E2S WP6-BG User manual

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document D233-00-001-IS Issue 2 10-11-2022 Sheet 1 of 2
WP6-BG
Weatherproof Break Glass
Manual Call Point
1) Introduction
The WP6-BG is a break glass manual call point
designed to withstand harsh environments. It has
the following ratings:
CE Marking:
UKCA Marking:
IP Rating:
IP66
Ambient Temperature Range:
-40°C to +75°C
Input Voltage:
AC voltage 250V Max. Current 5.0A Max.
DC voltage 48V Max. Current 1.0A Max.
DC voltage 24V Max. Current 3.0A Max.
The enclosure is made from Red GRP (Glass
reinforced Polyester). If alternative colours are
ordered, these will be painted with an epoxy
powder coat.
2) Call Point Location and Mounting
The location of the call point should enable ease of
access for operation and testing. The unit should
be mounted using the 4 off fixing holes which will
accept up to M4 sized fixings.
72.0 [2.83]
90.0 [3.54]
View of base unit showing fixing centres in mm [in]
To gain access to the mounting holes in the base
the front cover must be removed.
This is achieved by removing the 4 off M4 cap
head bolts holding on the cover.
Once the screws are removed the cover will hang
down out of the way to gain access to the Ex e
terminal block, the internal earth terminal and
mounting hole recesses.
3) Earthing
The unit has an internal earth terminal.
It is recommended that a cable crimp lug is used
on the earth wires.
The internal earth wire is placed under a earth
clamp which will stop the cable twisting. This is
secured by an M4 screw and spring washer.
Internal Earth DIN Rail terminals
terminal
4) Cable connections
There are 3 off cable entries for M20x1.5 cable
glands or stopping plugs with a minimum ingress
protection of IP66.
The unit can be wired in a number of different ways
depending whether normally open or normally
closed contacts are required.
Wire sizes allowable are 0.5mm² to 4.0mm²
5) Testing unit operation
The break glass unit can be tested without the
need to break/replace the frangible glass element.
A test key (7mm Allen key) is used to mechanically
drop the glass down activating the switch.
The test key is inserted in the test cam and rotated
clockwise by an angle of 60º the glass element will
visibly drop down in the viewable window.
The call point switch will now change over its
contacts to operate the alarm.
Once testing is complete the unit needs to be
reset, the test key is rotated back anticlockwise by
an angle of 60º back to its original position. The
glass element should now raise up so it is level
again in the viewable window.
1. 2. 3.
Insert test Hold in Rotate back
Key rotate position anticlockwise
clockwise during to reset
60º test
INSTRUCTION MANUAL
WP6-BG Weatherproof Break Glass Manual Call Point

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document D233-00-001-IS Issue 2 10-11-2022 Sheet 2 of 2
6) Replacement of glass element
If the break glass unit has been operated the
broken glass element can be quickly replaced.
The break glass cover plate is removed by
unscrewing the 4 off M4 cap head screws attaching
it.
Once the cover is removed the broken glass will be
free to be removed, clean out any other fragments
of glass carefully.
To fit the new glass element rotate the top cam
clockwise by an angle of 50º (use a 6mm Allen
key) this will than allow the glass to fit back into the
pocket it sits in, resting on the pivot point and test
cam, release the top cam to rest on the top of the
glass element.
Pivot point Test Cam Top Cam (rotate)
Replace the cover plate and tighten the 4 off M4
cap head screws.
Ensure the glass element is free to move under the
cover plate. This can be done by running through
the units test operation. See section 5 of this
instruction manual.
7) End-of-Line and Series Devices
All models can be fitted with series resistors, end-
of-line monitoring resistors, monitoring diodes,
Zener diodes and also specific customer modules if
supplied with direct current up to 50Vdc.
Part codes:
EOL (End of Line) device:
Resistor – ExxxR
Diode – ED1
Zener – ExxxZ
Series (In line) device:
Resistor – SxxxR
Diode – SD1
Zener – SxxxZ
LED
The unit can be wired with a maximum of 4 module
devices – see wiring schematic D233-06-001
When customer is fitting EOL or Series device
ensure device leads are insulated or routed so as
not to create an electrical short circuit.
The following table 1 shows limitations for all
devices.
Suggested EOL/
Series Device Type
Type of
component fitted
Value
End-of-Line
Resistor
330Ω
Suggested Min.
End-of-Line
Diode
Type 1N5401
2W
Series Resistor 330Ω
Suggested Min.
Series Zener
Diode Type
1N5333B
Suggested Sizes
3.3V
4.7V
5.1V
5.6V
6.2V
6.8V
10V
12V

