E2S D1xB2X05 Series User manual

INSTRUCTION MANUAL
D1xB2X05, D1xB2X10, D1xB2X15 & D1xB2X21
Xenon Beacons
For use in Hazardous Locations
E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D191-00-201-IS
Issue 3
28-11-22 Sheet 1 of 9
D1xB2X05
D1xB2X10
D1xB2X15
D1xB2X21
1) Warnings
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
DO NOT PAINT
TO REDUCE THE RISK OF IGNITION OF
HAZARDOUS ATMOSPHERES, THE FIRST
CONDUIT RUN MUST HAVE A SEALING
FITTING CONNECTED WITHIN 18 INCHES
OF ENCLOSE. SUBSEQUENT CONDUIT
RUNS MUST HAVE A SEALING FITTING
CONNECTED AS CLOSE AS PRACTICAL TO
THE WALL OF THE ENCLOSURE, BUT IN
NO CASE MORE THAN THE SIZE OF THE
CONDUIT OR 50MM, WHICHEVER IS THE
LESSER.
TO PREVENT IGNITION OF GROUP A, B, C
AND D ATMOSPHERES - SEE
INSTRUCTION FOR CHEMICAL
COMPATIBILITY
Avertissement:
NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
HAUT TENSION, RISK DE CHOC.
ATTENDEZ 5 MINUTES APRES AVOIR
DEBRANCHE L’ALIMENTATION AVANT
D’OUVRIR LA BOITIER
NE PAS PEINTURER
POUR RÉDUIRE LE RISQUE
D'INFLAMMATION DES ATMOSPHÈRES
DANGEREUSES, LE PREMIER CONDUIT DE
CONDUIT DOIVENT AVOIR UN RACCORD
D'ÉTANCHÉITÉ RACCORDÉ À MOINS DE 18
POUCES DE L'ENFERMEMENT. POUR
SUBSÉQUENT LES CONDUITES DE
CONDUIT LA DISTANCE ENTRE LA
SURFACE DE LA MASSE DE REMPLISSAGE
AU PLUS PRÈS DE L’ENVELOPPE DOIT
ÊTRE AUSSI PETITE QUE CE QUI EST
RÉALISABLE MAIS EN AUCUN CAS
SUPÉRIEURE À LA PLUS PETITE DES
DIMENSIONS CORRESPONDANT À LA
TAILLE DU CONDUIT OU À 50 MM.
POUR PRÉVENIR L'INFLAMMATION DES
ATMOSPHÈRES DES GROUPES A, B, C ET
D-VOIR L'INSTRUCTION POUR LA
COMPATIBILITÉ CHIMIQUE
2) Rating & Marking Information
2.1 Fire Alarm Ratings
The Following models are certified as visual alarm devices for
fire alarm use – private mode visual alarm devices in
accordance with UL1638 / CAN/ULC-S526 when used with
Clear or Red lens covers:
D1xB2X05DC024 / D1xB2X10DC024 / D1xB2X15DC024 /
D1xB2X21DC024
On-axis light output per UL1638:
Model
D1XB2
Light Intensity in cd
Clear Lens Red Lens
X05DC024 - 1Hz 20.44 5.89
X05DC024 - 1.33Hz 14.47 4.17
X05DC024 - 1.5Hz 11.1 2.13
X10DC024 - 1Hz 69.81 23.66
X10DC024 - 1.33Hz 49.42 16.75
X10DC024 - 1.5Hz 35.71 8.57
X15DC024 - 1Hz 98.61 31.83
2X15DC024 - 1.33Hz 69.81 22.53
X15DC024 - 1.5Hz 50.44 11.53
X21DC024 - 1Hz 215.85 70.74
X21DC024 - 1.33Hz 155.12 50.84
X21DC024 - 1.5Hz 137.47 45.05

