employed for direct-wiring.
Note: For UL/ULC installations use only 60Hz.
Batteries
Do not connect the battery until all other wiring is complete.
Note: A sealed, rechargeable, lead acid battery or gel type battery is
required to meet UL requirements for power standby times.
Connect the RED battery lead to the positive battery terminal and the
BLACK battery lead to the negative battery terminal.
Note: Refer to "Aux Loading and Battery Selection" on page 23.
Additional Wiring
Zone Wiring
Power down the alarm controller and complete all zone wiring.
Zones can be wired to supervise normally open devices (e.g., smoke
detectors) or normally closed devices (e.g., door contacts). The alarm panel
can also be programmed for single end-of-line or double end-of-line
resistors.
Zone programming is done using the following programming sections:
l[001] selects zone definition
l[013] Opt [1] for normally closed or EOL; Opt [2] for SEOL or
DEOL
l[201 - 208] partition assignment.
Observe the following guidelines when wiring zones:
lFor UL listed installations use SEOL or DEOL only
lMinimum 22 AWG wire, maximum 18 AWG
lDo not use shielded wire
lDo not exceed 100Ωwire resistance. Refer to the following table:
Table 1-4 Burglary Zone Wiring Chart
Wire Gauge Maximum Length to EOL Resistor (ft/-
meters)
22 3000 / 914
20 4900 / 1493
19 6200 / 1889
18 7800 / 2377
Figures are based on maximum wiring resistance of 100Ω.
Aux Power Wiring
These terminals provide 11.3-12.5VDC/700mA of current (shared with
PGM outputs). Connect the positive side of any device to the AUX+
terminal, the negative side to GND. The AUX output is protected; if too
much current is drawn from these terminals (wiring short) the output is
temporarily shut off until the problem is corrected.
Note: If using a 12V, 14Ah battery, maximum AUX capacity for 24-hour
standby is 470mA.
PGM Wiring
Min/max operating voltages for devices, sensors and modules is 9.5VDC
- 14VDC.
PGMs switch to ground when activated from the alarm controller. Connect
the positive side of the device to the AUX+ terminal and the negative side
to a PGM terminal.
PGM 1, 3, 4 supply up to 50mA; PGM 2 supplies up to 300mA.
A relay is required for current levels greater than 50mA or 300mA. PGM2
can also be used for 2-wire smoke detectors, 24-hr burglary input alarm.
Note: Use SEOL resistors on Fire zones only.
Figure 1-2 LED Output with Current Limiting Resistor and
Optional Relay Driver Output.
UL Compatibility ID For FSA-210B Series is: FS200
Note: For ULC listed installations, use FSA-210A and FSA-410A series.
Single End-of-Line (SEOL) Resistor
When SEOL resistors are installed at the end of a zone loop, the alarm
panel detects if the circuit is secure, open, or shorted. The SEOL resistor
must be installed at the end of the loop for proper supervision.
- 4 -
PowerSeries Neo Installation Guide
To enable SEOL supervision, program section [013], options [1] and [2]
to OFF.
Note: This option should be selected if either normally closed or normally
open detection devices or contacts are used.
Figure 1-3 SEOL Wiring
Double End of Line (DEOL) Resistors
When double end-of-line (DEOL) resistors are installed at the end of a
zone loop, the second resistor enables the panel to determine if the zone is
in open, closed, tampered or faulted.
Note: Any zone programmed for Fire or 24-hr Supervisory must be wired
with a SEOL resistor regardless of the type of zone wiring supervision
selected for the panel. If you change the zone supervision options from
DEOL to SEOL or from NC to DEOL, power the system down
completely, then power it back up for correct operation.
To enable DEOL supervision, program section [013], option [1] to OFF
and option [2] to ON.
Figure 1-4 DEOL Wiring
Bell Wiring
These terminals supply 700mA of current at 10.4 - 12.5VDC for
commercial/ residential installations. To comply with NFPA 72 Temporal
Three Pattern requirements, section [013] Opt [8] must be ON. Note that
steady, pulsed alarms are also supported.
