E2S D1 B2LD2 Series User manual

INSTRUCTION MANUAL
D1xB2LD2
LED Beacon
For use in Hazardous Locations
E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D191-00-401-IS
Issue 3
28-11-22 Sheet 1 of 6
D1xB2LD2
1) Warnings
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
DO NOT PAINT
TO REDUCE THE RISK OF IGNITION OF
HAZARDOUS ATMOSPHERES, THE FIRST
CONDUIT RUN MUST HAVE A SEALING
FITTING CONNECTED WITHIN 18 INCHES
OF ENCLOSE. SUBSEQUENT CONDUIT
RUNS MUST HAVE A SEALING FITTING
CONNECTED AS CLOSE AS PRACTICAL TO
THE WALL OF THE ENCLOSURE, BUT IN
NO CASE MORE THAN THE SIZE OF THE
CONDUIT OR 50MM, WHICHEVER IS THE
LESSER.
TO PREVENT IGNITION OF GROUP A, B, C
AND D ATMOSPHERES - SEE
INSTRUCTION FOR CHEMICAL
COMPATIBILITY
Avertissement:
NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
NE PAS PEINTURER
POUR RÉDUIRE LE RISQUE
D'INFLAMMATION DES ATMOSPHÈRES
DANGEREUSES, LE PREMIER CONDUIT DE
CONDUIT DOIVENT AVOIR UN RACCORD
D'ÉTANCHÉITÉ RACCORDÉ À MOINS DE 18
POUCES DE L'ENFERMEMENT. POUR
SUBSÉQUENT LES CONDUITES DE
CONDUIT LA DISTANCE ENTRE LA
SURFACE DE LA MASSE DE REMPLISSAGE
AU PLUS PRÈS DE L’ENVELOPPE DOIT
ÊTRE AUSSI PETITE QUE CE QUI EST
RÉALISABLE MAIS EN AUCUN CAS
SUPÉRIEURE À LA PLUS PETITE DES
DIMENSIONS CORRESPONDANT À LA
TAILLE DU CONDUIT OU À 50 MM.
POUR PRÉVENIR L'INFLAMMATION DES
ATMOSPHÈRES DES GROUPES A, B, C ET
D-VOIR L'INSTRUCTION POUR LA
COMPATIBILITÉ CHIMIQUE
2) Rating & Marking Information
2.1 NEC & CEC Class / Division Ratings for US /
Canada
The D1xB2LD2 LED beacons comply with the following
standards:
UL 1203 (Ed. 5) 2015
CSA C22.2 No. 30-M1986 (Ed. 1) 2003
CSA C22.2 No. 25 (Ed. 4) 2017
CSA C22.2 No. 205 (Ed. 3) 2017
The D1xB2LD2 LED Beacon is rated as follows:
Class I Div 1 Group ABCD T5 Ta -55°C to +80°C
Class I Div 1 Group ABCD T6 Ta -55°C to +75°C
Class II Div 1 Group EFG T5 Ta -55°C to +80°C
Class III Div 1 Ta -55°C to +80°C
Installation must be carried out in compliance with the
National Electric Code / Canadian Electric Code