Y
WIRE LINK N/C N/OCOM
87
M/S 1
654321
RB
Y
N/C
N/OCOM
EOL
SER
87
M/S 1
654321
RB
Y
N/C
N/OCOM
EOL
SER
87
M/S 1
654321
RB
Y
5
N/C N/OCOM
EOL
SER
87
M/S 1
64321
RB
Y
N/C N/OCOM
EOL
SER
87
M/S 1
654321
RB
-
N/C
-
N/C
-
-
N/OCOM
N/OCOM
DIODE
ZENER DIODE
POSITIVE (+) COMMON
(IF DIODES SUPPLIED & CONFIGURED BY E2S)
12345678
12345678
++
++ - -
-
N/O
--
--
++
++
87654321
87654321
POSITIVE (+) COMMON
(IF DIODES SUPPLIED & CONFIGURED BY E2S)
ZENER DIODE
DIODE
N/ON/C
-
COM
-
N/CCOM
N/O - Normally Open
Key:
COM - Common
N/C - Normally Closed
(Contacts closed in unoperated state)
(Contacts open in unoperated state)
5
EOL
SERIES
874
5
EOL
SERIES
874
Y
8
N/C N/O
WIRE LINK
7
COM
M/S 1
654321
RB
WP6 CALL POINTS
R.N.POTTS
2S
07-02-20
31NTS
D.A.H - 07-02-2020
WWW.E2S.COM
C
LONDON W3 7QH
ACTON
MANSELL ROAD
IMPRESS HOUSE
EUROPEAN SAFETY SYSTEMS LTD
WP6-BG WEATHERPROOF BREAK GLASS
MANUAL CALL POINT WIRING SCHEMATIC
IF IN DOUBT, ASK -
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
EUROPEAN SAFETY SYSTEMS LTD.
WRITTEN CONSENT.
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
LINEAR DIMENSIONAL TOLS
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D233-06-001
07-02-20
D.HOWGILL
R.N.POTTS
07-02-20
OF
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
INTRODUCTION
1
warning signals
E2S PART NO.
WP6-BG
DESCRIPTION
WP6-BG WEATHERPROOF BREAK GLASS MANUAL CALL POINT
1A - Circuit shown in Unoperated condition
(Glass Intact / Standby Condition)
Terminals (4,5) & (7,8) open
Terminals (4,5) & (6) closed
NOTE: Series / EOL devices can be fitted either by
customer or pre-installed by E2S at point of order.
polarity across devices must be observed
(Resistor polarity unimportant)
When fitting diodes or zener diodes,
Standard Unit as supplied by E2S
1B - Circuit shown in Operated condition
(Glass Broken / Button pushed in)
Standard Unit
Showing alternative configuration of optional Series / EOL Devices
Terminals (4,5) & (6) open
SWITCH TYPE: [S] - Single Microswitch
Terminals (4,5) & (7,8) closed
Wiring option shown with EOL &
series devices acting in parallel
Standard Unit
Showing positions of optional Series / EOL Devices
Wiring option shown with EOL &
series devices acting in series
Terminals (4,5) & (6) closed
Terminals (4,5) & (7,8) open
(Glass Intact / Standby Condition)
2A - Circuit shown in Unoperated condition
Terminals (4,5) & (6) open
Terminals (4,5) & (7,8) closed
(Glass Broken / Button pushed in)
2B - Circuit shown in Operated condition
Terminals (4,5) & (6) open
Terminals (4,5) & (7,8) closed
(Glass Broken / Button pushed in)
3B - Circuit shown in Operated condition
Terminals (4,5) & (6) closed
Terminals (4,5) & (7,8) open
(Glass Intact / Standby Condition)
(Resistor polarity unimportant)
WP6-BG[S]
polarity across devices must be observed
Without Series / EOL Devices
3A - Circuit shown in Unoperated condition
When fitting diodes or zener diodes,
NOTE: Series / EOL devices can be fitted either by
customer or pre-installed by E2S at point of order.
DATA REFERENCE
2-41-020

