Dynamatic 4000 User manual

1
Instruction Sheet
IS-539-15 revised 2019
15-533-1015 Panel Mount 4000 (4.3 A Controller)
15-551-1015 Standard Enclosure 4000 (4.3 A Controller)
15-539-0015 Panel Mount 4050 (8 A Controller)
15-553-0015 Standard Enclosure 4050 (8 A Controller)
Model 4000 and 4050 with Torque Limit and Jog at Run Speed
Introduction
These instructions relate specifically to
the model 4000 and 4050 controllers
assembled for Speed Control with
Torque Limit and Jog at Run Speed
modification. Connection diagram,
schematic diagram, switch
programming, plug wiring connection,
adjustment procedure and
recommended spare parts list for these
specific assemblies are contained in
this Instruction Sheet. Any differences
between these two controllers are
clearly noted. Use Instruction Manual
IM-130006-83XX with this Instruction
Sheet for complete installation,
operation and maintenance
instructions.
Caution: Above ground electrical
potentials scan be hazardous. Always
disconnect electrical power before
working on the controller.
*Heat sink assembly, HS1, and its
wiring are only supplied on 4050
controls. The parts are mounted on the
15-530-5 main 4000 boards.
Drive Source International/Dynamatic
7900 Durand Ave Bldg 3 Sturtevant, WI 53177
www.Dynamatic.com

2
INTRODUCTION.................................................................................................................... 1
Connection diagram for Standard Enclosure 4000 Controller................................................................3
Schematic Diagram for 4000 Controller .................................................................................................4
Connection Diagram for 4000 Panel Mount and 4050 Controllers ........................................................5
Schematic Diagram for 4050 Controller .................................................................................................6
Low Signal Follower Modification PCB 15-444-2 ....................................................................................6
MODIFICATION PCB MOUNTING.......................................................................................... 7
GENERAL DESCRIPTION........................................................................................................ 7
Preliminary Adjustments.......................................................................................................................... 7
Operator Controls .......................................................................................................................................7
Main PCB 15-530-5 or 15-530-6..................................................................................................................7
Trimpot Illustration:................................................................................................................................8
Torque Limit ................................................................................................................................................8
Adjustment Procedure ............................................................................................................................. 9
Zero Adjust R19 with LED monitor..............................................................................................................9
Zero Adjust R19, Alternate Method .......................................................................................................9
Max Speed/Volts R21- ................................................................................................................................9
Max Speed/Volts R21 with LED monitor ................................................................................................9
Max Speed/volts R21, Alternate Methods ...........................................................................................10
Time Constant (TC) Adjust R26 .................................................................................................................10
Current Feedback R20*- ...........................................................................................................................10
Accel Rate R18- .........................................................................................................................................11
Velocity Damping R22*-............................................................................................................................11
HI Damping R20- .......................................................................................................................................11
Torque Limit PCB 15-444-2 .......................................................................................................................11
Torque Limit PCB 15-444-2 .......................................................................................................................12
Jog at Run Speed-......................................................................................................................................12
Renewal Parts List .................................................................................................................................. 13

3
Connection diagram for Standard Enclosure 4000 Controller
ED-58215

4
Schematic Diagram for 4000 Controller

5
Connection Diagram for 4000 Panel Mount and 4050 Controllers
ED-56815

6
Schematic Diagram for 4050 Controller
Torque Limit Modification PCB 15-444-2

7
Modification PCB Mounting
If you have purchased a complete controller this section may be passed over and you may proceed to
General Description.
1. Place the Main PCB in front of you with the long dimension in a horizontal position and the
terminal strip to the left.
2. Remove the DIP switch by pulling it straight out of the receptacle, RECP 1. Then, peel the adhesive-
backed label off the other half of RECP 1.
3. Insert the arrow-type locking head of the four nylon stand-offs supplied into the four 0.188”
diameter holes in the main PCB and press in. The tabs will snap out to lock the stand-offs
permanently in position.
4. Hold the modification PCB assembly over the stand-offs with the ribbon connector toward you
and insert the ribbon connector plug into RECP 1. Be careful to see that all 16 pins are started
properly into the receptacle before pressing the plug in.
5. Align the holes in the modification PCB assembly over the stand-offs and press over the tapered
posts until the locking flanges snap out to lock the board in position.
General Description
For some variable speed drive applications, it is necessary to limit the torque available to a machine in
order to prevent damage to the machine itself or its process. The Torque Limit modification provides and
“override” feedback signal which indirectly limits the induction motor torque (current) to a preset
maximum value. This limit can be used to prevent the motor breakover torque from being reached during
a condition such as drive output shaft ‘lock-up” or the period when a large system inertia is being
accelerated. The adjustment range is from 50 to 150% of rated motor torque.
Preliminary Adjustments
Perform the following preliminary adjustments (which no power applied to the controller)
1. Operator Controls (supplied by customer unless specified)
a. Set the Run Speed potentiometer R5 to 0% (Full CCW)
b. Set the Jog/Run selector switch to the Run position
c. Note location of Start and Stop pushbuttons
2. Main PCB 15-530-5 or 15-530-6
The pots used are screwdriver adjust, single turn pots. Do not use a screwdriver with a blade width
exceeding 1/8” in width.
a. Set the Accel Rate potentiometer R18 to 100% (Full CW)
b. Set the Zero Adjust potentiometer R19 to 0% (Full CCW)
c. Set the Max Speed/Volts potentiometer R21 to 0% (Full CCW)
d. Set the Velocity Damping potentiometer R22 as follows (see trimpot illustration):
e. Set the Time Constant (TC) Adjust potentiometer R26 as follows (see trimpot illustration):