Figure 1-5 Bell Wiring
The Bell output is supervised and power limited by 2A thermistor. If
unused, connect a 1000Ωresistor across Bell+ and Bell- to prevent the
panel from displaying a trouble.
Telephone Line Wiring
Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an RJ-
31x connector as indicated in the following diagram. For connection of
multiple devices to the telephone line, wire in the sequence indicated. Use
26 AWG wire minimum for wiring.
Figure 1-6 Telephone Line Wiring
Telephone format is programmed in option [350]. Telephone call
directions are programmed in options [311]- [318].
Ground Wiring
Figure 1-7 Ground Installation
Note: Using an insulated green wire (minimum 22AWG), connect the
EGND terminal on the Corbus and the grounding wire from the building
electrical installation to any of the available holes on the back or side of the
metal cabinet. See the diagram attached to the cabinet for suggested GND
point location and hardware recommendations.
Note: Wire and installation hardware not included.
Enrollment
All optional modules and devices must be enrolled on the system. During
enrollment, the electronic serial number (ESN) of each device is identified
to the control panel and zones are assigned. A wireless transceiver
HSM2HOST or an RF keypad must be enrolled first before wireless
devices can be enrolled.
- 5 -
PowerSeries Neo Installation Guide
Enrolling Modules
During automatic and manual enrollment, if an attempt is made to enroll
more than the maximum number of modules, an error tone sounds and a
message is displayed on LCD keypads.
Table 1-5 Module Capacity
Module HS2016 HS2032 HS2064/
HS2064 E
HS2128/HS2128 E
HSM2108 8 Zone expander 1 3 7 15
HSM2208 8 Output expander 2 4 8 16
Wireless Keypad:
HS2LCDRF(P)4
HS2ICNRF(P)4
HS2LCDWF(P)(V)4
8 8 8 16
HS2TCHP Touchscreen
Keypad
8 8 8 16
HSM2300 Power Supply 1A 3 3 3 4
HSM2204 4 High-current
Output
1 1 3 4
HSM2HOSTx Transceiver 1 1 1 1
HSM2955
(not UL evaluated)
1 1 1 1
Modules can be enrolled automatically or manually using section [902] of
Installer programming.
To confirm that a module has been successfully enrolled, use Installer
Programming section [903].
Enroll Wireless Devices
Wireless devices are enrolled via the wireless transceiver module and
Installer Programming section [804][000].
Auto Enrollment
To enroll a wireless device using this method, press and hold the Enroll
button on the device for 2-5 seconds until the LED lights then release the
button. The alarm panel automatically recognizes the device and the keypad
displays a confirmation message. The device ID and next available zone
number are displayed. Press [*] to accept or scroll to another available
zone number. Batteries must be installed in the wireless device in order to
enroll.
Pre-Enrollment
Pre-enrollment is a two step process. The first step requires entering each
device ID ([804][001]-[716]). Every wireless device has an ID printed on
the sticker attached to the device. The format is XXX-YYYY where:
lXXX identifies the type or model of the device
lYYYY is a short encrypted ID used by the system to identify the
specific device
Pre-enrollment can be done at a remote location and using DLS/SA. The
second step is to press the enrollment button on the device, usually done
on location. Installer Programming does not have to be entered at this step.
Both steps must be performed in order to complete the enrollment.
Programming Methods
The alarm system can be programmed using the following methods:
Table 1-6 Programming Methods
Method Description Procedure
Template
programming
Use pre-defined templates to
quickly apply basic programming
and to set up DLS downloading.
Press [899] at the
“Enter Section”
screen.
See Template
Programming below
for details.
DLS
programming
Download and apply programming
using DLS 5 v1.3 for Neo v1.0
panels and DLS 5 v1.4+ for Neo
v1.0 and up products.
For local DLS, use a
PC-Link cable and
laptop with DLS-5
software installed.
For remote DLS, use
a telephone line,
cellular network or the
Internet.
Installer
programming
Manually program all alarm system
and device options.
