E2S BExBGL1D User manual

_______________________________________________________________________________________________________________________________
EuropeanSafetySystemsLtd. Impress House, MansellRoad, Acton, London W37QHsales@e-2-s.com Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
DocumentNo. IS2468-PIssue D18-03-10 Sheet 1of 4
INSTRUCTIONMANUAL(ATEX/IECEx)
BExBGL1DFlameproofLEDBeacon
ForuseinFlammableGasand DustAtmospheres
1)Introduction
TheBExBGL1DisaflameproofLEDbeaconwhichis
certified tomeettheATEXdirective94/9/ECandtheIECEx
scheme.The beaconproducesvisualwarningsignalsand
can be usedinhazardousareaswherepotentiallyflammable
gasanddustatmospheresmaybepresent. TheBExBGL1D
LEDbeaconhasninedifferentflashpatternsincludinga
steadyONstateandcan alsobe remotelyswitched toa
secondandthirdflashpattern.Thebeaconcan be usedin
Zone1andZone2areaswithgasesingroupsIIA,IIBand
IICandTemperatureClassificationsofT1,T2,T3,andT4.It
can alsobe usedinatemperatureclassificationT5,ifthe
upperambienttemperatureisrestrictedto+40ºC.Theunit
can be usedinZone21 andZone22 areasforcombustible
dustsandhasan IPratingofIP67andasurface
temperatureratingof T120ºCorT105ºCif theupperambient
temperatureisrestricted to+55ºCandT95ºCiftheupper
ambient temperatureisrestrictedto+40ºC.
2)Marking
All unitshavearatinglabel,whichcarriesthefollowing
important information:-
UnitType No. BExBGL1D
Input Voltage: DC Units10-50V
ACUnits10-35Vor230Vor115V
Codes: ExdIICT4forTa–50ºCto+70ºC
ExdIICT5forTa–50ºCto+40ºC
ExtDA21T120ºCbasedonmax. Taof+70ºC
CertificateNo’s KEMA00ATEX2006
IECExKEM10.0002
Warnings: DONOTOPENWHENANEXPLOSIVE
GAS ORDUSTATMOSPHEREISPRESENT
COVERBOLTSCLASS A4-80
USE HEATRESISTINGCABLES ANDCABLEGLANDS
(Rated 110ºC)ATAMB. TEMPERATURES OVER40ºC
YearofConstruction/
SerialNo. i.e. 10 / 1DB73000001
3)TypeApprovalStandards
ThebeaconhasECTypeExaminationandIECExcertificates
issuedbyKEMAandhavebeenapprovedtothefollowing
standards:-
EN60079-0:2006 IEC60079-0:2004(Ed4) General Requirements
EN60079-1:2007 IEC60079-1:2007 (Ed6) Flameproof Enclosure‘d’
EN61241-0:2006 IEC61241-0:2004(Ed1)DustGeneral
Requirements
EN61241-1:2004 IEC60079-1:2004(Ed1)DustEnclosurestD
4)Installation Requirements
Theledbeaconsmustbeinstalled inaccordancewiththe
latestissuesoftherelevantpartsoftheBS EN60079
specificationsortheequivalentIECspecifications–
Selection,Installationandmaintenanceofelectrical
apparatusforuseinpotentiallyexplosiveatmospheres(other
thanminingapplicationsorexplosiveprocessingand
manufacture):-
EN60079-14:2008 ElectricalInstallationsinHazardous
IEC60079-14:2007 (Ed4) Areas(otherthan mines)
EN60079-10:2003 Classification of HazardousAreas
IEC60079-10:2008 (Ed1)
Theinstallationoftheunitsmustalsobeinaccordancewith
anylocalcodesthatmayapplyandshouldonlybe carried
outbyacompetentelectricalengineerwhohasthe
necessarytraining.
5)Zones,Gas Group, Category,IPRating and
TemperatureClassification
TheBExBGL1Dbeaconshavebeencertified ExdIICT4for
Ta–50ºCto+70ºCandExdIICT5forTa–50ºCto+40ºCfor
gasandIP67T120ºCTa< +70ºC,T105ºCTa< +55ºCand
T95ºCTa< +40ºCfordust. Thismeansthattheunitscan be
installed inlocationswiththefollowingconditions:-
Area Classification Gas:
Zone1
Explosivegasairmixt
urelikelytooccurin
normaloperation.
Zone2
Explosivegasairmixturenotlikelytooccur,
andifit does, it willonlyexist forashort time.
GasGroupings:
GroupIIA
Propane
GroupIIB
Ethylene
GroupIIC
HydrogenandAcetylene
TemperatureClassification:
T1
400
o
C
T2
300
o
C
T3
200
o
C
T4
135
o
C
T5
100
o
C
Amb. +40ºC
0518
CEMarking
Notified BodyNo.
II 2G/D
Epsilonx
Equipment Groupand
Category:

_______________________________________________________________________________________________________________________________
EuropeanSafetySystemsLtd. Impress House, MansellRoad, Acton, London W37QHsales@e-2-s.com Tel: +44 (0)20 8743 8880
www.e-2-s.com Fax: +44 (0)20 8740 4200
DocumentNo. IS2468-PIssue D18-03-10 Sheet 2of 4
Area Classification Dust:
Zone21
Explosivedustairmixturelikelytooccurin
normaloperation.
Zone22
Explosivedust airmixturenot likelytooccur, and
ifit does, it will onlyexist forashort time.
IPRating: IP67 T120ºCTa< +70ºC
T105ºCTa< +55ºC
T95ºCTa< +40ºC
EquipmentCategory: 2G/D
AmbientTemperatureRange: -50°Cto+70°C
(T5=+40ºC)
6)Beacon Location and Mounting
Thelocationof thebeaconsshouldbemadewithdueregard
totheareaoverwhichthewarningsignalmustbe visible.
Theyshouldonlybefixedtoservicesthatcan carrythe
weight oftheunit.
Thebeaconsshouldbesecurelyboltedtoasuitablesurface
usingthe7mm diameterboltholesinthestainless steelU
shaped mountingbracket(see figure1).Therequired angle
can be achieved bylooseningthetwolarge bracket screwsin
thesideoftheunit, whichallowadjustmentofthebeaconin
stepsof 18°.Oncompletionoftheinstallation thetwolarge
bracketadjustmentscrewsonthe sideoftheunitmustbe
fullytightened toensurethat theunitcannot moveinservice.
SAFETYWARNING:
Theflashdomeguardmustnotberemovedfromtheunit
atanytime.
7)Access to theFlameproofEnclosure
Inordertoconnecttheelectricalsupplycablestothebeacon
itisnecessarytoremovetheflameproofcovertogainaccess
totheflameproofchamber.Toachievethisremovethefour
M6hexagonsocketheadscrews(see figure2)andwithdraw
theflameproofcovertakingextremecarenottodamagethe
flameproofjointsintheprocess.
Notethefour M6screwsareClass A4-80 stainlesssteel
andonlyscrewsofthiscategorycanbeusedonthe
beacons. Itisthereforeimportantthatthesescrewsand their
springwashersarekept inasafeplaceduringinstallation.
Oncompletionofthecablewiringinstallationtheflameproof
jointsshouldbe inspected toensurethattheyareclean and
thattheyhavenotbeendamaged duringinstallation.Also
checkthattheearthbondingwirebetweenthetwocasting
sectionsissecureandthe‘O’ringsealisinplace.When
replacingtheflameproofcovercastingensurethat it issquare
withtheflameproofchambercastingbeforeinserting.
Carefullypushthecoverinplaceallowingtimefortheairto
be expelled.Onlyafterthecoverisfullyinplaceshouldthe
fourM6StainlessSteelA4-80coverboltsandtheirspring
washerbe inserted andtightened down.If thecoverjams
whileitisbeinginserted,carefullyremoveitandtryagain.
Neverusethecoverboltstoforcethecoverintoposition.
8)PowerSupplySelection
Itisimportantthatasuitablepowersupplyisusedtorun the
beacons.Thepowersupplyselected musthavethe
necessarycapacitytoprovidetheinputcurrenttoall ofthe
beacons
Thefollowingtableshowsthe inputcurrenttakenbythe
variousbeacons:-
UnitType NominalI/PInput Max.
VoltageCurrentI/P
Volts
BExBGL1D 10-50VDC 400mA@24V 50V
BExBGL1D 10-35VAC 812mA@20V 35V
BExBGL1D 230VAC65mA 253V
BExBGL1D 115VAC135mA 126V
Theinputcurrentwill varyaccording tothe voltageinput
level.The currentlevelsshownabovearefornominalinput
voltage.
Theabovetablealsoshowsthe maximumvoltagesatwhich
thebeaconscan be operated.
9)CableSelection
Whenselectingthecablesizeconsiderationmustbegivento
theinputcurrentthateachunitdraws(see tableabove),the
numberofbeaconsonthelineandthelengthofthecable
runs.Thecablesizeselected musthavethenecessary
capacitytoprovide theinputcurrenttoallofthebeacons
connected totheline.
Flashdome
Guard
Flameproof
Chamber
Flameproof
Cover
S/SBracket
Figure1
4off M6CoverScrews
ExternalEarth
Terminal
Figure2