8
Mechanical Unit Model Numbers
Velocity
Damping
Setting
AC/ACW/ACS/PD/VT
Fractional Hp (FHP)
AS/AT/AE/VT/EC
Fractional Hp
14/112/140
0%
181/182/184/186
18/21/132/160/180/210
50%
214/216/254/256
25/27/180/225/250/280
75%
280/320/360/440
320/360/440
75%
Mechanical Unit Model Numbers
TC Adjust
Setting
AC/ACW/ACS/PD/VT Fractional
Hp (FHP)
AS/AT/AE/VT/EC
FHP/181/182
0%
184/186/214
14/18/112/132/140/180
15%
216/254/256/280
21/160/210
30%
320/360/440
25/24/180/225/250/280
320/360/440
100%
*Typical product number stamped on mechanical unit nameplate:
1. A1-100214-0053, specific mechanical model is AC-214
2. B2-100210-0008, specific mechanical model is AS-21
Trimpot Illustration:
3. Torque Limit Mod PCB 15-444-2
a. Set the Torque Limit Damping potentiometer R18 at 50% CW
b. Set the Torque Limit potentiometer R19 at 50% CW (this setting is approximately 150% of
rated motor torque)
c. Set HI Damping potentiometer R20 to 0% (Full CCW)

9
d. Check the drive nameplate for motor hp, voltage and current ratings. Set the programming
switches as indicated in Table 1 on the connection diagram for your rated motor current.
4. Place a clamp-on ammeter on one lead of the ac motor
Adjustment Procedure
Caution: To avoid personal injury or damage to the test equipment remove power before connecting or
disconnecting test equipment.
The Model 4000 and 4050 controllers contain an LED status monitor which provides a visual means of
setting the maximum speed and zero adjust. This LED set up along with an alternate method is given
below.
1. Turn ON the power to the drive and start the ac motor
2. Start the controller with the Start pushbutton. Note the location of the Stop pushbutton
3. Zero Adjust R19 with LED monitor- Slowly increase the Zero Adjust Potentiometer R19 CW
while monitoring the LED, D22. When controller output is turned on or clutch voltage is turned
ON (or the drive shaft begins to rotate), the LED should start flashing. Now just back off slowly
until the flashing stops.
Zero Adjust R19, Alternate Method- This adjustment can be set to provide zero rpm or some
minimum speed greater than zero, as required by the machine operating requirements.
a. For zero rpm, turn the Zero Adjust potentiometer R19 CW until the output shaft just begins
to turn. Then, back off on the control until the output shaft just stops turning. Stop and start
the controller a few times to be sure the drive shaft does not rotate.
b. For a minimum speed greater than zero, the LED cannot be used. Turn the Zero Adjust
potentiometer CW until the desired speed is attained. For an accurate setting use a
tachometer or stroboscope.
4. Max Speed/Volts R21-This adjustment can be set to limit drive speed to its rated maximum or
to a slower speed as required by the machine process. An LED status monitor has been provided
on the main board to allow you to set the maximum speed the tachometer or stroboscope will
give an accurate rpm setting while the use of a voltmeter will give only an approximate speed
setting. This is because the voltmeter is measuring generator voltage instead of actual output
rpm.
Max Speed/Volts R21 with LED monitor Set the Run Speed potentiometer R5 at 100%, (Full CW).
The drive should be loaded for best results. Set the Max Speed/Volts potentiometer R21 at 100%
(Full CW). Caution: drive will go to top speed. The LED should be out when the drive is at top
speed. With the LED out, slowly turn the Max Speed/Volts potentiometer R21 CCW until the LED
lights. This indicates that the speed of the drive is in the regulating range of the controller. The
clutch voltage should drop below 45V. This will be approximately the maximum rated speed of
the drive. The maximum speed point setting will vary with different mechanical units.