Press [*][8][installer
code] while the
system is disarmed.
Viewing Programming
Programming sections can be viewed from any system keypad. The
method for viewing and selecting programming options using LCD, LED
and ICON keypads depends on the keypad type used. See below for
specific instructions on programming with each keypad type.
Generally, programming options are accessed in the following way:
1. Enter Installer Programming mode ([*][8]).
2. Navigate to a specific programming section.
3. Select an option to view or change its programming.
All programming options are numbered and can be accessed by navigating
through the menu (LCD) or by keying in the program section number. For
toggle options, the name of the option is displayed (LCD) or LEDs 1-8 are
illuminated (LED and ICON).
Use the keypad numbers to toggle options on or off. Sections requiring
data input, such as phone numbers, display the full data in fields up to 32
characters long (LCD). To input data, use the scroll keys to select a
character then press the keypad button corresponding to the number/letter
required. Scroll to the next character and repeat the procedure as needed.
Press the [#] key to save changes and exit the program section.
Minimum Required Programming
Once basic installation of the alarm panel is complete, the following
general configuration options can be set.
[000] Language Selection
(LCD keypads only)
- 6 -
PowerSeries Neo Installation Guide
Use this section to set the language displayed by LCD keypads. To select a
language:
1. Enter Installer Programming: [*][8][Installer Code].
2. Enter programming section [000]>[000].
3. Key in the 2-digit number corresponding to the language required. See
below:
01 = English 11 = Swedish 22 = Bulgarian
02 = Spanish 12 = Norwegian 23 = Latvian
03 = Portuguese 13 = Danish 24 = Lithuanian
04 = French 14 = Hebrew 25 = Ukrainian
05 = Italian 15 = Greek 26 = Slovakian
06 = Dutch 16 = Turkish 27 = Serbian
07 = Polish 18 = Croatian 28 = Estonian
08 = Czech 19 = Hungarian 29 = Slovenian
09 = Finnish 20 = Romanian
10 = German 21 = Russian
Time and Date
Use this section to program the alarm system clock.
Menu: [*][6][Master Code] > Time and Date
Keypad: [*][6][Master Code] + 01
Enter time and date using the following format: (HH:MM); (MM-DD-
YY). Valid time entries are 00-23 hours, 00-59 minutes. Valid date entries
are 01-12 months, 01-31 days.
Setting Up a Partition
Partitions are added or removed from the system by applying or removing
a partition mask via Installer Programming section [200]. The number of
available partitions depends on the alarm panel model.
Bell/Siren Operation
Each partition must have a siren. The system siren connected to the bell
output of the alarm controller can be mounted in a central location within
hearing range of all partitions. Each partition can also have wireless sirens
activated only on the assigned partition.
Keypad Partition Setup
Keypads can be configured to control an individual partition or all
partitions. In general, a partition keypad controls the partition it is assigned
to. A Global keypad controls all partitions. Global keypads should be
placed in common areas of the premises, such as points of entry or
reception areas, where the ability to arm and disarm more than one
partition at a time is required.
Partition keypads can also be temporarily loaned to other partitions.
To select a keypad operating mode:
1. Enter Installer Programming: [*][8][installer code].
2. Select [861]-[876] to program keypads 1-16.
lPress [000] for partition assignment.
lFor Global operation, key in 00.
lTo assign a keypad to a partition, key in 01-08 for partition 1-8.
3. Press the [#] and reapeat step 2 for next keypad. When finished
programming all keypads, press the [#] key twice to exit
programming.
Users are assigned partition access rights via the [*][5] menu.
Assign sirens to partitions:
[804]>[000]>[551]-[556]>[000]
Set up partition account codes:
[310]>[001]-[008]
Set up partition timers:
lEntry/exit delay, settle delay – [005]>[001]-[008]
lAutomatic arming/disarming schedule – [151]-[158]>[001]/[002]
lAuto disarming holiday schedule – [151]-[158]>[003]
lNo activity arming – [151]-[158]>[006]
lAutomatic clock adjust – [005]>[000], option 6
lDelay between dialing attempts – [377]>[012]
Assign Zone Types
A zone type defines how a zone operates within the system and how it
responds when triggered.