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D191-00-201-IS Issue 3 28-11-22 Sheet 2 of 9
2.2 Surge Current Ratings for use in Fire Alarm
Systems
2.3 NEC & CEC Class / Division Ratings for US /
Canada
The D1xB2X Xenon beacons comply with the following
standards:
UL 1203 (Ed. 5) 2018
UL1638A (Ed. 1) 2016
UL1638 (Ed. 5) 2017
CSA C22.2 No. 30-M1986 (Ed. 3) 2016
CSA C22.2 No. 25 (Ed. 4) 2017
CSA C22.2 No. 205 (Ed. 3) 2017
The D1xB2X05DC012, D1xB2X05DC024 &
D1xB2X05DC048 Xenon Beacons are rated as follows:
Class I Div 1 Group ABCD T5 Ta -55°C to +80°C
Class I Div 1 Group ABCD T6 Ta -55°C to +65°C
Class II Div 1 Group EFG T5 Ta -55°C to +80°C
Class III Div 1 Ta -55°C to +80°C
The D1xB2X05AC115 & D1xB2X05AC230 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T4A Ta -55°C to +70°C
Class I Div 1 Group ABCD T5 Ta -55°C to +55°C
Class I Div 1 Group ABCD T6 Ta -55°C to +40°C
Class II Div 1 Group EFG T4 Ta -55°C to +40°C
Class III Div 1 Ta -55°C to +40°C
The D1xB2X10DC024 & D1xB2X10DC048 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T4 Ta -55°C to +80°C
Class I Div 1 Group ABCD T4A Ta -55°C to +70°C
Class I Div 1 Group ABCD T5 Ta -55°C to +50°C
Class II Div 1 Group EFG T4 Ta -55°C to +80°C
Class III Div 1 Ta -55°C to +80°C
The D1xB2X10AC115 & D1xB2X10AC230 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T4 Ta -55°C to +70°C
Class I Div 1 Group ABCD T4A Ta -55°C to +55°C
Class II Div 1 Group EFG T4 Ta -55°C to +40°C
Class III Div 1 Ta -55°C to +40°C
The D1xB2X15DC024 & D1xB2X15DC048 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T3C Ta -55°C to +80°C
Class I Div 1 Group ABCD T4 Ta -55°C to +55°C
Class II Div 1 Group EFG T4 Ta -55°C to +80°C
Class III Div 1 Ta -55°C to +80°C
The D1xB2X15AC115 & D1xB2X15AC230 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T4 Ta -55°C to +70°C
Class I Div 1 Group ABCD T4A Ta -55°C to +55°C
Class II Div 1 Group EFG T4 Ta -55°C to +40°C
Class III Div 1 Ta -55°C to +40°C
The D1xB2X21DC024 & D1xB2X21DC048 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T3B Ta -55°C to +80°C
Class I Div 1 Group ABCD T3C Ta -55°C to +75°C
Class I Div 1 Group ABCD T4 Ta -55°C to +50°C
Class II Div 1 Group EFG T3C Ta -55°C to +40°C
Class III Div 1 Ta -55°C to +40°C
The D1xB2X21AC115 & D1xB2X21AC230 Xenon Beacons
are rated as follows:
Class I Div 1 Group ABCD T3C Ta -55°C to +60°C
Class I Div 1 Group ABCD T4 Ta -55°C to +55°C
Class I Div 1 Group ABCD T4A Ta -55°C to +40°C
Class II Div 1 Group EFG T4 Ta -55°C to +40°C
Class III Div 1 Ta -55°C to +40°C
Installation must be carried out in compliance with the
National Electric Code / Canadian Electric Code
2.4 NEC Class / Zone ratings US
The D1xB2X Xenon beacons comply with the following
standards:
UL 60079-0 (Ed. 6) 2017
UL 60079-1 (Ed. 7) 2015
UL 60079-31 (Ed. 2) 2015
The D1xB2X05DC012, D1xB2X05DC024 &
D1xB2X05DC048 Xenon Beacons are rated as follows:
Class I Zone 1 AEx db IIC T4 Ta -55°C to +80°C
Class I Zone 1 AEx db IIC T5 Ta -55°C to +75°C
Class I Zone 1 AEx db IIC T6 Ta -55°C to +60°C
Zone 21 AEx tb IIIC T99°C Ta -55°C to +80°C
The D1xB2X05AC115 & D1xB2X05AC230 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T4 Ta -55°C to +70°C
Class I Zone 1 AEx db IIC T5 Ta -55°C to +50°C
Zone 21 AEx tb IIIC T153°C Ta -55°C to +70°C
Model
D1XB2
Nominal
V
oltage
Voltage
Range
Flash
Rate
Peak
Surge
current
RMS
surge
current
X05DC024 24Vdc 20-28Vdc 1Hz 955mA 370mA
1.33Hz 960mA 370mA
1.5Hz 955mA 365mA
Double 960mA 355mA
X10DC024 24Vdc 20-28Vdc 1Hz 970mA 700mA
1.33Hz 970mA 700mA
1.5Hz 990mA 700mA
Double 990mA 695mA
X15DC024 24Vdc 20-28Vdc 1Hz 990mA 925mA
1.33Hz 990mA 930mA
1.5Hz 990mA 925mA
Double 990mA 905mA
X21DC024 24Vdc 20-28Vdc 1Hz 1590mA 1220mA
1.33Hz 1710mA 1240mA
1.5Hz 1590mA 1240mA
Double 1650mA 1200mA