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D191-00-401-IS
Issue 3
28-11-22 Sheet 2 of 6
2.2 NEC Class / Zone ratings US
The D1xB2LD2 LED beacons comply with the following
standards:
UL 60079-0-2013
UL 60079-1-2015
UL 60079-31-2015
The D1xB2LD2 LED Beacon is rated as follows:
Class I Zone 1 AEx db IIC T5 Ta -55°C to +80°C
Class I Zone 1 AEx db IIC T6 Ta -55°C to +70°C
Zone 21 AEx tb IIIC T100°C Ta -55°C to +80°C
Installation must be carried out in compliance with the
National Electric Code.
2.3 CEC Class / Zone ratings Canada
The D1xB2LD2 LED beacons comply with the following
standards:
CAN/CSA C22.2 No. 60079-0-2015
CAN/CSA C22.2 No. 60079-1-2016
CAN/CSA C22.2 No. 60079-31-2015
The D1xB2LD2 LED Beacon is rated as follows:
Ex db IIC T5 Ta -55°C to +80°C
Ex db IIC T6 Ta -55°C to +70°C
Ex tb IIIC T100°C Ta -55°C to +80°C
Installation must be carried out in compliance with the
Canadian Electric Code
2.4 ATEX / IECEx & UKEx Certification
The D1xB2LD2 LED beacons comply with the following
standards:
EN IEC60079-0:2018 / IEC60079-0:2017 (Ed 7)
EN60079-1:2010 / IEC60079-1: ed. 7.0 (2014-06)
EN60079-31:2014 / IEC60079-31:2013 ed. 2.0 (2013-11)
The D1xB2LD2 LED Beacon is rated as follows:
Ex db IIC T5 Gb Ta -55°C to +80°C
Ex db IIC T6 Gb Ta -55°C to +70°C
Ex tb IIIC T100°C Db Ta -55°C to +80°C
For D1xB2LD2AC230 units, the certification approval has
validated continuous use up to 38°C ambient and are for
transient use up to 80°C ambient
Certificate No. DEMKO 19 ATEX 2009X
IECEx ULD 19.0006X
UL21UKEX2130X
ATEX Mark,
Equipment Group and
Category:
II 2G
II 2D
CE Marking and
Notified Body No.
2813
UKCA Marking and
Notified Body No.
0518
The units can be installed in locations with the following
conditions:
Area Classification Gas:
Zone 1 Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur in
normal operation, and if it does, it will only exist
for a short time.
Gas Groupings:
Group IIA Propane
Group IIB Ethylene
Group IIC Hydrogen and Acetylene
Temperature Classification:
T1 450ºC
T2 300ºC
T3 200ºC
T4 135ºC
T5 100ºC
T6 85ºC (up to 70°C ambient)
Dust Groupings:
Group IIIA Combustible Flyings
Group IIIB Non-conductive Dust
Group IIIC Conductive Dust
Maximum Surface Temperature for Dust Applications:
100ºC
Equipment Category: 2G / 2D
Equipment Protection Level: Gb, Gc, Db, Dc
Ambient Temperature Range: -55°C to +80°C
2.5 Ingress Protection Ratings
The product is rated for ingress Protection as follows:
IP rating
per EN60529: IP66
Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13
Suitable for exposure to Acetone , Ammonium Hydroxide ,
Diethyl Ether , Ethyl Acetate , Ethylene Dichloride , Furfural,
n-hexane , Methyl Ethyl Ketone , Methanol , 2-NitroPropane
and Toluene.
To maintain the ingress protection rating, the cable entries
must be fitted with suitably rated, certified cable entry and/or
blanking devices during installation.