_______________________________________________________________________________________________________________________________
EuropeanSafetySystemsLtd. Impress House, MansellRoad, Acton, London W37QHsales@e-2-s.com Tel: +44 (0)20 8743 8880
www.e-2-s.com Fax: +44 (0)20 8740 4200
DocumentNo. IS2468-PIssue D18-03-10 Sheet 3of 4
SAFETYWARNING: IftheBExBGL1Dbeaconsareusedat
highambienttemperatures,i.e.over+40ºC,thenthecable
entrytemperaturemayexceed+70ºCandthereforesuitable
heatresistingcablesmustbe used,witharated service
temperatureofat least 110ºC.
10)Earthing
BothACandDCbeaconunitsmustbeconnectedtoagood
qualityearth.Theunitsareprovided withinternaland
externalearthingterminalswhicharebothlocated onthe
terminalchambersectionoftheunit(see figures2and3).
Whenusingtheinternalearthterminalensurethatthe
stainless steelM4flatwasherisbetweentheincoming earth
wireandtheenclosure.
Whenusingtheexternalearthterminalacablecrimplug
must be used. Thecablelugshouldbelocatedbetweenthe
twoM5stainless steelflat washers. TheM5stainless steel
springwashermust be fixed betweentheouterflat washer
andtheM5stainless steelnut toensurethat thecablelugis
secured against looseningandtwisting.
Theinternalearthbondingwireensuresthatagoodquality
earthismaintained betweentheflameproof chambercasting
andtheflameproofcovercasting.
11)CableGlands
TheBExBGL1Dbeaconshavedualcableglandentrieswhich
haveanM20 x1.5entrythreadasstandard.Onlycable
glandsapprovedforEx‘d’applicationscan be used,which
mustbe suitableforthetype ofcablebeingusedandalso
meettherequirementsoftheEx‘d’flameproofinstallation
standardEN60079-14:2008/ IEC60079-14:2007.
Whenonlyonecableentryisusedtheotheronemustbe
closedwithanEx‘d’flameproofblankingplug, whichmust be
suitablyapproved fortheinstallationrequirements.
Forcombustibledustapplications,thecableentrydeviceand
blankingelementsshall be intype ofexplosionprotection
increasedsafety"e"orflameproofenclosure"d"andshall
haveanIP6XratingaccordingtoEN60529.
SAFETYWARNING: IftheBExBGL1Dbeaconsareusedat
highambienttemperatures,i.e.over+40ºC,thenthecable
entrytemperaturemayexceed+70ºCandthereforesuitable
heat resistingcableglandsmust beused, witharated service
temperatureofat least 110ºC.
12)CableConnections
Thecablesupplyconnectionsaremade intotheterminal
blocksontheelectronicpcbassemblylocatedinthe
flameproofenclosure,seesection7ofthismanualforaccess
totheflameproofenclosure.TheACunithastwolive
terminalsandtwoneutralterminalsfortheinputandoutput
supplywiringandtheDC unit hastwo+veterminalsandtwo
-veterminalsfortheinputandoutputsupplywiring.Both
unitshaveS2andS3terminalstoremotelychange theflash
pattern, see section13 ofthismanual.
SupplyTerminals
Stage S2&S3
Terminals
FlashPattern
PinHeaders
Supplyand
Stage S2&S3
Terminals
FlashPattern
Pin Headers
Wireshavingacrosssectionalareaofupto2.5mm²can be
connected toeachterminalway.If an input andoutputwireis
required a2.5mm²wirecan be connectedtoeachterminal
way.Whenconnectingwirestothe terminalsgreatcare
shouldbe takentodressthewiressothatwhen thecoveris
2off M20
CableEntries
InternalEarthTerminal
Figure3
Internal
Bonding Wire
Terminal
BExBGL1
DBeaconCoverInternalView
Figure4
BExBGL1D
ACLED
Beacons
BExBGL1DDCLED
Beacons
Figure5

_______________________________________________________________________________________________________________________________
EuropeanSafetySystemsLtd. Impress House, MansellRoad, Acton, London W37QHsales@e-2-s.com Tel: +44 (0)20 8743 8880
www.e-2-s.com Fax: +44 (0)20 8740 4200
DocumentNo. IS2468-PIssue D18-03-10 Sheet 4of 4
inserted intothechamberthewiresdo notexertexcess
pressureontheterminalblocks.Thisisparticularlyimportant
whenusingcableswithlarge crosssectionalareassuchas
2.5mm².
13)Flash PatternSelection and 2nd &3rd Stages
TheBExBGL1DLEDbeaconshave9differentflashpatterns
includingoneONstatethatcan be selectedforthefirst
stage.Theycan thenberemotelyswitchedtosecondand
thirdstage flashpatterns.Theflashpatternsareselectedby
pinheadersonthepcbforbothDC andACunits.Thetable
onpagefourshowsthepinheaderpositionsforthe nine
flashpatternsandwhichpatternsareavailableforthesecond
andthirdstages.Tooperatetheledbeacononstage one
simplyconnectthesupplyvoltage tothenormalsupply
terminals(+veand–veforDC units, LandNforACunits).
Theoperationofthesecondandthirdstagesisdifferentfor
DC andACunits.
DC UnitsSecondandThirdStage Selection
Tochange tothesecondstage flashpattern,simplyconnect
a-vesupplylinetoterminalS2,whilemaintainingthedc
supplytothe+veand–veterminals.Similarlyforthe third
stage flashpattern,connecta-vesupplylinetoterminalS3.
ThesupplylinetotheS3terminalwill automaticallyoverride
asupplytotheS2terminal.
ACUnitsSecondandThirdStageSelection
Toselectthesecondandthirdstageflashpatternsonthe
BExBGL1DACbeaconstheCommon(C)terminalonthe
three wayterminalblockonthepcbisconnectedtotheS2
terminalforthesecondstage toneandtheS3terminalforthe
thirdstage tone.
14)End ofLineMonitoring (DC Units)
OntheBExBGL1DDCbeacons,dcreverselinemonitoring
can be usedifrequired.All DC beaconshaveablocking
diode fittedintheirsupplyinputlines.Anend ofline
monitoringdiode oran endof linemonitoringresistorcan be
connectedacrossthe+veand–veterminals.If an end of line
resistorisuseditmusthaveaminimumresistancevalueof
3k3ohmsandaminimumwattage of0.5wattsoraminimum
resistancevalueof500ohmsandaminimumwattage of2
watts.
Flash Pattern Table
Stage
1
LED
Stage2 Stage3
Pattern
FlashPattern
Pattern
Pattern
1
ON
9
8
2
Rotating3LEDonFast
7
1
3
Rotating6LEDonFast
8
1
4
Rotating3LEDonSlow
9
1
5
Rotating6LEDonSlow
6
1
6
Doublestrikestrobe 1Hz
9
1
7
Singlestrikestrobe2Hz
3
1
8
Doublestrikestrobe 2Hz
3
1
9
Alternateside flash1:12Hz
3
1
PINHEADERPOSITIONS
PatternNo.1 PatternNo. 2 PatternNo. 3
PatternNo.4 PatternNo. 5 PatternNo. 6
PatternNo.7 PatternNo. 8 PatternNo. 9
PatternSelection
PinHeaders
PCBEdge
BExBGL1DDCLEDBeaconWiring
S3S2
Stage3
Stage2
+
-
-+ + - S2 S3 S3S2C-+
BExBGL1DACLEDBeaconWiring
S3S2
Stage 3
Stage 2
L
N
C
C
NL LN CS2 S3 S3S2CNL