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D191-00-201-IS Issue 3 28-11-22 Sheet 3 of 9
The D1xB2X10DC024 & D1xB2X10DC048 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T4 Ta -55°C to +80°C
Class I Zone 1 AEx db IIC T5 Ta -55°C to +45°C
Zone 21 AEx tb IIIC T132°C Ta -55°C to +80°C
The D1xB2X10AC115 & D1xB2X10AC230 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T3 Ta -55°C to +70°C
Class I Zone 1 AEx db IIC T4 Ta -55°C to +65°C
Zone 21 AEx tb IIIC T153°C Ta -55°C to +70°C
The D1xB2X15DC024 & D1xB2X15DC048 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T3 Ta -55°C to +80°C
Class I Zone 1 AEx db IIC T4 Ta -55°C to +65°C
Zone 21 AEx tb IIIC T132°C Ta -55°C to +80°C
The D1xB2X15AC115 & D1xB2X15AC230 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T3 Ta -55°C to +70°C
Class I Zone 1 AEx db IIC T4 Ta -55°C to +65°C
Zone 21 AEx tb IIIC T153°C Ta -55°C to +70°C
The D1xB2X21DC024 & D1xB2X21DC048 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T3 Ta -55°C to +80°C
Class I Zone 1 AEx db IIC T4 Ta -55°C to +45°C
Zone 21 AEx tb IIIC T181°C Ta -55°C to +80°C
The D1xB2X21AC115 & D1xB2X21AC230 Xenon Beacons
are rated as follows:
Class I Zone 1 AEx db IIC T3 Ta -55°C to +60°C
Class I Zone 1 AEx db IIC T4 Ta -55°C to +50°C
Zone 21 AEx tb IIIC T153°C Ta -55°C to +60°C
Installation must be carried out in compliance with the
National Electric Code.
2.5 CEC Class / Zone ratings Canada
The D1xB2X Xenon beacons comply with the following
standards:
CAN/CSA C22.2 No. 60079-0 (Ed. 3) 2015
CAN/CSA C22.2 No. 60079-1 (Ed. 3) 2016
CAN/CSA C22.2 No. 60079-31 (Ed. 2) 2015
The D1xB2X05DC012, D1xB2X05DC024 &
D1xB2X05DC048 Xenon Beacons are rated as follows:
Ex db IIC T4 Ta -55°C to +80°C
Ex db IIC T5 Ta -55°C to +75°C
Ex db IIC T6 Ta -55°C to +60°C
Ex tb IIIC T99°C Ta -55°C to +80°C
The D1xB2X05AC115 & D1xB2X05AC230 Xenon Beacons
are rated as follows:
Ex db IIC T4 Ta -55°C to +70°C
Ex db IIC T5 Ta -55°C to +50°C
Ex tb IIIC T153°C Ta -55°C to +70°C
The D1xB2X10DC024 & D1xB2X10DC048 Xenon Beacons
are rated as follows:
Ex db IIC T4 Ta -55°C to +80°C
Ex db IIC T5 Ta -55°C to +45°C
Ex tb IIIC T132°C Ta -55°C to +80°C
The D1xB2X10AC115 & D1xB2X10AC230 Xenon Beacons
are rated as follows:
Ex db IIC T3 Ta -55°C to +70°C
Ex db IIC T4 Ta -55°C to +65°C
Ex tb IIIC T153°C Ta -55°C to +70°C
The D1xB2X15DC024 & D1xB2X15DC048 Xenon Beacons
are rated as follows:
Ex db IIC T3 Ta -55°C to +80°C
Ex db IIC T4 Ta -55°C to +65°C
Ex tb IIIC T132°C Ta -55°C to +80°C
The D1xB2X15AC115 & D1xB2X15AC230 Xenon Beacons
are rated as follows:
Ex db IIC T3 Ta -55°C to +70°C
Ex db IIC T4 Ta -55°C to +65°C
Ex tb IIIC T153°C Ta -55°C to +70°C
The D1xB2X21DC024 & D1xB2X21DC048 Xenon Beacons
are rated as follows:
Ex db IIC T3 Ta -55°C to +80°C
Ex db IIC T4 Ta -55°C to +45°C
Ex tb IIIC T181°C Ta -55°C to +80°C
The D1xB2X21AC115 & D1xB2X21AC230 Xenon Beacons
are rated as follows:
Ex db IIC T3 Ta -55°C to +60°C
Ex db IIC T4 Ta -55°C to +50°C
Ex tb IIIC T153°C Ta -55°C to +60°C
Installation must be carried out in compliance with the
Canadian Electric Code
2.6 ATEX / IECEx & UKEx Certification
The D1xB2X Xenon beacons comply with the following
standards:
EN IEC60079-0:2018 / IEC60079-0:2017 (Ed 7)
EN60079-1:2014 / IEC60079-1 (Ed. 7) (2014)
EN60079-31:2014 / IEC60079-31 (Ed. 2) (2013)
The D1xB2X05DC012, D1xB2X05DC024 &
D1xB2X05DC048 Xenon Beacons are rated as follows:
Ex db IIC T4 Gb Ta -55°C to +80°C
Ex db IIC T5 Gb Ta -55°C to +75°C
Ex db IIC T6 Gb Ta -55°C to +60°C
Ex tb IIIC T104°C Db Ta -55°C to +80°C
The D1xB2X05AC115 & D1xB2X05AC230 Xenon Beacons
are rated as follows:
Ex db IIC T4 Gb Ta -55°C to +70°C
Ex db IIC T5 Gb Ta -55°C to +50°C
Ex tb IIIC T116°C Db Ta -55°C to +70°C