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D191-00-401-IS
Issue 3
28-11-22 Sheet 3 of 6
252.3 [9.93in]
7.00 [0.28in]
45.0°
3/4" NPT SIDE ENTRY
2 OFF POSITIONS
MARKED *
M20x1.5 SIDE ENTRY
2 OFF POSITIONS
MARKED #
3/4" NPT BOTTOM ENTRY
FOR POLE MOUNTING
BEACON
2 OFF FEET SUPPLIED IN STOWED POSITION
SUITABLE FOR POLE OR BRACKET
MOUNTING BEACON
RETAINED BY 2 OFF M5 SCREWS PER FOOT
166.0 [6.54in]
83.0 [3.27in]
2 OFF FEET SUPPLIED IN STOWED POSITION
SUITABLE FOR POLE OR BRACKET
MOUNTING BEACON
RETAINED BY 2 OFF M5 SCREWS PER FOOT
BASE CONFIGURED WITH
FEET SET OUT FOR SURFACE MOUNTING
BEACON
Ø9.0 [Ø0.36in]
Flame Path internal thread on
base shown hatched
Cemented Joint
between glass
dome and metal
casting on lid
shown hatched
Flame Path external thread
on lid shown hatched
2.6 Electrical Ratings
#
Rated at 1Hz
Table 1: Electrical Ratings
It is important that a suitable power supply is used to run the
equipment. The power supply selected must have the
necessary capacity to provide the input current to all the units.
The input current will vary according to the voltage input level.
3) Special Conditions of Use
The enclosure coating is non-conductive and may generate an
ignition-capable level of electrostatic charges under certain
extreme conditions. The user should ensure that the
equipment is not installed in a location where it may be
subjected to external conditions (such as high pressure steam)
which might cause a build-up of electrostatic charges on non-
conducting surfaces. Additionally, cleaning of the equipment
should be done only with a damp cloth.
4) Installation
There are no restrictions on unit orientation.
The junction box must only be installed by suitably qualified
personnel in accordance with the latest issues of the relevant
standards:
EN60079-14 / IEC60079-14: Explosive atmospheres -
Electrical installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive
atmospheres - Classification of areas. Explosive gas
atmospheres
EN60079-10-2 / IEC60079-10-2: Explosive
atmospheres - Classification of areas. Explosive dust
atmospheres
The installation of the units must also be in accordance with
any local codes that may apply and should only be carried out
by a competent electrical engineer who has the necessary
training.
4.1 Safe Installation Requirements:
To maintain the ingress protection rating and mode of
protection, the cable entries must be fitted with suitably
certified cable entry and/or blanking devices during
installation. If conduit is used for installation, seal conduit
within 18 inches from the first enclosure, subsequent conduit
runs must have a sealing fitting connected as close as practical
to the wall of the enclosure, but in no case more than the size
of the conduit or 50mm, whichever is the lesser.
If entries are fitted with adaptors they must be suitably certified
for the application. Fitting of blanking elements into adaptors
is not permitted.
Check that the ‘O’ ring seal is in place before replacing the
explosionproof cover.
Lens guard must be fitted for Class Division installations.
5) Location and Mounting
The location of the beacon should be made with due regard to
the area over which the warning signal must be visible. It
should only be fixed to services that can carry the weight of the
unit.
The D1xB2LD2 beacon can be mounted using one of three
methods.
1. The beacon can be surface mounted by removing,
rotating and reinstalling the stowed mounting lugs. These
are suitable for 6mm diameter fixings.
a. Remove 2 x M5 fasteners per
mounting lug
b. Reverse and rotate lug and
reseat onto enclosure
c. Secure lug using the 2 x M5
Fasteners
2. Alternatively the beacon can be conduit mounted using
the 3/4”NPT entry on the base of the unit.
3. Additionally, the beacon can be mounted using the ratchet
adjustable stainless-steel wall bracket assembly. This is
available as an accessory – part code: SP77-0001.
Fig. 1 Fixing Location for Beacon
Model
D1xB2
Nom.
Voltage
Voltage
Range
Nom.
operating
current
#
Max.
Operating
Current
LD2DC024 24Vdc 18-30Vdc 230mA 500mA
LD2AC115 115Vac 110-120Vac 95mA 180mA
LD2AC230 230Vac 220-240Vac 50mA 100mA