10
There are two other conditions for which the LED will be out besides the drive being set for zero
speed or running wide open above the regulating range. These are whenever the “E” relay is
deenergized (the drive is stopped), or due to a wiring error, ground or some malfunction of the
controller itself.
Max Speed/volts R21, Alternate Methods
a. To set maximum rated speed with a tach or stroboscope: turn the Run Speed potentiometer
R5 to 100% (full CW) Allow the drive to accelerate to full speed, turn the Max Speed/Volts pot
CW until the rated speed indicated is the same as the speed listed on the nameplate of the
mechanical unit.
b. To set approximate maximum speed with a voltmeter, connect a voltmeter (60 Vac scale
across terminals G1 and G2. Turn the Run Speed pot R5 to 100% (Full CW) Allow the drive to
accelerate to full speed. With the drive at full speed, turn the Max Speed/Volts pot CW until
the meter reading ceases to rise. Back off the adjustment (CCW) until the meter reading just
begins to drop. This is the point of maximum speed.
c. To set a maximum speed that is less than rated maximum speed requires the use of a
tachometer or stroboscope indicator. This cannot be accomplished with the LED status
monitor. Turn the Run Speed potentiometer to 100% (Full CW). Allow the drive to accelerate
to full speed, slowly increase Max Speed/Volts potentiometer setting CW until the desired
speed is indicated.
5. Since there may be some interaction between the Zero Adjust and the Max Speed/Volts,
particularly if the minimum speed is other than zero, repeat steps 3 and 4 until the desired speeds
are obtained for both the zero and max positions of the Run Speed pot.
6. Time Constant (TC) Adjust R26- The TC adjust is used to set current feedback by using coil
voltage and a variable RC combination to simulate the different coil time constants of various size
drives. A trimpot illustration is provided to facilitate the setting of this control. Sufficient range
has been provided for drive size from fractional through 20 hp for the 4000 controller and up to
125 hp for the 4050 controller. Set you TC control appropriately for your individual drive size as
shown in Preliminary Adjustments.
Setting are not critical and so may be ‘tuned” for each drive. High inertia applications can benefit
from a higher than normal setting.
7. Current Feedback R20*-Normal operation will not require use f this potentiometer. Certain
applications are best met with a negative current feedback response which is slower in settling
and less likely to overshoot at low rpms. There are some low inertia, light load, linear acceleration
applications that may also benefit from improved low-end linearity with current feedback
damping. If you have one of these applications, remove jumper J1 from the Normal position and
place it in the increased position. Adjust Current Feedback R20 as required to obtain desired drive
response.
*See Basic 4000/4050 manual for a more detailed description of this adjustment.

11
8. Accel Rate R18-The purpose of Linear Acceleration is to slow down drive response to an increase
in command. Without Linear Accel control, the drive will respond to operator speed adjustments
very quickly, limited only by the torque capacity of the drive. With the Linear Accel circuit, the
output of the controller is linear with respect to time. This circuit is adjustable from 3 to 90
seconds. When set at the slowest acceleration rate, the drive will take 90 seconds to accelerate
from zero to rated speed, following a linear ramp. When less than rated speed is set, this time
required to reach top speed is proportionally less.
The Linear Acceleration circuit may be activated or deactivated in both Manual/Run and
Jog/Thread/Auto modes by setting the programing switches as indicated on the programming
chart on the connection diagram.
To set the Accel Rate: stop the controller with the Stop pushbutton. Turn the Run Speed
potentiometer to 100% (Full CW). With the drive at a complete stop, push the Start pushbutton,
and time the interval required for the drive to accelerate from zero to full speed. Adjust the Accel
Rate potentiometer R18, accordingly, CW for a faster accel rate.
9. Velocity Damping R22*-this potentiometer is used to match the controller response to the drive
response (drive response is a function of the clutch coil time constant and system inertia). The
proper setting for this adjustment depends upon the drive size and total inertia.
See Preliminary Adjustments. If instability (speed control becomes erratic) occurs at any setting
increase (turn CW) slightly until the speed becomes stable.
*See basic 4000/4050 manual for a more destined description of this adjustment.
10. HI Damping R20-This pot is located on the Torque Limit modification board. It is used for
applications, such as stamping presses, where the load inertia is greater than 5 to 10 times the
drive inertia. In these cases, turn the Velocity Damping pot R22 on the main board to zero (full
CCW). Now adjust the HI Damping pot R20 the modification board until the proper response is
achieved (neither oscillatory nor sluggish). If, however, maximum CW is attained and the system
remains oscillatory, further damping may be obtained from R22 on the main board. The main PCB
Velocity Damping pot R22 has about 75% of the damping range that the HI Damping pot R20 has
on the modification board. However, they may be used in combination on high inertia applications
where increased damping is required.
11. Torque Limit PCB 15-444-2 (Normal Load)
a. Apply a normal load on the mechanical unit driven by the clutch
b. Monitor the motor current. Since current is proportional to torque check your nameplate for
the rated motor current to determine the desired torque limit. Example- if your drive is rated
at 10 amps, and you want to limit the torque (150% of 10 amperes is 15 amperes), start the
drive and note the maximum current on the ac ammeter during acceleration. If the current
tis less than a50% of rated motor torque, increase the Torque Limit setting R19 CW. If the
current rating is too high, decrease the Torque Limit setting CCW. Stop the unit and repeat
the Start Up. Check on the ac ammeter during acceleration. If the motor current during
acceleration never reaches 150% of rated motor current, Increase the load and repeat current
monitoring.