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D191-00-201-IS
Issue 3
28-11-22 Sheet 4 of 9
The D1xB2X10DC024 & D1xB2X10DC048 Xenon Beacons
are rated as follows:
Ex db IIC T4 Gb Ta -55°C to +80°C
Ex db IIC T5 Gb Ta -55°C to +45°C
Ex tb IIIC T135°C Db Ta -55°C to +80°C
The D1xB2X10AC115, D1xB2X10AC230, D1xB2X15AC115
& D1xB2X15AC230 Xenon Beacons are rated as follows:
Ex db IIC T3 Gb Ta -55°C to +70°C
Ex db IIC T4 Gb Ta -55°C to +65°C
Ex tb IIIC T139°C Db Ta -55°C to +70°C
The D1xB2X15DC024 & D1xB2X15DC048 Xenon Beacons
are rated as follows:
Ex db IIC T3 Gb Ta -55°C to +80°C
Ex db IIC T4 Gb Ta -55°C to +65°C
Ex tb IIIC T146°C Db Ta -55°C to +80°C
The D1xB2X21DC024 & D1xB2X21DC048 Xenon Beacons
are rated as follows:
Ex db IIC T3 Gb Ta -55°C to +80°C
Ex db IIC T4 Gb Ta -55°C to +45°C
Ex tb IIIC T169°C Db Ta -55°C to +80°C
The D1xB2X21AC115 & D1xB2X21AC230 Xenon Beacons
are rated as follows:
Ex db IIC T3 Gb Ta -55°C to +60°C
Ex db IIC T4 Gb Ta -55°C to +50°C
Ex tb IIIC T141°C Db Ta -55°C to +60°C
Certificate No. DEMKO 19 ATEX 2009X
IECEx ULD 19.0006X
UL21UKEX2130X
ATEX Mark,
Equipment Group and
Category:
II 2G
II 2D
CE Marking and
Notified Body No.
2813
UKCA Marking and
Notified Body No.
0518
The units can be installed in locations with the following
conditions:
Area Classification:
Zone 1 Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur in
normal operation, and if it does, it will only exist
for a short time.
Zone 21 Explosive dust air mixture likely to occur in
normal operation.
Zone 22
Explosive dust air mixture not likely to occur in
normal operation, and if it does, it will only exist
for a short time.
Gas Groupings:
Group IIA Propane
Group IIB Ethylene
Group IIC Hydrogen and Acetylene
Temperature Classification:
T1 450ºC
T2 300ºC
T3 200ºC
(D1xB2X15DC & D1xB2X21DC
up to 80°C ambient,
D1xB2X10AC & D1xB2X15AC
up to 70°C ambient,
D1xB2X21AC up to 60°C ambient)
T4 135ºC
(D1xB2X05DC & D1xB2X10DC
up to 80°C ambient,
D1xB2X05AC up to 70°C ambient,
D1xB2X10AC, D1xB2X15DC &
D1xB2X15AC up to 65°C ambient,
D1xB2X21AC up to 50°C ambient,
D1xB2X21DC u
p
to 45°C ambient
)
T5 100ºC
(D1xB2X05DC up to 75°C ambient,
D1xB2X05AC up to 50°C ambient,
D1xB2X10DC up to 45°C ambient)
T6 85ºC (D1xB2X05DC up to 60°C ambient)
Dust Groupings:
Group IIIA Combustible Flyings
Group IIIB Non-conductive Dust
Group IIIC Conductive Dust
Maximum Surface Temperature for Dust Applications:
104°C (D1xB2X05DC)
116ºC (D1xB2X05AC)
135ºc (D1xB2X10DC)
139°C (D1xB2X10AC, D1xB2X15AC)
141°C (D1xB2X21AC)
146°C (D1xB2X15DC)
169ºC (D1xB2X21DC)
Equipment Category: 2G / 2D
Equipment Protection Level: Gb, Gc, Db, Dc
Ambient Temperature Range:
-55°C to +80°C (D1xB2X05DC, D1xB2X10DC,
D1xB2X15DC, D1xB2X21DC)
-55°C to +70°C (D1xB2X05AC, D1xB2X10AC,
D1xB2X15AC)
-55°C to +60°C (D1xB2X21AC)
The certification approval has validated continuous use up to
38°C ambient and are for transient use up to 80°C ambient.

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D191-00-201-IS Issue 3 28-11-22 Sheet 5 of 9
2.7 Ingress Protection Ratings
The product is rated for ingress Protection as follows:
IP rating
per EN60529: IP66
Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13
Suitable for exposure to Acetone , Ammonium Hydroxide ,
Diethyl Ether , Ethyl Acetate , Ethylene Dichloride , Furfural,
n-hexane , Methyl Ethyl Ketone , Methanol , 2-NitroPropane
and Toluene.
To maintain the ingress protection rating, the cable entries
must be fitted with suitably rated, certified cable entry and/or
blanking devices during installation.
2.8 Electrical Ratings
#Rated at 1Hz
Table 1: Electrical Ratings
It is important that a suitable power supply is used to run the
equipment. The power supply selected must have the
necessary capacity to provide the input current to all the units.
The input current will vary according to the voltage input level.
3) Special Conditions of Use
The enclosure coating is non-conductive and may generate an
ignition-capable level of electrostatic charges under certain
extreme conditions. The user should ensure that the
equipment is not installed in a location where it may be
subjected to external conditions (such as high pressure steam)
which might cause a build-up of electrostatic charges on non-
conducting surfaces. Additionally, cleaning of the equipment
should be done only with a damp cloth.
Flame Path Positions
4) Installation
There are no restrictions on unit orientation.
The junction box must only be installed by suitably qualified
personnel in accordance with the latest issues of the relevant
standards:
EN60079-14 / IEC60079-14: Explosive atmospheres -
Electrical installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive
atmospheres - Classification of areas. Explosive gas
atmospheres
EN60079-10-2 / IEC60079-10-2: Explosive
atmospheres - Classification of areas. Explosive dust
atmospheres
The installation of the units must also be in accordance with
any local codes that may apply and should only be carried out
by a competent electrical engineer who has the necessary
training.
4.1 Safe Installation Requirements
To maintain the ingress protection rating and mode of
protection, the cable entries must be fitted with suitably
certified cable entry and/or blanking devices during
installation. If conduit is used for installation, seal conduit
within 18 inches from the enclosure.
If entries are fitted with adaptors they must be suitably certified
for the application. Fitting of blanking elements into adaptors
is not permitted.
Check that the ‘O’ ring seal is in place before replacing the
explosionproof cover.
Lens guard must be fitted for Class Division installations.
5) Location and Mounting
The location of the beacon should be made with due regard to
the area over which the warning signal must be visible. It
should only be fixed to services that can carry the weight of the
unit.
The D1xB2X beacon can be mounted using one of three
methods.
Model
D1xB2
Nom.
Voltage
Voltage
Range
Nom.
operating
current
Max
Current
X05DC012 12Vdc 12-14Vdc 585 600
X05DC024 24Vdc 20-28Vdc 295 350
X05DC048 48Vdc 42-54Vdc 145 150
X05AC115 115Vac 110-120Vac 140 200
X05AC230 230Vac 220-240Vac 70 100
X10DC024 24Vdc 20-28Vdc 605 710
X10DC048 48Vdc 42-54Vdc 230 250
X10AC115 115Vac 110-120Vac 220 300
X10AC230 230Vac 220-240Vac 130 180
X15DC024 24Vdc 20-28Vdc 835 920
X15DC048 48Vdc 42-54Vdc 330 360
X15AC115 115Vac 110-120Vac 310 420
X15AC230 230Vac 220-240Vac 170 230
X21DC024 24Vdc 20-28Vdc 1130 1240
X21DC048 48Vdc 42-54Vdc 530 560
X21AC115 115Vac 110-120Vac 500 530
X21AC230 230Vac 220-240Vac 195 270
Flame Path internal thread on
base shown hatched
Cemented Joint
between glass
dome and metal
casting on lid
shown hatched
Flame Path
external thread
on lid shown
hatched