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D191-00-401-IS
Issue 3
28-11-22 Sheet 4 of 6
- - + +S2 S3
E E N N L L
6) Access to the Enclosure
In order to connect the electrical supply cables to the beacon,
it is necessary to open the explosion proof enclosure. Loosen
the locking grub screw in the cover and then remove the
glass dome cover assembly to gain access to the chamber.
This can be achieved by unscrewing the glass dome cover,
taking extreme care not to damage the threads when doing
so.
Fig. 2 Accessing the Enclosure.
On completion of the installation the flameproof threads should
be inspected to ensure that they are clean and that they have
not been damaged during installation. Ensure the O-ring seal
is in place and undamaged.
When fitting the flameproof cover ensure the thread is
engaged correctly. Fully tighten the cover all the way, ensure
no gap is visible between the cover and base of the beacon
enclosure.
7) Selection of Cable, Cable Glands, Blanking
Elements & Adapters
When selecting the cable size, consideration must be given to
the input current that each unit draws (see section 12), the
number of beacons on the line and the length of the cable runs.
The cable size selected must have the necessary capacity to
provide the input current to all of the beacons connected to the
line.
The entries are 2-off M20 x 1.5 thread & 3-off ¾” NPT thread
If a high IP (Ingress Protection) rating is required then a
suitable sealing washer must be fitted under the cable glands
or blanking plugs.
For use in explosive dust atmospheres, a minimum ingress
protection rating of IP6X must be maintained.
For use in explosive gas atmospheres, a minimum ingress
protection rating of IP54 must be maintained.
NPT plugs should be greased before insertion.
For high ambient temperatures the cable entry temperature
or the cable branching point temperature may exceed 60ºC
and therefore suitable heat resisting cables and cable glands
must be used, with a rated service temperature of at least the
values stated below:
Max Ambient
temperature (°C) 50 55 60 65 70 75 80
Req. cable gland
rating (°C) 65 70 75 80 85 90 95
8) Cable Connections
The units have 2-off M20 x 1.5 threaded entries and 3-off ¾”
NPT x 14 threaded entries.
Electrical Connections are to be made into the terminal blocks
using solid or stranded wire, sizes 0.5-2.5mm2 / AWG 20-14.
Wire insulation needs to be stripped 6-7mm. Wires may be
fitted securely with crimped ferrules. Terminal screws need to
be tightened down with a tightening torque of 0.4 Nm / 3.5 Lb-
in.
See section 5 of this manual for access to the enclosure.
9) Wiring
A 6-way terminal block is provided on the beacons for power.
The DC units have 2-off +ve, 2-off –ve, a stage 2, a stage 3
and an Earth terminal.
See Schematic diagram D191-06-401.
Fig. 4 D1xB2LD2DC024 Terminals
The AC units have 2-off Live, 2-off Neutral and 2-off Earth
terminals.
See Schematic diagram D191-06-405.
Fig. 6 D1xB2LD2AC Terminals
Glass dome
cover
Warning – High voltage may be present,
risk of electric shock. DO NOT open when
energised, disconnect power before
opening.
Warning –
Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.
3/4" NPT
Entry
M20 Entry
3/4" NPT
Conduit
Entr
y

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D191-00-401-IS
Issue 3
28-11-22 Sheet 5 of 6
Fig. 8 Dip Switch
1=ON; 0=OFF
Example shown:
100000 = Flashing 1Hz
(Default setting)
9.1 Line Monitoring
On the D2xB1X unit, DC reverse line monitoring can be used
if required.
All DC beacons have a blocking diode fitted in their supply
input lines. An end of line monitoring resistor can be connected
across the +ve and –ve terminals in the explosion proof
enclosure. If an end of line resistor is used it must have the
following values:
Minimum resistance 3K3 Ohms Minimum Power 0.5W
Minimum resistance 500 Ohms Minimum Power 2.0W
The resistor must be connected directly across the +ve and
-ve terminals as shown in the following drawing. Form the
resistor legs as shown in Fig. 7a, fit the resistor across the two
terminals, as shown in Fig. 7b.
Fig. 7a End of Line Resistor Forming
Fig. 7b End of Line Resistor Placement
10) Settings
10.1 Flash Rate Setting
The D1xB2LD2 beacon can produce different flash patterns as
shown in Table 1. The flash patterns are selected by operation
of the flash setting DIP switch on the PCB, Fig 8.
Switch
Setting S1 Mode S2 Mode S3 Mode
(123456)
000000 Steady High Power Flashing 1Hz Flashing Triple Strike
000001 Steady Low Power Flashing 1Hz Flashing Triple Strike
100000 Flashing 1Hz Flashing Double Strike Flashing Triple Strike
101000 Flashing 1.5Hz Flashing 2Hz Flashing Double Strike
010000 Flashing 2Hz Flashing Triple Strike Flashing Triple Strike
110000 Flashing Double Strike Steady High Power Flashing Triple Strike
001000 Flashing Triple Strike Flashing 2Hz Flashing Double Strike
Fig. 8 DIP Switch location
11) Earthing
The unit has an external and an internal earth terminal, (please
see fig 9).
Please note that for AC supply voltage product versions the
Earth terminal on the PCBA does not provide an earth
connection to the product enclosure. The enclosure must be
independently earthed using either the external or internal
earth fixing point, (see fig 9 and notes below).
Internal earthing connections should be made to the internal
Earth terminal in the base of the housing using a ring crimped
terminal to secure the earth conductor under the earth clamp.
The earth conductor should be at least equal in size and rating
to the incoming power conductors.
External earthing connections should be made to the M5 earth
stud, using a ring crimp terminal to secure the earth conductor
to the earth stud. The external earth conductor should be at
least 4mm
”
in size.
Fig. 9: Internal & External Earth Locations
End of Line
Resisto
r
Warning – high-intensity light source. Avoid
looking directly at the light source for
extended periods of time.
External Earth
Stud
Internal Earth
Terminal