Y
LED
R1
N/C (-)
N/O (-)COM (+)
EOL
SER
87
M/S 1
654321
R
B
Y
LED
R1
R
N/C (-)
N/O (-)COM (+)
EOL
SER
87
M/S 1
654321
B
N/O
--
--++
++
87654321
87654321
POSITIVE (+) COMMON (AS SUPPLIED BY E2S)
ZENER DIODE
DIODE
-
N/C
-
-
COM N/O
N/C
COM
LED
BY
R
123456
M/S 1
78
COM (+) N/O (-)
N/C (-)
R1
Y
LED
R1
N/C (-)
N/O (-)COM (+)
87
M/S 1
654321
R
B
WP6 CALL POINTS
2S
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D233-06-001
D.HOWGILL
R.N.POTTS
R.N.POTTS
07-02-20
OF
WP6-BG WEATHERPROOF BREAK GLASS
MANUAL CALL POINT WIRING SCHEMATIC
INTRODUCTION
D.A.H - 07-02-2020
NTS 2 3
07-02-20
07-02-20
1
warning signals
Standard L.E.D Unit as supplied by E2S
Without series / EOL Devices
4A - Circuit shown in Unoperated condition
(Glass Intact / Standby Condition)
Terminals (4,5) & (7,8) open
Terminals (4,5) & (6) closed
4B - Circuit shown in Operated condition
(Glass Broken / Button pushed in)
Terminals (4,5) & (7,8) closed
Terminals (4,5) & (6) open
5B - Circuit shown in Operated condition
(Glass Broken / Button pushed in)
Terminals (4,5) & (7,8) closed
Terminals (4,5) & (6) open
5A - Circuit shown in Unoperated condition
(Glass Intact / Standby Condition)
Terminals (4,5) & (7,8) open
Terminals (4,5) & (6) closed
WP6-BG[S].....[L] SWITCH TYPE: [S] - Single Microswitch LED OPTION: [L] - LED Included
When fitting diodes or zener diodes,
polarity across devices must be observed
Note: LED is configured by E2S
and the polarity must be observed.
Use positive (+) common when wiring
into the call point
Standard L.E.D Unit
Showing optional series / EOL devices
NOTE: Series / EOL devices can be fitted either by
customer or pre-installed by E2S at point of order.