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D191-00-201-IS
Issue 3
28-11-22 Sheet 6 of 9
252.3 [9.93in]
7.00 [0.28in]
45.0°
3/4" NPT SIDE ENTRY
2 OFF POSITIONS
MARKED *
M20x1.5 SIDE ENTRY
2 OFF POSITIONS
MARKED #
3/4" NPT BOTTOM ENTRY
FOR POLE MOUNTING
BEACON
2 OFF FEET SUPPLIED IN STOWED POSITION
SUITABLE FOR POLE OR BRACKET
MOUNTING BEACON
RETAINED BY 2 OFF M5 SCREWS PER FOOT
166.0 [6.54in]
83.0 [3.27in]
2 OFF FEET SUPPLIED IN STOWED POSITION
SUITABLE FOR POLE OR BRACKET
MOUNTING BEACON
RETAINED BY 2 OFF M5 SCREWS PER FOOT
BASE CONFIGURED WITH
FEET SET OUT FOR SURFACE MOUNTING
BEACON
Ø9.0 [Ø0.36in]
1. The beacon can be surface mounted by removing,
rotating and reinstalling the stowed mounting lugs. These
are suitable for 6mm diameter fixings.
a. Remove 2 x M5 fasteners per
mounting lug
b. Reverse and rotate lug and
reseat onto enclosure
c. Secure lug using the 2 x M5
Fasteners
2. Alternatively, the beacon can be conduit mounted using
the 3/4” NPT entry on the base of the unit.
3. Additionally, the beacon can be mounted using the ratchet
adjustable stainless-steel wall bracket assembly. This is
available as an accessory – part code: SP77-0001.
Fig. 1 Fixing Location for Beacon
6) Access to the Enclosure
In order to connect the electrical supply cables to the beacon,
it is necessary to open the explosion proof enclosure. Loosen
the locking grub screw in the cover and then remove the
glass dome cover assembly to gain access to the chamber.
This can be achieved by unscrewing the glass dome cover,
taking extreme care not to damage the threads when doing
so.
Fig. 2 Accessing the Enclosure.
On completion of the installation the flameproof threads should
be inspected to ensure that they are clean and that they have
not been damaged during installation. Ensure the O-ring seal
is in place and undamaged.
When fitting the flameproof cover ensure the thread is
engaged correctly. Fully tighten the cover all the way, ensure
no gap is visible between the cover and base of the beacon
enclosure.
7) Selection of Cable, Cable Glands, Blanking
Elements & Adapters
When selecting the cable size, consideration must be given to
the input current that each unit draws (see section 11), the
number of beacons on the line and the length of the cable runs.
The cable size selected must have the necessary capacity to
provide the input current to all of the beacons connected to the
line.
The entries are 2-off M20 x 1.5 thread & 3-off ¾” NPT thread
If a high IP (Ingress Protection) rating is required then a
suitable sealing washer must be fitted under the cable glands
or blanking plugs.
For use in explosive dust atmospheres, a minimum ingress
protection rating of IP6X must be maintained.
For use in explosive gas atmospheres, a minimum ingress
protection rating of IP54 must be maintained.
NPT plugs should be greased before insertion.
For high ambient temperatures the cable entry temperature
or the cable branching point temperature may exceed 60ºC
and therefore suitable heat resisting cables and cable glands
must be used, with a rated service temperature of at least the
values stated below:
Table 2: Required Cable/Cable Gland Ratings (°C).
8) Cable Connections
The units have 2-off M20 x 1.5 threaded entries and 3-off ¾”
NPT x 14 threaded entries.
Electrical Connections are to be made into the terminal blocks
using solid or stranded wire, sizes 0.5-2.5mm2 / AWG 20-14.
Wire insulation needs to be stripped 6-7mm. Wires may be
fitted securely with crimped ferrules. Terminal screws need to
be tightened down with a tightening torque of 0.4 Nm / 3.5 Lb-
in.
See section 5 of this manual for access to the enclosure.
Glass dome
cover
Warning – High voltage may be present,
risk of electric shock. DO NOT open when
energised, disconnect power before
opening.
Warning –
Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.
3/4" NPT
Entry
M20 Entry
3/4" NPT
Conduit
Entr
y