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D191-00-401-IS
Issue 3
28-11-22 Sheet 6 of 6
12) Maintenance, Overhaul & Repair
Maintenance, repair and overhaul of the equipment should
only be carried out by suitably qualified personnel in
accordance with the current relevant standards:
EN60079-19 / IEC60079-19 Explosive atmospheres -
Equipment repair, overhaul and reclamation
EN 60079-17 / IEC60079-17 Explosive atmospheres -
Electrical installations inspection and maintenance
To avoid a possible ELECTROSTACTIC CHARGE the unit
must only be cleaned with a damp cloth.
Units must not be opened while an explosive atmosphere is
present.
If opening the unit during maintenance operations a clean
environment must be maintained and any dust layer removed
Flameproof joints are not intended to be repaired.
13) Interchangeable & Spare Parts
The Beacon lens cover is interchangeable, contact E2S Ltd for
a replacement lens cover available in various colours.
To change the lens cover, unscrew the 4-off M5 socket head
screws, spring and flat washers using a 4mm Hex key.
Remove the wire guard and replace the old lens cover with the
new lens cover.
Fig. 10 Replacement of beacon lens cover
Fit the wire guard back onto the housing, over the new lens
cover aligning the fixing holes of the guard, lens cover and
housing. Refit the fixings to hold into place, the fixings MUST
be fitted in the order shown above.
14) SIL 2 Reliability Data
Reliability and Functional safety IEC/EN61508 which has
been assessed and is considered suitable for use in low
demand safety function:
1. Random Hardware Failures and Architectural constraints
(route
2
H
).
2. As an unvoted item (i.e. hardware fault tolerance of 0) at
SIL 2.
The product was assessed against failure modes:
Failure respond to an input by lighting a beacon.
Spurious light output despite no input.
3. When employing the device in a SIL2 compliant system
the user should ensure frequent or continuous automatic
monitoring of continuity.
Integrity in respect of failure to
function
SIL2
& SIL1
Total Failure rate 0.
48
pmh
“Hazardous” failure rate (revealed)
0
pmh
“Hazardous” failure rate (unrevealed) 0.
48
pmh
“Safe” failure rate (revealed) 0 pmh
“Safe” failure rate (unrevealed) 0
System type B
Hardware Fault Tolerance 0
Dia
g
nostic Covera
g
e
>
60
%
PFD (hazardous failure)
2.1
x 10
-
3
Proof Test Interval Up to 1 year
Warning –
Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.
M5 screw
M5 spring washer
M5 flat washe
r

Page left Intentionally blank

warning signals
2S
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D191-06-401
R.N.POTTS OF
D1xB2 LD2 BEACON
NTS 1 1
AINTRODUCTION
RSR - 28/11/22
D1xB2 LD2
R.N.POTTS WIRING DIAGRAMS
Stage 3
R1
-
-
S2
S3
DC LED D1xB2LD2 UNITS
Line Monitoring
Power: +ve & -ve
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
RECOMMENDED MINIMUM VALUES:
R1
500Ω MIN, 2W MIN OR 3K3Ω MIN, 0.5W MIN
+
+
Stage 2
-ve IN
-ve OUT
+ve OUT
+ve IN L
L
Neutral IN
Neutral OUT
Live OUT
Live IN
Earth
Earth
N
N
E
E
AC LED D1xB2LD2 UNITS
Power: Live & Neutral
R. RAIT 28/11/22
28/11/22
28/11/22