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected]m Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. BExBGL1D (Gas-Dust) English Issue A (Four Sheets) 26-01-11 (1)
INSTRUCTION MANUAL (ATEX
/ IECEx
)
(GBR)
BExBGL1D Flameproof LED Beacon
For use in Flammable Gas and Dust Atmospheres
2) Marking
All units have a rating label, which carries the following
important information:-
Unit Type No. BExBGL1D
Input Voltage: DC Units 10-50V
AC Units 10-35V or 230V or 115V
Codes: Ex d IIC T4 for Ta –50ºC to +70ºC
Ex d IIC T5 for Ta –50ºC to +40ºC
Ex tD A21 T120ºC based on max. Ta of +70ºC
Certificate No’s KEMA 00ATEX2006
IECEx KEM 10.0002
Warnings: DO NOT OPEN WHEN AN EXPLOSIVE
GAS OR DUST ATMOSPHERE IS PRESENT
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND CABLE GLANDS
(Rated 110ºC) AT AMB. TEMPERATURES OVER 40ºC
4) Installation Requirements
The led beacons must be installed in accordance with the
latest issues of the relevant parts of the BS EN 60079
specifications or the equivalent IEC specifications –
Selection, Installation and maintenance of electrical
apparatus for use in potentially explosive atmospheres (other
than mining applications or explosive processing and
manufacture):-
EN60079-14:2008 Electrical Installations in Hazardous
IEC60079-14:2007 (Ed4) Areas (other than mines)
EN60079-10:2003 Classification of Hazardous Areas
IEC60079-10:2008 (Ed1)
Installation should only be carried out by competent
personnel and local codes of practice applied.
5) Zones, Gas Group, Category and Temperature
Classification
The units can be installed in locations with the following
conditions:-
Area Classification Gas:
Zone 1 Explosive gas air mixture likely to occur in
normal operation.
Zone 2 Explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
Gas Groupings:
Group IIA Propane
Group IIB Ethylene
Group IIC Hydrogen and Acetylene
Temperature Classification:
T1 400
o
C
T2 300
o
C
T3 200
o
C
T4 135
o
C
T5 100
o
C Amb. +40ºC
Area Classification Dust:
Zone 21 Explosive dust air mixture likely to occur in
normal operation.
Zone 22 Explosive dust air mixture not likely to occur, and
if it does, it will only exist for a short time.
IP Rating: IP67 T120ºC Ta < +70ºC
T105ºC Ta < +55ºC
T95ºC Ta < +40ºC
Equipment Category: 2G/D
Ambient Temperature Range: -50°C to +70°C
(T5 = +40ºC)
5) Beacon Location and Mounting
See drawing A
SAFETY WARNING: The flashdome guard must not be
removed from the unit at any time.
6) Access to the Flameproof Enclosure
See drawing B
Note the four M6 screws are Class A4-80 stainless steel
and only screws of this category can be used on the
beacons. It is therefore important that these screws and their
spring washers are kept in a safe place during installation.
0518
CE Marking
Notified Body No.
II 2G/D
Epsilon x
Equipment Group and
Category:

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sa[email protected]m Tel: +44 (0)20 8743 8880
www.e-2-s.com Fax: +44 (0)20 8740 4200
Document No. BExBGL1D (Gas-Dust) English Issue A (Four Sheets) 26-01-11 (2)
8) Power Supply Selection
The system power supply must have the necessary capacity
to provide the input current to all of the beacons connected to
the system.
The following table shows the input current taken by the
various beacons:-
Unit Type Nominal I/P Input Max.
Voltage Current I/P Volts
BExBGL1D 10-50V DC 400mA@24V 50V
BExBGL1D 10-35V AC 812mA@20V 35V
BExBGL1D 230V AC 65mA 253V
BExBGL1D 115V AC 135mA 126V
The above table also shows the maximum voltages at which
the beacons can be operated.
9) Cable Selection
Cables must be capable of handling the current draw from all
of the unts on the line
SAFETY WARNING: If the BExBGL1D beacons are used at
high ambient temperatures, i.e. over +40ºC, then the cable
entry temperature may exceed +70ºC and therefore suitable
heat resisting cables must be used, with a rated service
temperature of at least 110ºC.
10) Earthing
Both AC and DC beacon units must be connected to a good
quality earth. The units are provided with internal and
external earthing terminals which are both located on the
terminal chamber section of the unit (see figures 2 and 3).
When using the internal earth terminal ensure that the
stainless steel M4 flat washer is between the incoming earth
wire and the enclosure.
When using the external earth terminal a cable crimp lug
must be used. The cable lug should be located between the
two M5 stainless steel flat washers. The M5 stainless steel
spring washer must be fixed between the outer flat washer
and the M5 stainless steel nut to ensure that the cable lug is
secured against loosening and twisting.
The internal earth bonding wire ensures that a good quality
earth is maintained between the flameproof chamber casting
and the flameproof cover casting.
11) Cable Glands
The BExBGL1D beacons have dual cable gland entries which
have an M20 x 1.5 entry thread as standard. Only cable
glands approved for Ex ‘d’ applications can be used, which
must be suitable for the type of cable being used and also
meet the requirements of the Ex ‘d’ flameproof installation
standard EN60079-14:2008 / IEC60079-14:2007.
When only one cable entry is used the other one must be
closed with an Ex ‘d’ flameproof blanking plug, which must be
suitably approved for the installation requirements.
For combustible dust applications, the cable entry device and
blanking elements shall be in type of explosion protection
increased safety "e" or flameproof enclosure "d" and shall
have an IP 6X rating according to EN 60529.
SAFETY WARNING: If the BExBGL1D beacons are used at
high ambient temperatures, i.e. over +40ºC, then the cable
entry temperature may exceed +70ºC and therefore suitable
heat resisting cable glands must be used, with a rated service
temperature of at least 110ºC.
12) Cable Connections
See drawings C and D / wiring diagram E
13) Flash Pattern Selection and 2nd & 3rd Stages
The BExBGL1D LED beacons have 9 different flash patterns
including one ON state that can be selected for the first
stage. They can then be remotely switched to second and
third stage flash patterns. The flash patterns are selected by
pin headers on the pcb for both DC and AC units. The table
on page four shows the pin header positions for the nine
flash patterns and which patterns are available for the second
and third stages. To operate the led beacon on stage one
simply connect the supply voltage to the normal supply
terminals (+ve and –ve for DC units, L and N for AC units).
The operation of the second and third stages is different for
DC and AC units.
DC Units Second and Third Stage Selection
To change to the second stage flash pattern, simply connect
a -ve supply line to terminal S2, while maintaining the dc
supply to the +ve and –ve terminals. Similarly for the third
stage flash pattern, connect a -ve supply line to terminal S3.
The supply line to the S3 terminal will automatically override
a supply to the S2 terminal.
AC Units Second and Third Stage Selection
To select the second and third stage flash patterns on the
BExBGL1D AC beacons the Common (C) terminal on the
three way terminal block on the pcb is connected to the S2
terminal for the second stage tone and the S3 terminal for the
third stage tone.
14) End of Line Monitoring (DC Units)
On the BExBGL1D DC beacons, dc reverse line monitoring
can be used if required. All DC beacons have a blocking
diode fitted in their supply input lines. An end of line
monitoring diode or an end of line monitoring resistor can be
connected across the +ve and –ve terminals. If an end of line
resistor is used it must have a minimum resistance value of
3k3 ohms and a minimum wattage of 0.5 watts or a minimum
resistance value of 500 ohms and a minimum wattage of 2
watts.

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)20 8743 8880
www.e-2-s.com Fax: +44 (0)20 8740 4200
Document No. BExBGL1D (Gas-Dust) English Issue A (Four Sheets) 26-01-11 (3)
Flash Pattern Table
Stage 1
LED
Stage 2
Stage 3
Pattern
Flash Pattern
Pattern
Pattern
1 ON 9 8
2 Rotating 3 LED on Fast 7 1
3 Rotating 6 LED on Fast 8 1
4 Rotating 3 LED on Slow 9 1
5 Rotating 6 LED on Slow 6 1
6 Double strike strobe 1 Hz 9 1
7 Single strike strobe 2 Hz 3 1
8 Double strike strobe 2 Hz 3 1
9 Alternate side flash 1:1 2 Hz 3 1
PIN HEADER POSITIONS
Pattern No. 1 Pattern No. 2 Pattern No. 3
Pattern No. 4 Pattern No. 5 Pattern No. 6
Pattern No. 7 Pattern No. 8 Pattern No. 9
Pattern Selection
Pin Headers
PCB Edge

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)20 8743 8880
www.e-2-s.com Fax: +44 (0)20 8740 4200
Document No. BExBGL1D (Gas-Dust) English Issue A (Four Sheets) 26-01-11 (4)
Drawing A
Tighten screw to secure.
Spænd skruen for at fastgøre.
Schroef aandraaien om vast te zetten.
Serrer la vis pour une fixation sûre.
Zum Sichern Schraube anziehen.
Stringere la vite per il fissaggio.
Stram skruen for å feste.
Aperte o parafuso para fixar.
Apriete el tornillo para asegurar.
Dra åt skruven för att fästa.
Loosen screw to adjust.
Løsn skruen for at tilpasse.
Schroef losdraaien om af te stellen.
Desserrer la vis pour régler.
Zum Regulieren Schraube lockern.
Allentare la vite per poter effettuare la
regolazione.
Løsne skruen for å justere.
Desaperte o parafuso para ajustar.
Afloje el tornillo para ajustar.
Lossa skruven för att justera.
Lossen screw
to adjust
Tighten screw
to secure
180º
Drawing B
Drawing C
Supply Terminals
Stage S2 & S3
Terminals
Flash Pattern
Pin Headers
Drawing D
Supply and
Stage S2 & S3
Terminals
Flash Pattern
Pin Headers
Wiring Diagram E
BExBGL1D DC LED Beacon Wiring
S3S2
Stage 3
Stage 2
+
-
-+ + - S2 S3 S3S2C-+
BExBGL1D AC LED Beacon Wiring
S3S2
Stage 3
Stage 2
L
N
C
C
NL L N C S2 S3 S3S2CNL
BExBGL1D DC LED
Beacons
BExBGL1D AC LED
Beacons