000 - Null Zone 040 - 24-Hour Gas
001 - Delay 1 041 - 24-Hour CO
002 - Delay 2 042 - 24-Hour Holdup*
003 - Instant 043 - 24-Hour Panic
004 - Interior 045 - 24-Hour Heat
005 - Interior Stay/Away 046 - 24-Hour Medical*
006 - Delay Stay/Away 047 - 24-Hour Emergency
007 - Delayed 24-Hour Fire 048 - 24-Hour Sprinkler*
008 - Standard 24-Hour Fire 049 - 24-Hour Flood
009 - Instant Stay/Away 051 - 24-Hour Latching Tamper
010 - Interior Delay 052 - 24-Hour Non-Alarm
011 - Day Zone 056 - 24-Hour High Temperature
012 - Night Zone 057 - 24 Hour Low Temperature
016 - Final Door Set 060 - 24-Hour Non-Latching Tamper
017 - 24-Hour Burglary 066 - Momentary Keyswitch Arm
018 - 24-Hour Bell/Buzzer 067 - Maintained Keyswitch Arm
023 - 24-Hour Supervisory 068 - Momentary Keyswitch Disarm
024 - 24-Hour Supervisory Buzzer 069 - Maintained Keyswitch Disarm
025 - Auto Verified Fire 071 - Door Bell
027 - Fire Supervisory 072 - Push to Set
* Not UL evaluated
Assign zone attributes:
[002]>[001]-[128]>Select one of the following zone attributes:
1 – Bell Audible
2 – Bell Steady
3 – Chime Function
4 – Bypass Enabled
- 7 -
PowerSeries Neo Installation Guide
5 – Force Arm
6 – Swinger Shutdown
7 – Transmission Delay
8 – Burglary Verification
9 – Normally Closed EOL
10 – Single EOL
11 – Double EOL
12 – Fast/Normal Loop Response
13 – Zone 2-way Audio Activation
14 – Hold Up Verification
Create labels:
[000]>[001]-[821] 2 x 14 ASCII characters.
Add access codes:
To program an access code: [006] then one of the following:
[001] – Installer code
[002] – Master code
[003] – Maintenance code
Access codes are either 4, 6 or 8 digits in length, depending on the setting
of programming section [041]. Duplicate codes are not valid.
Alternate Communicator Setup
The alternate communicator is an optional wireless or ethernet
communications device that can be used as a backup to the PSTN
connection or as a primary means of communication between the alarm
panel and the central monitoring station. The alternate communicator
communicates via 3G (HSPA) or Ethernet.
The following configuration steps are required to set up the alternate
communicator:
lInstall the alternate communicator and wire it to the alarm panel
(use PCLINK_2 header)
lEnroll the alternate cellular communicator with Connect 24
lSet the communication path: [300]
lEnable the alternate communicator: [382] option 5
lEnable event reporting: [307]/[308]
lProgram communication delay timer: [377]
lProgram DLS access: [401] option 07
Refer to the 3G2080(R)/ TL2803G(R)/ TL280(R) installation manual for
details.
[300] Panel/Receiver Communication Paths
This section is used to select the path of communications between the
alarm system and the central station.
To use PSTN as the communications path, program section [300] options
001 through 004 as [01] PSTN 1.
To use the alternate communicator to establish a communications path,
program two of the receivers (section [300] options 001, 002, 003 or 004)
as [03] and [04] for Ethernet, and two of the receivers as [05] and [06] for
cellular.
Testing the System
Installer Walk Test
Walk test enables the installer to test the operation of each detector by
tripping zones, causing an actual alarm. Enter section [901] to initiate a
walk test. When a zone is tripped, all system sirens emit a tone to indicate
that the zone is working correctly.
After 15 minutes without zone activity, the walk test terminates
automatically. To manually exit walk test mode, enter [901] again.