Page left Intentionally blank

E2STelephone:+44(0)2087438880Fax:+44(0)2087404200Email:[email protected]www.e2s.comDC‐077_Issue_E‐Page1of1‐QAF_252_Issue_5
MartinStreetzDocumentNo.:DC‐077_Issue_E
QualityAssuranceManagerDateandPlaceofIssue:London,07/07/2022
EUDeclarationofConformity
Manufacturer: EuropeanSafetySystemsLtd.
ImpressHouse,MansellRoad,Acton
London,W37QH
UnitedKingdom
AuthorisedRepresentative:E2SWarnsignaltechnikUG
Charlottenstrasse45‐51
72764Reutlingen
Germany
EquipmentType: D1xB2X05,D1xB2X10,D1xB2X15,D1xB2X21,D1xB2LD2,D1xJ2
Directive2014/34/EU:EquipmentandProtectiveSystemsforuseinPotentiallyExplosiveAtmospheres(ATEX)
NotifiedBodyforEUtypeExamination(ModuleB):ULInternationalDemkoA/S
NotifiedBodyNo.:0539
Borupvang5A,2750Ballerup,Denmark
EU‐typeExaminationCertificate(ModuleB):DEMKO19ATEX2009XRev.1
NotifiedBodyforQualityAssuranceNotification/ConformitytoEU‐type
basedon
qualityassuranceoftheproductionprocess(ModuleD):
SiraCertificationService
NotifiedBodyNo.:2813
CSAGroupNetherlandsB.V,Utrechtseweg310,6812AR,Arnhem,Netherlands
QualityAssuranceNotification(ModuleD):SIRA05ATEXM342
Provisionsfulfilledbytheequipment:II2GExdIICT6…T3Gb
II2DExtbIIICT95°C…T169°CDb
Standardsapplied:EN60079‐0:2018
EN60079‐1:2014
EN60079‐31:2014
IP6XDustProtectiontoEN60079‐0/EN60079‐31
Directive2014/30/EU:ElectromagneticCompatibilityDirective(EMC)
Standardsapplied:ENIEC61000‐6‐1:2019&IEC61000‐6‐1:2016
ENIEC61000‐6‐2:2019&IEC61000‐6‐2:2016
ENIEC61000‐6‐3:2021&IEC61000‐6‐3:2020
ENIEC61000‐6‐4:2019&IEC61000‐6‐4:2018
Directive2011/65/EU:Restrictionoftheuseofcertainhazardoussubstancesinelectricalandelectronicequipment(RoHS)
Theproductandallthecomponentscontainedwithinitareinaccordancewiththerestrictionoftheuseofhazardoussubstancesinelectricalandelectronic
equipment,includingamendmentbyDirective2015/863/EU.
Regulation(EC)1907/2006:Registration,Evaluation,AuthorisationandRestrictionofChemicals(REACH)
Theproductandallthecomponentscontainedwithinitarefreefromsubstancesofveryhighconcern.
OtherStandardsandRegulations
EN60529:1991+A1:2000+A2:2013.‐Degreesofprotectionprovidedbyenclosures(IPcode)–enclosureratedIP66/67
OnbehalfofEuropeanSafetySystemsLtd.,Ideclarethat,onthedatetheequipmentaccompaniedbythisdeclarationisplacedonthemarket,theequipment
conformswithalltechnicalandregulatoryrequirementsoftheabovelisteddirectives,regulationsandstandards.
ThisDeclarationisissuedunderthesoleresponsibilityofthemanufacturer.