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D191-00-201-IS Issue 3 28-11-22 Sheet 7 of 9
9) Wiring
A 4-way terminal block is provided on the DC beacons for
power. There are 2-off +ve, 2-off –ve terminal and an internal
Earth boss.
See Schematic diagram D191-06-201.
Terminals
- - + +
Fig. 3 D1xB2XDC Terminals
A 5-way terminal block is provided on the AC beacons for
power. There are 2-off Live, 2-off Neutral and an Earth
terminal.
See Schematic diagram D191-06-205.
Terminals
L L N N E
Fig. 4 D1xB2XAC Terminals
9.1 Line Monitoring
On the D2xB1X unit, DC reverse line monitoring can be used
if required.
All DC beacons have a blocking diode fitted in their supply
input lines. An end of line monitoring resistor can be connected
across the +ve and –ve terminals in the explosion proof
enclosure. If an end of line resistor is used it must have the
following values:
Minimum resistance 3K3 Ohms Minimum Power 0.5W
Minimum resistance 500 Ohms Minimum Power 2.0W
The resistor must be connected directly across the +ve and
-ve terminals as shown in the following drawing. Form the
resistor legs as shown in Fig. 5a, fit the resistor across the two
terminals, as shown in Fig. 5b.
Fig. 5a End of Line Resistor Forming
Fig. 5b End of Line Resistor Placement
10) Earthing
The unit has an external and an internal earth terminal, (please
see fig 6).
Please note that for AC supply voltage product versions the
Earth terminal on the PCBA does not provide an earth
connection to the product enclosure. The enclosure must be
independently earthed using either the external or internal
earth fixing point, (see fig 6 and notes below).
Internal earthing connections should be made to the internal
Earth terminal in the base of the housing using a ring crimped
terminal to secure the earth conductor under the earth clamp.
The earth conductor should be at least equal in size and rating
to the incoming power conductors.
External earthing connections should be made to the M5 earth
stud, using a ring crimp terminal to secure the earth conductor
to the earth stud. The external earth conductor should be at
least 4mm” in size.
Fig. 6: Internal and External Earth Locations
End of Line
Resisto
r
Internal Earth
Terminal
External
Earth Stud

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D191-00-201-IS
Issue 3
28-11-22 Sheet 8 of 9
11) Settings
11.1 Flash Rate Setting
The D1xB2X beacon can produce different flash patterns as
shown in Table 1. The flash patterns are selected by operation
of the flash setting DIP switch on the PCB, Fig 7.
Note: Only 1Hz flash rate is Private Mode Fire approved
AC Units DC Units
Fig. 7: DIP Switch Location
(*Setting permitted for use as private mode fire alarm device)
Table 3: Switch Positions for Flash Patterns
12) Interchangeable & Spare Parts
The Beacon lens cover is interchangeable, contact E2S Ltd for
a replacement lens cover available in various colours.
To change the lens cover, unscrew the 4-off M5 socket head
screws, spring and flat washers using a 4mm Hex key.
Remove the wire guard and replace the old lens cover with the
new lens cover.
Fig. 8 Replacement of beacon lens cover
Fit the wire guard back onto the housing, over the new lens
cover aligning the fixing holes of the guard, lens cover and
housing. Refit the fixings to hold into place, the fixings MUST
be fitted in the order shown above.
Switch
Setting S1 Mode
1=ON; 0=OFF
Example shown (Fig.7):
10 = Flashing 1.5Hz
(Default setting is 00 1Hz)
00 1Hz* (60FPM)
01 1.33Hz (80FPM)
10 1.5Hz (90FPM)
11 Double Flash
Warning – Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.
Warning – high-intensity light source.
Avoid looking directly at the light source for
extended periods of time.
M5 screw
M5 spring washer
M5 flat washe
r

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D191-00-201-IS Issue 3 28-11-22 Sheet 9 of 9
13) Maintenance, Overhaul & Repair
Maintenance, repair and overhaul of the equipment should
only be carried out by suitably qualified personnel in
accordance with the current relevant standards:
EN60079-19 / IEC60079-19 Explosive atmospheres -
Equipment repair, overhaul and reclamation
EN 60079-17 / IEC60079-17 Explosive atmospheres -
Electrical installations inspection and maintenance
To avoid a possible ELECTROSTACTIC CHARGE the unit
must only be cleaned with a damp cloth.
Units must not be opened while an explosive atmosphere is
present.
If opening the unit during maintenance operations a clean
environment must be maintained and any dust layer removed.
Flameproof joints are not intended to be repaired.
14) SIL 2 Reliability Data
Reliability and Functional safety IEC/EN61508 which has
been assessed and is considered suitable for use in low
demand safety function:
1. Random Hardware Failures and Architectural constraints
(route 2H).
2. As an unvoted item (i.e. hardware fault tolerance of 0) at
SIL 2.
The product was assessed against failure modes:
Failure respond to an input by lighting a beacon.
Spurious light output despite no input.
3. When employing the device in a SIL2 compliant system
the user should ensure frequent or continuous automatic
monitoring of continuity.
Integrity in respect of failure to function SIL2& SIL1
Total Failure rate 0.48 pmh
“Hazardous” failure rate (revealed) 0 pmh
“Hazardous” failure rate (unrevealed) 0.48 pmh
“Safe” failure rate (revealed) 0 pmh
“Safe” failure rate (unrevealed) 0
System type B
Hardware Fault Tolerance 0
Dia
g
nostic Covera
g
e >60%
PFD (hazardous failure) 2.1 x 10-3
Proof Test Interval Up to 1 year