Viewing the Event Buffer
The event buffer contains logs of events that have occurred on the alarm
system beginning with the most recent. The capacity of the event buffer is
scalable and can hold 500/1000 events (depending on panel model) before
rolling over. The buffer displays events according to their time stamp,
beginning with the most recent. The event buffer can be uploaded using
DLS.
Each event displays the time and date, a description of the event, the zone
label, access code number or any other pertinent information. To view the
event buffer, press [*][6][Master Code][*].
Troubleshooting
LCD programmable-message keypad:
lPress [*][2] followed by access code if required to view a trouble
condition
lThe trouble light flashes and the LCD displays the first trouble
condition
lUse the arrow keys to scroll through all trouble conditions present
on the system
Note: When additional information is available for a specific trouble
condition, a [*] is displayed. Press the [*] key to view the additional
information.
LED and ICON keypads:
lPress [*][2] to view a trouble condition
lThe trouble light flashes
lRefer to the trouble summary list below to determine the trouble
condition(s) present on the system
[*][2] Trouble Display
This feature is used to view system troubles. If a trouble is present, the
keypad Trouble indicator illuminates and an audible indication is emitted
(two short beeps every 10 seconds, except while in AC failure). Silence
the audible indicator by pressing [#].
Troubles may be viewed while the system is armed or disarmed. The
system may be programmed to show all troubles while armed or only fire
troubles.
The system can be configured to require a user code to view [*][2] system
troubles. See section [023] option 5.
- 8 -
PowerSeries Neo Installation Guide
To view trouble conditions:
lPress [*][2] to enter the Trouble menu.
lOn an LCD keypad, scroll to a trouble type then press [*] to view
the specific trouble. The zone name and trouble condition for each
trouble are displayed on the screen.
lOn LED/ICON keypads, zone indicator lights illuminate to
identify existing trouble types (e.g., Zone light 1 represents Ser-
vice Required trouble type). Press the number key corresponding
to a zone light to view the specific trouble. Lights 1-12 illuminate
to indicate the trouble as follows:
Table 1-7 : Trouble Indications
Trouble 01 –Service Required:
[01] Bell Circuit Trouble: The bell circuit is open.
[02] RF Jam: The HSM2HOSTx has detected an RF Jam condition.
[03] Aux Supply Trouble: The alarm controller, HSM2204 or HSM2300 has an
overcurrent condition on Aux.
[04] Loss of Clock: System time and date require programming.
[05] Output 1 Fault: An HSM2204 module has detected an open condition on output
#1.
Trouble 02 – Battery Trouble:
[01] Panel Low Battery Trouble: The battery voltage (under load) is below 11.5V.
Restores at 12.5V.
[02] Panel No Battery: No battery connected to alarm controller.
[04] HSM2204 01 - 04 Low Battery: An HSM2204 has a battery voltage less than
11.5V.
[05] HSM2204 01 - 04 No Battery: No battery connected to HSM2204.
[07] HSM2300 01 - 04 Low Battery: An HSM2300 has a battery voltage less than
11.5V
[08] HSM2300 01 - 04 No Battery: No battery connected to HSM2300.
Trouble 03 – Bus Voltage:
[01] HSM2HOSTx Bus Low Voltage: The HSM2HOSTx module has measured less
than 6.3V on its Aux input.
[02] Keypad 01 - 16 Bus Low Voltage: A hardwired keypad has a bus voltage of less
than 6.9V for ICON/LCD (RF version) and 7.7V for non-RF models.
[04] HSM2108 01 - 15 Bus Low Voltage: A zone expander has a bus voltage of less
than 5.9V.
[05] HSM2300 01 - 04 Bus Low Voltage: A power supply has a bus voltage of less
than 6.9V.
[06] HSM2204 01 - 04 Bus Low Voltage: A high current output module has a bus
voltage of less than 6.9V.
[08] HSM2208 01 - 16 Bus Low Voltage: The low current output module has detected
a voltage less than 5.9V on its aux input.