E2STelephone:+44(0)2087438880Fax:+44(0)2087404200Email:[email protected]www.e2s.com DC‐096_Issue_A‐Page1of1‐QAF_252_Issue_5
MartinStreetz DocumentNo.: DC‐096_Issue_A
QualityAssuranceManager DateandPlaceofIssue: London,24/02/2022
UKCADeclarationofConformity
Manufacturer: EuropeanSafetySystemsLtd.
ImpressHouse,MansellRoad,Acton
London,W37QH
UnitedKingdom
EquipmentType: D1xB2X05,D1xB2X10,D1xB2X15,D1xB2X21,D1xB2LD2,D1xJ2
DirectiveUKSI2016:1107(asamendedbyUKSI2019:696)–Schedule3A,Part1:ProductorProtectiveSystemIntendedforuseinPotentiallyExplosiveAtmospheres
(UKCA)
NotifiedBodyforUKtypeExamination(ModuleB): ULInternational(UK)Ltd
NotifiedBodyNo.:0843
Unit1‐3HorizonKingslandBusinessPark,WadeRoad,
Basingstoke,HampshireRG248AHUK
UK‐typeExaminationCertificate(ModuleB): UL21UKEX2130X
NotifiedBodyforQualityAssuranceNotification/ConformitytoEU‐type
basedon
qualityassuranceoftheproductionprocess(ModuleD):
SiraCertificationService
NotifiedBodyNo.:0518
RakeLane,Eccleston,ChesterCH49JN,UK
QualityAssuranceNotification(ModuleD): CSAE22UKQAN0046
Provisionsfulfilledbytheequipment: II2GExdIICT6…T3Gb
II2DExtbIIICT95°C…T169°CDb
Standardsapplied: EN60079‐0:2018
EN60079‐1:2014
EN60079‐31:2014
IP6XDustProtectiontoEN60079‐0/EN60079‐31
Directive2014/30/EU:ElectromagneticCompatibilityDirective(EMC)
Standardsapplied: EN61000‐6‐1:2007
EN61000‐6‐2:2005
EN61000‐6‐3:2007/A1:2011/AC:2012
EN61000‐6‐4:2007/A1:2011
Directive2011/65/EU:Restrictionoftheuseofcertainhazardoussubstancesinelectricalandelectronicequipment(RoHS)
Theproductandallthecomponentscontainedwithinitareinaccordancewiththerestrictionoftheuseofhazardoussubstancesinelectricalandelectronic
equipment,includingamendmentbyDirective2015/863/EU.
Regulation(EC)1907/2006:Registration,Evaluation,AuthorisationandRestrictionofChemicals(REACH)
Theproductandallthecomponentscontainedwithinitarefreefromsubstancesofveryhighconcern.
OtherStandardsandRegulations
EN60529:1991+A1:2000+A2:2013.‐Degreesofprotectionprovidedbyenclosures(IPcode)–enclosureratedIP66/67
OnbehalfofEuropeanSafetySystemsLtd.,Ideclarethat,onthedatetheequipmentaccompaniedbythisdeclarationisplacedonthemarket,theequipment
conformswithalltechnicalandregulatoryrequirementsoftheabovelisteddirectives,regulationsandstandards.
ThisDeclarationisissuedunderthesoleresponsibilityofthemanufacturer.

Page left Intentionally blank
This manual suits for next models
3
Table of contents
Other E2S Security System manuals

E2S
E2S IS-CP4B-PT User manual

E2S
E2S BExBG15D-P-SIL User manual

E2S
E2S GNExCP7-BG-S User manual

E2S
E2S BexCS11005D24DC-RD User manual

E2S
E2S GNExB2LD2 User manual

E2S
E2S D1xB2X05 Series User manual

E2S
E2S E2xC1LD2R User manual

E2S
E2S IS-D105 User manual

E2S
E2S AlertAlight DL105X User manual

E2S
E2S BExCBG05-05D User manual
Popular Security System manuals by other brands

Watchguard
Watchguard DVR4E(PACK) Quick installation guide

Lifemax
Lifemax The Friends & Family Home Safety Alert instructions

Paradox
Paradox Esprit 727 Installation instructions manual

Abus
Abus TVAC15000 user manual

Activeforever
Activeforever AquaGuard owner's manual

Co2meter
Co2meter CM-1029 installation manual