warning signals
2S
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D191-06-201
R.N.POTTS OF
D1xB2 X05/X10/X15/X21
NTS 1 2
D1xB2 BEACONS
R.N.POTTS
R. RAIT
BEACON WIRING DIAGRAMS
+ve IN
+ve OUT
-ve IN
-ve OUT
R1
+
+
-
-
DC XENON D1xB2 X05, X10, X15 & 21J UNITS
Line Monitoring
Power: +ve & -ve
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
RECOMMENDED MINIMUM VALUES:
R1
500Ω MIN, 2W MIN OR 3K3Ω MIN, 0.5W MIN
28/11/22
28/11/22
28/11/22
NEW PCBA & FORMAT INTRODUCED
J.S - 22/03/21
B
RE-DRAWN IN 2D
NOTES, TERMINALS & EOL RESISTOR ADDED
DAH 17/12/19
C
NEW FORMAT INTRODUCED
RSR - 28/11/22
D

warning signals
2S
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D191-06-201
R.N.POTTS OF
D1xB2 X05/X10/X15/X21
NTS 2 2
D1xB2 BEACONS
R.N.POTTS
R. RAIT 28/11/22
BEACON WIRING DIAGRAMS
AC XENON GNExB2 X21 UNITS
Power: Live & Neutral
Neutral IN
Neutral OUT
Live IN
Live OUT
N
N
L
L
AC XENON D1xB2 X05, X10 & X15 UNITS
Power: Live & Neutral
Neutral IN
Neutral OUT
Live IN
Live OUT
N
N
L
L
E
Earth
NEW PCBA & FORMAT INTRODUCED
J.S - 22/03/21
B
RE-DRAWN IN 2D
NOTES, TERMINALS & EOL RESISTOR ADDED
DAH 17/12/19
C
28/11/22
28/11/22
NEW FORMAT INTRODUCED
RSR - 28/11/22
D

E2STelephone:+44(0)2087438880Fax:+44(0)2087404200Email:[email protected]www.e2s.comDC‐077_Issue_E‐Page1of1‐QAF_252_Issue_5
MartinStreetzDocumentNo.:DC‐077_Issue_E
QualityAssuranceManagerDateandPlaceofIssue:London,07/07/2022
EUDeclarationofConformity
Manufacturer: EuropeanSafetySystemsLtd.
ImpressHouse,MansellRoad,Acton
London,W37QH
UnitedKingdom
AuthorisedRepresentative:E2SWarnsignaltechnikUG
Charlottenstrasse45‐51
72764Reutlingen
Germany
EquipmentType: D1xB2X05,D1xB2X10,D1xB2X15,D1xB2X21,D1xB2LD2,D1xJ2
Directive2014/34/EU:EquipmentandProtectiveSystemsforuseinPotentiallyExplosiveAtmospheres(ATEX)
NotifiedBodyforEUtypeExamination(ModuleB):ULInternationalDemkoA/S
NotifiedBodyNo.:0539
Borupvang5A,2750Ballerup,Denmark
EU‐typeExaminationCertificate(ModuleB):DEMKO19ATEX2009XRev.1
NotifiedBodyforQualityAssuranceNotification/ConformitytoEU‐type
basedon
qualityassuranceoftheproductionprocess(ModuleD):
SiraCertificationService
NotifiedBodyNo.:2813
CSAGroupNetherlandsB.V,Utrechtseweg310,6812AR,Arnhem,Netherlands
QualityAssuranceNotification(ModuleD):SIRA05ATEXM342
Provisionsfulfilledbytheequipment:II2GExdIICT6…T3Gb
II2DExtbIIICT95°C…T169°CDb
Standardsapplied:EN60079‐0:2018
EN60079‐1:2014
EN60079‐31:2014
IP6XDustProtectiontoEN60079‐0/EN60079‐31
Directive2014/30/EU:ElectromagneticCompatibilityDirective(EMC)
Standardsapplied:ENIEC61000‐6‐1:2019&IEC61000‐6‐1:2016
ENIEC61000‐6‐2:2019&IEC61000‐6‐2:2016
ENIEC61000‐6‐3:2021&IEC61000‐6‐3:2020
ENIEC61000‐6‐4:2019&IEC61000‐6‐4:2018
Directive2011/65/EU:Restrictionoftheuseofcertainhazardoussubstancesinelectricalandelectronicequipment(RoHS)
Theproductandallthecomponentscontainedwithinitareinaccordancewiththerestrictionoftheuseofhazardoussubstancesinelectricalandelectronic
equipment,includingamendmentbyDirective2015/863/EU.
Regulation(EC)1907/2006:Registration,Evaluation,AuthorisationandRestrictionofChemicals(REACH)
Theproductandallthecomponentscontainedwithinitarefreefromsubstancesofveryhighconcern.
OtherStandardsandRegulations
EN60529:1991+A1:2000+A2:2013.‐Degreesofprotectionprovidedbyenclosures(IPcode)–enclosureratedIP66/67
OnbehalfofEuropeanSafetySystemsLtd.,Ideclarethat,onthedatetheequipmentaccompaniedbythisdeclarationisplacedonthemarket,theequipment
conformswithalltechnicalandregulatoryrequirementsoftheabovelisteddirectives,regulationsandstandards.
ThisDeclarationisissuedunderthesoleresponsibilityofthemanufacturer.