[09] HSM2955 Bus Low Voltage: The audio module has detected a voltage less than
9.65V on its aux input.
Trouble 04 – AC Troubles:
[01] Zone 001 - 128 AC Trouble: An AC trouble has been detected on a PGX934 PIR
+ Camera.
[03] Siren 01 - 16 AC: A siren has an AC trouble.
[04] Repeater 01 - 08 AC: A wireless repeater has an AC trouble.
[05] HSM2300 01 - 04 AC: An HSM2300 has an AC trouble.
[06] HSM2204 01 - 04 AC: An HSM2204 has an AC trouble.
[07] Panel AC: The alarm controller has an AC failure condition.
Trouble 05 – Device Faults:
[01] Zone 001 - 128: A zone is in fault. Additional information displayed on LCD
keypads for the following troubles: Fire Trouble (2-W Smoke, PGX916, PGX926),
Freeze (PGX905), Self Test (PGX984), CO (PGX913), and Probe Disconnected
(PGX905). Also generated by a short on hardwired zones when DEOL is used or by a
wireless supervisory fault.
[02] Keypad 01 - 16: A wireless or hardwired keypad is in fault.
[03] Siren 01 - 16: A siren is in fault.
[04] Repeater 01 - 08: A wireless repeater is in fault (supervisory or loss of AC/DC).
Trouble 06 – Device Low Battery:
[01] Zone 001- 128: Wireless zone has a low battery.
[02] Keypad 01-16: Keypad has a low battery.
[03] Siren 01 - 16: Siren has a low battery.
[04] Repeater 01 - 08: Repeater has a low battery.
[05] User 01 - 1000: Wireless Key has a low battery.
Trouble 07 – Device Tampers:
[01] Zone 001 - 128 Tamper: A wireless or hardwired zone configured for DEOL
operation is in tamper.
[02] Keypad 01 - 16 Tamper: A hardwired or wireless keypad is in tamper.
[03] Siren 01 - 16 Tamper: A wireless siren is in tamper.
[04] Repeater 01 - 08 Tamper: A wireless repeater is in tamper.
[05] Audio Station 01 - 04 Tamper: An audio station connected to an HSM2955 is in
tamper.
Trouble 08 – RF Delinquency Trouble:
[01] Zone 001 - 128 RF Delinquency: No response from a wireless zone for 13
minutes. This trouble prevents arming until acknowledged or cleared using [*][2].
[02] Keypad 01 - 16 RF Delinquency: No response from a wireless keypad for 13
minutes.
[03] Siren 01 - 16 RF Delinquency: No response from a wireless siren for 13 minutes.
[04] Repeater 01 - 16 RF Delinquency: No response from a wireless repeater for 13
minutes.
Trouble 09 – Module Supervisory Trouble:
[01] HSM2HOSTx not responding.
[02] Keypad 01 - 16 not responding.
[04] HSM2108 01 - 15 not responding.
[05] HSM2300 01 - 04 not responding.
[06] HSM2204 01 - 04 not responding.
[08] HSM2208 01 - 16 not responding.
[09] HSM2955 is not responding.
- 9 -
PowerSeries Neo Installation Guide
Trouble 10 – Module Tamper:
[01] HSM2HOSTx Tamper.
[02] Keypad 01 - 16 Tamper.
[04] HSM2108 01 - 15 Tamper.
[05] HSM2300 01 - 04 Tamper.
[06] HSM2204 01 - 04 Tamper.
[08] HSM2208 01 - 16 Tamper.
[09] HSM2955 Tamper
Trouble 11 – Communications:
[01] TLM: Telephone line disconnected from control panel.
[02] Receiver 01-04 FTC Trouble: Failure to communicate using programmed receiver
paths.
[03] Alt. Comm SIM Lock: SIM card has incorrect or unrecognized PIN.
[04] Alt. Comm Cellular: Radio or SIM card failure, low signal strength detected, or
cellular network fault.
[05] Alt. Comm Ethernet: Ethernet connection unavailable. A valid IP address is either
not programmed or the module was unable to get an IP with DHCP.