12
c. When the clutch is being torque limited, decrease the setting of the torque damping
potentiometer r18 CCW until instability (hunting develops. Then increase the setting CW until
stability is attained. Recheck the Torque Limit setting as described in step 11b and readjust if
necessary.
12. Torque Limit PCB 15-444-2 (If normal load cannot be applied)
a. Apply a load to the motor and note the motor current (IR) a load of 50% of full load or more
is desirable.
b. Check the motor nameplate for full load current (IF) of the motor.
c. Connect a voltmeter across terminals 1 and 2 and measure the voltage (VR) at a motor current
of IR
d. Calculate what the voltage would be across terminals 1 and 2 at full load:
VF= ()×()
VF= Current xfmr output voltage at full load
VR= Current xfmr output voltage at reduced load
IF= Motor current at full load
IR= Motor current at reduced load
e. Disconnect the leads to terminals 1 and 2 on 15-444-2 Modification board and connect a
variac
f. Adjust the variac for VF and adjust the Torque Limit pot until the output speed of the drive
just begins to decrease. Increasing the output of the variac slightly will cause the speed of
the drive to decrease sharply. When making this adjustment DO NOT exceed 75 volts out of
the variac.
g. Torque Limit Damping- Follow the procedure outlined in step 11c. A load must be applied,
and the circuit must be limiting torque to make this adjustment.
13. Jog at Run Speed-Stop the controller, set the Run Speed pot to some slow speed and set the
Run/Jog switch to Jog. Push down the Start pushbutton, the drive will run at the selected slow
speed as long as the Start pushbutton is depressed.

13
Renewal Parts List for Standard 4000 & 4050 Controllers with Torque Limit and Jog at Run Speed
Qty
Part Number
Description
Legend
Model 4000 Controllers
15-530-0005 Main PCB Assembly **
1
27-123-0001
Mini-Jumper
J1
*2
32-018-4091
Fuse, 4 Amp, 250 V
FU1, 2
*1
53-398-0001
Relay, 4pdt, plug-in
E
15-533-1015 Panel Mount
1
15-530-0005
Main PCB (Refer to PCB parts list above)
*1
15-444-0002
Torque Limit PCB assembly
4
36-298-0010
Circuit board support
15-551-1015 Standard Enclosure
1
15-530-5
Main PCB (Refer to PCB parts list above)
*1
15-444-0002
Torque Limit PCB assembly
4
36-298-0010
Circuit board support
Model 4050 Controllers
15-530-0006 Main PCB Assembly **
1
27-123-0001
Mini Jumper
J1
*2
32-028-0100
Fuse, 10 Amp, 250 V
FU1, 2
*1
53-398-0001
Relay, 4pdt, plug-in
E
15-539-0015 Panel Mount
1
15-530-0006
Main PCB (Refer to PCB parts list above)
*1
15-444-0005
Torque Limit PCB assembly
1
15-529-0019
Heat sink assembly, incl. Q1 & D3
4
36-298-0010
Circuit board support
15-553-0015 Standard Enclosure
1
15-539-0015
Basic Panel assembly (Refer to Panel Mount parts list
above)
*Denotes minimum spare parts **Denotes suggested spares when downtime is critical

14
Drive Source International/Dynamatic
7900 Durand Ave Bldg 3 Sturtevant, WI 53177
www.Dynamatic.com
Other manuals for 4000
3
This manual suits for next models
5
Table of contents
Other Dynamatic Controllers manuals

Dynamatic
Dynamatic 4000 User manual

Dynamatic
Dynamatic EC 2000-CES User manual

Dynamatic
Dynamatic CES User manual

Dynamatic
Dynamatic 4050 User manual

Dynamatic
Dynamatic 4050 User manual

Dynamatic
Dynamatic 4050 User manual

Dynamatic
Dynamatic 4000 User manual

Dynamatic
Dynamatic 4000 User manual

Dynamatic
Dynamatic EC 2000 User manual