N/O
POSITIVE COMMON
(IF DIODES SUPPLIED & CONFIGURED BY E2S)
ZENER DIODE
DIODE
+--
+
+--
+
N/CN/C
87654321
N/CN/C
87654321
COM
--
N/O N/OCOM
N/O
--
COMN/OCOM
N/O
--
COMCOM
1
M/S 2M/S 1
N/CN/C
N/O
COM
EOL
N/O
YBRYB
M/S 2
COM
EOL
87
M/S 1
65432
R
2
M/S 2M/S 1
N/CN/C
N/O
COM
EOL
N/O
YBRYB
M/S 2
COM
EOL
M/S 1
R
8765431
WP6 CALL POINTS
2S
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D233-06-001
D.HOWGILL
R.N.POTTS
R.N.POTTS
07-02-20
OF
WP6-BG WEATHERPROOF BREAK GLASS
MANUAL CALL POINT WIRING SCHEMATIC
INTRODUCTION
D.A.H - 07-02-2020
NTS 3 3
07-02-20
07-02-20
1
warning signals
Standard Dual Switch Unit
Showing optional EOL devices
6A - Circuit shown in Unoperated condition
(Glass Intact / Standby Condition)
M/S1: Terminals 1 & 4 open. MS/2: Terminals 5 & 8 open.
M/S1: Terminals 1 & 3 closed. M/S2: Terminals 5 & 7 closed.
6B - Circuit shown in Operated condition
(Glass Broken / Button pushed in)
M/S1: Terminals 1 & 4 closed. MS/2: Terminals 5 & 8 closed.
M/S1: Terminals 1 & 3 open. M/S2: Terminals 5 & 7 open.
SWITCH TYPE: [D] - Dual Microswitch
WP6-BG[D]
When fitting diodes or zener diodes,
polarity across devices must be observed
(Resistor polarity unimportant)
Other wiring configurations are available pre-configured
(e.g. Dual switch configured with series and EOL devices)
Contact E2S Sales for special wiring requests
Special Wiring Unit
Single or Dual Switch with wiring to customer request
WP6-BG[X] SWITCH TYPE: [X] - Special Order
NOTE: EOL devices can be fitted either by customer
or pre-installed by E2S at point of order.

E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: [email protected] www.e2s.com DC-081_Issue_C Page 1 of 1 QAF_252_Issue_5
Martin Streetz Document No.: DC-081_Issue_C
Quality Assurance Manager Date and Place of Issue: London, 23/11/2022
EU & UKCA Declaration of Conformity
Manufacturer: European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH
United Kingdom
Authorised Representative: E2S Warnsignaltechnik UG
Charlottenstrasse 45-51
72764 Reutlingen
Germany
Equipment Type: WP3-BG,
WP6-PB,
WP7-PB, WP7-PT, WP7-PM
Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN 61000
-
6
-
1:2007
EN 61000-6-2:2005
EN 61000-6-3:2007 / A1:2011 / AC: 2012
EN 61000-6-4:2007 / A1:2011
Directive 2006/95/EC (until 19th April 2016) / Directive 2014/35/EU (from 20th April 2016): Low Voltage Directive (LVD)
Standards applied:
EN
60947
-
1:2007+A2:2014
Directive 2011/65/EU: Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS)
The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic
equipment, including amendment by Directive 2015/863/EU.
Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH)
The product and all the components contained within it are free from substances of very high concern.
Other Standards and Regulations
EN 60529:1992+A2:2013 - Degrees of protection provided by enclosures (IP code) – enclosure rated IP66
On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment
conforms with all technical and regulatory requirements of the above listed directives, regulations and standards.
This Declaration is issued under the sole responsibility of the manufacturer.
This manual suits for next models
1
Other E2S Security System manuals

E2S
E2S BExCP3C-PB User manual

E2S
E2S BExCBG05-05D User manual

E2S
E2S GNExS1 User manual

E2S
E2S BExBG05D User manual

E2S
E2S STExB2X05DC012 User manual

E2S
E2S D1xS2 Series User manual

E2S
E2S GNExS1FDC024-S User manual

E2S
E2S GNExCP6B-PT User manual

E2S
E2S D2xB1XH1 User manual

E2S
E2S D1xB2X05 Series User manual

E2S
E2S D1*CP1-PS Series User manual

E2S
E2S D1 B2LD2 Series User manual

E2S
E2S D2 C2X05DC024 Series User manual

E2S
E2S D1xS1FDC024-S User manual

E2S
E2S SONFL1XDC012 User manual

E2S
E2S GNExCP6C-PT User manual

E2S
E2S D2xC1 Troubleshooting guide

E2S
E2S D2xB1LD2DC024 User manual

E2S
E2S BExS120D User manual

E2S
E2S D105AX User manual