[06] Receiver 01-04 Absent: Alternate communicator unable to initialize a receiver.
[07] Receiver 01-04 Supervision: Alternate communicator unable to communicate with
a receiver.
[09] Alt. Comm Fault: The alternate communicator has stopped responding.
[10] Alt Comm FTC Trouble: The alternate communicator has failed to communicate
an internal event not generated by the panel.
Trouble 12 – Not Networked Troubles:
[01] Zone 001-128 Not Networked Trouble: Generated when a zone becomes out of
sync with the wireless network or has not been synchronized with the network after
enrollment.
[02] Keypad 01-16 Not Networked Trouble: Generated when a keypad becomes out of
sync with the wireless network or has not been synchronized with the network after
enrollment.
[03] Siren 01-16 Not Networked Trouble: Generated when a siren becomes out of sync
with the wireless network or has not been synchronized with the network after
enrollment.
[04] Repeater 01-08 Not Networked Trouble: Generated when a repeater becomes out
of sync with the wireless network or has not been synchronized with the network after
enrollment.
[05] User 01 - 1000 Not Networked Trouble: Generated when a wireless key becomes
out of sync with the wireless network or has not been synchronized with the network
after enrollment.
IMPORTANT!
Ensure you have the following information available before contacting
Customer Support :
lAlarm controller type and version, (e.g., HSM2064 1.0):
Note: Version number can be accessed by entering [*][Installer Code]
[900] on any LCD keypad. This information is also located on a sticker on
the printed circuit board.
lList of modules connected to control panel, (e.g., HSM2108,
HSM2HOSTx etc.) .
Specifications
Zone Configuration
l16, 32, 64, or 128 wireless zones supported and up to 8 hard-
wired zones available on the controller
l40 zone types and 14 programmable zone attributes
lZone configurations available: normally closed, single EOL and
DEOL supervised
lHardwired zone expansion (fully supervised) available using the
model HSM2108 (eight zone expander module)
lWireless zone expansion (fully supervised) available using the
HSM2Host 2-way wireless integration module (operating at
915MHz (North America), 433MHz (Europe) and 868MHz (inter-
national)
Access Codes
lUp to 1002 access codes: 1000 (level 2-EN), one installer code
(level 3-EN), and one maintenance code
lProgrammable attributes for each user code (see "Access Code
Attributes" on page 1)
lWhen using 8-digit access codes, the minimum number of vari-
ations are:
HS2016
HS2032: 1388888
HS2064/HS2128: 1052631
HS2064 E: 200000
HS2128 E: 100000
Warning Device Output
lIntegral sounder capable of 85 dB @ 3m, self-powered type Z
l2 remote, wireless indoor/outdoor warning devices supported:
models PGX901 (indoor), PGX911 (outdoor) (X=4, 8, or 9)
lProgrammable as steady, pulsed or temporal three (as per
ISO8201) and temporal four (CO alarm) output
lWarning device sounds alarms in the following priority: fire, CO,
burg
Memory
lCMOS EEPROM memory
lRetains programming and system status on AC or battery failure
for 20 years min. (not verified by UL)
Power Supply - North America
Transformer: DSC PTD1640U, PTD1640
Primary: 120V, 60Hz Class II
Secondary: 16.5VAC, 40VA Max.
Power Supply - International
lInput ratings: 220V-240Vac, 50/60Hz, 200mA
lTransformer required, mounted in the same enclosure,
permanently connected
lTransformer secondary ratings: 16.5Vac, 40VA min.
Note: For installations using the transformer mounted inside the cabinet,
replace fuse only with the same type (20mm) rated 250V/315mA.
Regulated power supply:
l1.7A regulated, supervised and integral to the control unit
lType A as per EN50131-6 Standard
l700mA auxiliary supply, 12V DC
lPositive temperature coefficient (PTC) for Bell, Aux+ and Battery
terminals
lReverse battery detection/protection
lSupervision for AC power and low battery
- 10 -