E2STelephone:+44(0)2087438880Fax:+44(0)2087404200Email:[email protected]omwww.e2s.com DC‐096_Issue_A‐Page1of1‐QAF_252_Issue_5
MartinStreetz DocumentNo.: DC‐096_Issue_A
QualityAssuranceManager DateandPlaceofIssue: London,24/02/2022
UKCADeclarationofConformity
Manufacturer: EuropeanSafetySystemsLtd.
ImpressHouse,MansellRoad,Acton
London,W37QH
UnitedKingdom
EquipmentType: D1xB2X05,D1xB2X10,D1xB2X15,D1xB2X21,D1xB2LD2,D1xJ2
DirectiveUKSI2016:1107(asamendedbyUKSI2019:696)–Schedule3A,Part1:ProductorProtectiveSystemIntendedforuseinPotentiallyExplosiveAtmospheres
(UKCA)
NotifiedBodyforUKtypeExamination(ModuleB): ULInternational(UK)Ltd
NotifiedBodyNo.:0843
Unit1‐3HorizonKingslandBusinessPark,WadeRoad,
Basingstoke,HampshireRG248AHUK
UK‐typeExaminationCertificate(ModuleB): UL21UKEX2130X
NotifiedBodyforQualityAssuranceNotification/ConformitytoEU‐type
basedon
qualityassuranceoftheproductionprocess(ModuleD):
SiraCertificationService
NotifiedBodyNo.:0518
RakeLane,Eccleston,ChesterCH49JN,UK
QualityAssuranceNotification(ModuleD): CSAE22UKQAN0046
Provisionsfulfilledbytheequipment: II2GExdIICT6…T3Gb
II2DExtbIIICT95°C…T169°CDb
Standardsapplied: EN60079‐0:2018
EN60079‐1:2014
EN60079‐31:2014
IP6XDustProtectiontoEN60079‐0/EN60079‐31
Directive2014/30/EU:ElectromagneticCompatibilityDirective(EMC)
Standardsapplied: EN61000‐6‐1:2007
EN61000‐6‐2:2005
EN61000‐6‐3:2007/A1:2011/AC:2012
EN61000‐6‐4:2007/A1:2011
Directive2011/65/EU:Restrictionoftheuseofcertainhazardoussubstancesinelectricalandelectronicequipment(RoHS)
Theproductandallthecomponentscontainedwithinitareinaccordancewiththerestrictionoftheuseofhazardoussubstancesinelectricalandelectronic
equipment,includingamendmentbyDirective2015/863/EU.
Regulation(EC)1907/2006:Registration,Evaluation,AuthorisationandRestrictionofChemicals(REACH)
Theproductandallthecomponentscontainedwithinitarefreefromsubstancesofveryhighconcern.
OtherStandardsandRegulations
EN60529:1991+A1:2000+A2:2013.‐Degreesofprotectionprovidedbyenclosures(IPcode)–enclosureratedIP66/67
OnbehalfofEuropeanSafetySystemsLtd.,Ideclarethat,onthedatetheequipmentaccompaniedbythisdeclarationisplacedonthemarket,theequipment
conformswithalltechnicalandregulatoryrequirementsoftheabovelisteddirectives,regulationsandstandards.
ThisDeclarationisissuedunderthesoleresponsibilityofthemanufacturer.

Page left Intentionally blank

Page left Intentionally blank

Page left Intentionally blank
This manual suits for next models
7
Table of contents
Other E2S Security System manuals

E2S
E2S GNExCP6B-PB User manual

E2S
E2S IS-L101L-R/Y User manual

E2S
E2S STExB2X05-S Series User manual

E2S
E2S D2XC2XH1 User manual

E2S
E2S BExCBGL2-05D-P User manual

E2S
E2S GNExCP6B-PT User manual

E2S
E2S BExCTS110-05D-P User manual

E2S
E2S D1xS2FDC024-S User manual

E2S
E2S GNExB2X05 Series User manual

E2S
E2S D1xS1 Series User manual

E2S
E2S BExCBL2-L2D-P User manual

E2S
E2S D2xC2LD3 User manual

E2S
E2S D2xC2LD2 Series User manual

E2S
E2S D1 B2LD2 Series User manual

E2S
E2S MBLD2 Series User manual

E2S
E2S BexCS11005D24DC-RD User manual

E2S
E2S D2xC2LD2 Series User manual

E2S
E2S D1xC2 Series User manual

E2S
E2S D1xC3 User manual

E2S
E2S GNExCP6B-PT User manual