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected]m Tel: +44 (0)20 8743 8880
www.e2s.com Fax: +44 (0)20 8740 4200
Document No. BExBGL1D (Gas-Dust) German Issue A (Three Sheets) 02-02-11
TECHNISCHE HIN
WEISE
(ATEX
/ IECEx
)
(DEU)
BExBGL1D Explosionsgeschützte LED-Leuchte
Zum Einsatz in entflammbaren Gas- und
Staubatmosphären
2) Kennzeichnung
Alle Geräte sind mit einem Typenschild mit den folgenden
wichtigen Informationen versehen:-
Gerätetyp-Nr. BExBGL1D
Eingangsspannung:
Gleichstromgeräte (DC) 10-50 V
Wechselstromgeräte (AC) 10-35V; 230V; 115V
Code: Ex d IIC T4 für Ta –50ºC to +70ºC
Ex d IIC T5 für Ta –50ºC to +40ºC
Ex tD A21 T120ºC based on max. Ta of +70ºC
Zertifikat-Nr. KEMA 00ATEX2006
IECEx KEM 10.0002
Warnung NICHT IN EXPLOSIONSFÄHIGEN GAS- ODER
STAUBATMOSPHÄREN ÖFFNEN
ABDECKSCHRAUBEN KLASSE A4-80
WÄRMEBESTÄNDIGE KABEL UND
KABELVERSCHRAUBUNGEN VERWENDEN
(Nennleistung 110ºC) BEI UMGEB.-TEMP. ÜBER 40ºC
4) Installationsanforderungen
Die LED-Leuchten müssen gemäß den folgenden oder
vergleichbaren Standards installiert werden.
EN60079-14:2008 Elektrische Installationen in
IEC60079-14:2007 (Ed4) Gefahrenbereichen (außer
Bergwerken)
EN60079-10:2003 Klassifizierung von Gefahrenbereichen
IEC60079-10:2008 (Ed1)
Die Installation sollte nur von qualifiziertem Fachpersonal
vorgenommen werden. Örtliche anerkannte Verfahren sind
zu beachten.
5) Zonen, Gasgruppe, Kategorie und
Temperaturklassifizierung
Die Geräte können an Standorten aufgestellt werden, an
denen die folgenden Bedingungen vorliegen:-
Bereichseinteilung Gas:
Zone 1 Bei normalem Betrieb kann mit hoher
Wahrscheinlichkeit eine explosive Gas-Luft-
Mischung vorliegen.
Zone 2 Explosive Gas-Luft-Mischung unwahrschein-
lich und sollte sie doch auftreten, dann nur
kurzfristig.
Gasgruppen:
Gruppe IIA Propan
Gruppe IIB Äthylen
Gruppe IIC Wasserstoff und Azetylen
Temperaturklassifizierung:
T1 400
o
C
T2 300
o
C
T3 200
o
C
T4 135
o
C
T5 100
o
C Amb. +40ºC
Bereichseinteilung Staub:
Zone 21 Explosionsgefährdetes Staub-/Luftgemisch,
das beim normalen Betrieb durchaus
auftreten kann
Zone 22 Explosionsgefährdetes Staub-/Luftgemisch,
dessen Auftreten unwahrscheinlich bzw. von
kurzer Dauer ist.
IP-Schutzklasse: IP67 T120ºC Ta < +70ºC
T105ºC Ta < +55ºC
T95ºC Ta < +40ºC
Gerätekategorie: 2G/D
Umgebungstemperaturbereich: -50°C to +70°C
(T5 = +40ºC)
6) Standort und Montage der Leuchte
Siehe Zeichnung A
SICHERHEITSHINWEIS: Der Schutz der Signalhaube darf
auf keinen Fall vom Gerät entfernt werden.
7) Zugang zum schwer entflammbaren Gehäuse
Siehe Zeichnung B
Hinweis: Die vier Schrauben M6 sind aus Edelstahl Klasse
A4-80 gefertigt. Für diese Leuchten sind nur Schrauben
dieser Kategorie geeignet. Diese Schrauben und die
zugehörigen Federringe sind beim Einbau daher sorgfältig
aufzubewahren.
0518
II 2G/D
CE-Kennzeichnung:
Nr. der demeldeten
Stelle:
Epsilon x:
Gerätegruppe und
–kategorie:

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)20 8743 8880
www.e2s.com Fax: +44 (0)20 8740 4200
Document No. BExBGL1D (Gas-Dust) German Issue A (Three Sheets) 02-02-11
8) Stromversorgung
Die Stromversorgung der Anlage muss ausreichen, um alle
angeschlossenen Leuchten mit Eingangsstrom zu versorgen.
Folgende Tabelle zeigt die Eingangsstromaufnahme der
verschiedenen Leuchten:-
Gerätetyp Eingangs- Eingangs- Max. I/P
Spannung strom Spannung
BExBGL1D 10-50V DC 400mA@24V 50V
BExBGL1D 10-35V AC 812mA@20V 35V
BExBGL1D 230V AC 65mA 253V
BExBGL1D 115V AC 135mA 126V
Obige Tabelle zeigt auch die maximale Spannung an, mit der
die Leuchten betrieben werden können.
9) Kabelwahl
Die Kabel müssen den Strom aller angeschlossenen Geräte
führen können.
SICHERHEITSHINWEIS: Wenn die BExBGL1 Leuchte bei
hohen Umgebungstemperaturen eingesetzt werden (d. h. bei
über +40ºC), kann die Kabeleingangstemperatur +70ºC
übersteigen. Daher sind geeignete hitzebeständige Kabel mit
einer Nennbetriebstemperatur von mindestens 110ºC zu
verwenden.
10) Erdung
Die Wechsel- und Gleichstrom-Leuchten müssen mit einer
hochwertigen Erdung verbunden werden. Die Geräte sind mit
internen und externen Erdklemmen (am Klemmkammerteil
des Geräts, siehe Abb. 2 und 3) versehen.
Bei Verwendung der internen Erdklemme ist sicherzustellen,
dass die M4-Edelstahl-Unterlegscheibe zwischen Eingangs-
Erdkabel und dem Gehäuse liegt.
Bei Verwendung der externen Erdklemme ist ein
Quetschkabelschuh zu verwenden, der zwischen den beiden
flachen M5-Edelstahl-Unterlegscheiben eingesetzt werden
sollte. Die M5-Unterlegscheiben sind zwischen der äußeren
flachen Unterlegscheibe und der M5-Edelstahlmutter
einzusetzen, um zu gewährleisten, dass der Kabelschuh sich
nicht lösen oder verdrehen kann.
Der interne Erdungs-Abbindedraht stellt sicher, dass
zwischen dem Gehäuse der drucksicheren Kammer und dem
Gehäuse der drucksicheren Abdeckung eine sichere Erdung
besteht.
11) Kabelverschraubungen
Die BExBGL1D Leuchten sind mit doppelten
Kabelverschraubungen mit Eingangsgewinden von M20 x1.5
versehen. Es dürfen nur Kabelverschraubungen verwendet
werden, die für Ex ‘d’-Anwendungen zugelassen sind. Die
Kabelverschraubungen müssen für den eingesetzten
Kabeltyp geeignet sein und zudem den Anforderungen der
Ex ‘d’-Norm zur Installation drucksicherer Geräte EN60079-
14:2008 / IEC60079-14:2007 entsprechen.
Wenn nur ein Kabeleingang verwendet wird, muss der
andere mit einem druckfesten Ex ‘d’ Stopfen, der für die
Installationsbedingungen zugelassen ist, verschlossen
werden.
Bei Anwendungen in brennbaren Staubbereichen sind
Kabelverschraubungen und Stopfen, die mit erhöhter
Sicherheit (Typ „e“) oder druckfester Kapselung („Typ „d“)
geschützt sind, zu installieren und müssen der Schutzklasse
IP 6X gemäß EN60529:1992 entsprechen.
SICHERHEITSHINWEIS: Wenn die BExBGL1D Leuchten bei
hohen Umgebungstemperaturen eingesetzt werden (d. h. bei
über +40ºC), kann die Kabeleingangstemperatur +70ºC
übersteigen. Daher sind geeignete hitzebeständige Kabel mit
einer Nennbetriebstemperatur von mindestens 110ºC zu
verwenden.
12) Kabelanschlüsse
Siehe Zeichnung C und D / Schaltbild E
13) Blinkmusterauswahl und 2. & 3. Stufen
Die BExBGL1D LED-Leuchten verfügen über 9
verschiedene Blinkmuster einschließlich eines AN-
Status (Dauerleuchte), der als erste Alarmstufe
gewählt werden kann. Anschließend können die Stufen
2 und 3 Blitzmuster extern angesteuert werden. Die
Blitzmuster sowohl für die DC- als auch die AC-Geräte
werden über Kontaktbrücken auf der Leiterplatte
eingestellt. Die Tabelle auf Seite 3 zeigt die Positionen
der Kontaktbrücken für die verschiedenen Blinkmuster
und welche Blinkmuster als 2. und 3. Alarmstufe zur
Verfügung stehen. Um die LED-Leuchte auf Stufe 1 zu
betreiben, muss die Netzspannung an die normalen
Netzanschlussklemmen angeschlossen werden (+ und
– für DC-Geräte, L und N für AC-Geräte).
Der Betrieb der 2. und 3. Stufe ist bei DC- und AC-
Geräten unterschiedlich.
DC-Geräte – Auswahl der 2. und 3. Stufe
Um auf die 2. Stufe umzuschalten, muss die - minus
Klemme mit der S2 Klemme verbunden werden,
während die DC-Versorgungsleitung an den + und –
Klemmen bleibt. Um auf die 3.Stufe umzuschalten,
muss die - minus Klemme mit der S3 Klemme
verbunden werden. Die Zuleitung zur S3-Klemme hebt
automatisch den Anschluss an die S2-Klemme auf.
AC-Geräte – Auswahl der 2. und 3. Stufe
Um die Blitzmuster der Stufe 2 und 3 auf einer
BExBGL1D AC-Leuchte auszuwählen, wird die C-
Klemme der Drei-Wege-Anschlussleiste auf der
Leiterplatte für die zweite Stufe an die S2-Klemme und
für die dritte Stufe an die S3-Klemme angeschlossen.

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)20 8743 8880
www.e2s.com Fax: +44 (0)20 8740 4200
Document No. BExBGL1D (Gas-Dust) German Issue A (Three Sheets) 02-02-11
15) Überwachung des Leitungsendes
(Gleichstromgeräte)
Bei BExBGL1D-Gleichstromgeräten kann bei Bedarf eine
Wechselstrom-Sperre eingesetzt werden. Alle Gleichstrom-
Leuchten sind mit einer Sperrdiode versehen, die in die Netz-
Eingangsleitungen eingesetzt ist. Eine Überwachungsdiode
oder ein Kontrollwiderstand für das Leitungsende können
über die Klemmen + und – angeschlossen werden. Wird ein
Widerstand für das Leitungsende verwendet, muss sein
Widerstandswert mindestens 3k3 Ohm und die
Mindestleistung 0,5 Watt betragen, oder aber es muss ein
Widerstandswert von mindestens 500 Ohm und eine
Mindestleistung von 2 Watt vorliegen.
Blinkmuster-Tabelle
Stufe
1
LED
Stufe
2
Stufe
3
Muster
Blinkmuster
Muster
Muster
1 AN 9 8
2 3 LED rotierend, schnell 7 1
3 6 LED rotierend, schnell 8 1
4 3 LED rotierend, langsam 9 1
5 6 LED rotierend, langsam 6 1
6 Doppelblitz 1 Hz 9 1
7 Einzelblitz 2 Hz 3 1
8 Doppelblitz 2 Hz 3 1
9 Wechselblitz 2 Hz 3 1
Positionen der Kontaktbrücken
Pattern No. 1 Pattern No. 2 Pattern No. 3
Pattern No. 4 Pattern No. 5 Pattern No. 6
Pattern No. 7 Pattern No. 8 Pattern No. 9
Pattern Selection
Pin Headers
PCB Edge

EC DECLARATION OF CONFORMITY
Manufacturer: European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH, UK
Telephone: +44 (0)20 8743 8880 European Safety Systems Ltd
Facsimile: +44 (0)20 8740 4200 Company Registration No. 2763350
E-mail: sales@e2s.com Registered Office: Impress House
www.e2s.com Mansell Road, London, UK, W3 7QH, UK
Equipment Type: BExBG05D, BExBG05E,
BExBG10D, BExBG10E,
BExBG15D, BExBG15E,
BExBG21D,
BExTBG05D,
BExBGL1D
Directive 94/9/EC: Electrical and Mechanical equipment for use in explosive atmospheres (ATEX)
Notified Body for EC type Examination:
KEMA Quality B.V.
Notified Body No.: 0344
Utrechtseweg 310, 6812 AR Arnhem, The Netherlands
EC
-
type Examination Certificate:
KEMA 00ATEX2006
Notified Body for Quality Assurance
Notification:
Sira Certification Service
Notified Body No.: 0518
Rake Lane, Eccleston, Chester CH4 9JN, UK
Quality Assur
ance Notification
:
SIRA 05 ATEX M342
Provisions fulfilled by the equipment:
ll2 G Ex d llC T3 to T6 or
ll2 G Exde llC T4 to T6
ll2 D Ex tD A21 lP66 or lP67 T85 °C to T200 °C
Standards applied:
EN 60079-0:2006
EN 60079-1:2007
EN 60079-7:2003
EN 61241-0:2006
EN61241-1:2004
Directive 2004/108/EC: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN 61000-6-1:2007
EN 61000-6-2:2005
EN 61000-6-3:2007
EN 61000-6-4:2007
The standards EN 60079-0: 2006, EN 60079-7:2003, EN 61241-0:2006 and EN 61241-1:2004 are no longer
harmonized. The requirements of these standards have been checked against the harmonized standards EN 60079-
0:2009, EN 60079-7:2007 and EN 60079-31:2009 and there were no major technical changes affecting the latest
technical knowledge for the products listed above.
On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is
placed on the market, the equipment conforms with all technical and regulatory requirements of the above listed
directives.
Martin Streetz Date and Place of Issue: London, 04/07/2012
Quality Assurance Manager Document No: DC-004-Issue_C
Table of contents
Other E2S Security System manuals

E2S
E2S BExCS110-L2 User manual

E2S
E2S BExBG05D-P-SIL User manual

E2S
E2S SONFL1H-HO Series User manual

E2S
E2S D2xB1XH1 User manual

E2S
E2S SPECTRA H100 B User manual

E2S
E2S STExB2LD2 User manual

E2S
E2S D2xC2LD3 User manual

E2S
E2S Appello A121APPX User manual

E2S
E2S D2xB1LD2DC024 User manual

E2S
E2S IS-mA1M User manual