Elmdene VERTEC-3000-G3 User manual

Technical Support Line +44 (0)23 9269 6638 (Option 3) PAK200218 ss 05B Oct 2012 ©2012 ELMDENE NTERNAT ONAL LTD
VERTEC-3000-G3 External Grade 3 Sounder
F
EATURES
-
105
dB(A) siren output
-12v dc voltage operation
-ntegral 1.0 Watt Xenon tube strobe (with
active inrush current limit)
-3 way tamper protection: cover, rear & module
-Separate sound and strobe trigger inputs
-Hold-off supply failure detection
-Battery and piezo test with fault output
-Remote test input facility
-Selectable sound auto cut-off timer: no cut-off,
5s (for test), 3, 10, 15 minutes
-
Full SAB using internal batt
ery
-Twin Comfort LEDs selectable on, off, alternate
flash
-4 selectable sound tones
-Audible Tamper to assist commissioning
-Ring Line Monitoring
-Fully enclosed electronics module
-Engineer Mode for quiet installation and
maintenance
-Polycarbonate cover and backplate
-Microprocessor controlled
Elmdene International Ltd
Tel: +44(0)23 9269 6638
3 Keel Close, Interchange Park, Fax: +44(0)23 9266 0483
Portsmouth, Hampshire, PO3 5QD, UK
Web: www.elmdene.co.uk
Figure 1:
Vertec 3000
Module

Technical Support Line +44 (0)23 9269 6638 (Option 3) PAK200218 ss 05B Oct 2012 ©2012 ELMDENE NTERNAT ONAL LTD
O
PERATION
The Vertec 3000 is used for notification of an alarm condition as generated within an intruder, hold-up or other alarm
system. n response to commands from the alarm system control panel, the sounder will emit a high intensity sound
and/or operate a visual flash.
The sounder will detect any attempt to gain unauthorised access to the sounder by removal of the cover, or any attempt
to remove it away from its mounting surface. This will generate a tamper signal which is normally fed back to the alarm
control panel. ntegrity of the Trigger Command (Ring Line) connection is constantly monitored and will cause the unit to
self activate if loss of connection is detected.
These sounders are classified as self powered sounders and have an on-board battery which is recharged via the external
power source. This battery is used to operate the sounder if the external power is removed. The sounders will self actuate
in the event that a tamper condition is detected or the external power to the sounder is removed.
Every 24 hours the sounder performs a self test to check the integrity of its on-board battery, its battery charging circuit
and its piezo transducers. f an error condition is detected, a fault signal is generated. This is normally connected back to
the control panel. This self-test can be triggered at any time by a Remote Test command sent from the control panel.
To assist with commissioning, the sounders have an Engineer Mode to provide silent start-up and Tamper Tones that
indicate the correct closure of the tamper detection switches.
Two Comfort LEDs are used to provide a heart-beat type visual indication when the sounder is not sounding. These may
be disabled.
F
UNCTIONAL
I
NFORMATION
Tam er Circuit for Single or Multi le Cascade Installations
For a single siren installation, link TS to H- and connect TR to the control panel Tamper return input. n cascade
installations with two or more sounders, the TS (Tamper Source) will normally be connected to the TR (Tamper Return) of
the next sounder, except for the last unit which will have TS linked to H- .
Engineer Mode
This selects silent start-up and silent maintenance. The ENG input may be brought back to the control panel and
connected to a programmable output. Switching this control panel output high when maintenance is required will prevent
the sounder from self activating when the cover is removed or R- activated. The Tamper output is open when ENG is high;
this prevents inadvertent system setting with the sounder left in Engineer Mode.
Self Test and Fault Out ut
The sounder performs a self test every 24 hours. This function tests the condition of the battery and piezo sounders. f a
fault is found the Healthy/Fault output will open.
The Fault output will be cleared (output closed) when:
- the fault has been cleared, e.g. battery (re)connection
- the fault has been cleared and the sounder performs its next 24hour self test
- the fault has been cleared and a self test is triggered using the Engineering Remote Test input
- the fault has been cleared and the sounder has been disconnected from H+ AND the SAB battery has been disconnected
(hardware reset)
Remote Test
Taking the Engineer/Remote Test input high will force a self test. The Healthy/Fault output is immediately opened to
acknowledge receipt of the Remote Test instruction. The condition of the piezos and battery is immediately tested. Any
fault found will be indicated by the Healthy/Fault output remaining open after 10s. The Healthy/Fault output will remain
open until the fault has been cleared and another Self Test or Remote Test has been performed. f the self test has passed,
the Healthy/Fault output will close after 10s of starting the Remote Test.
2

Technical Support Line +44 (0)23 9269 6638 (Option 3) PAK200218 ss 05B Oct 2012 ©2012 ELMDENE NTERNAT ONAL LTD
O
PTIONS
S
ELECTION
Figure 1: Connections and Jumper Link Options
Note: Factory Default is 15 minute Cut-off, flashing LED’s, SAB Mode, Tone 4
Sound Cut-off Timer
The sounder will automatically stop sounding after the time period selected by the Sound Cut-off Timer links, J1/J6,
irrespective of the status of the sound trigger (R-) input. The 5s option is provided to reduce nuisance noise during testing.
Comfort LEDs
Twin comfort LEDs may be configured for alternate flashing, permanently on or permanently off by selection of J2/J7. When
enabled, the LEDs flash at a rate of approximately 1Hz.
SAB Mode
n SAB mode the sounder can draw current from both the control panel and the battery. The siren will self-activate if either of
the tampers are activated.
n SCB mode the sounder draws the majority of its current from the battery to minimise drain on the control panel. This allows
the user to connect multiple units to a control panel without overloading it. Select SCB mode using the J8 link (Figure 2.0). n
this mode the sounder will NOT self activate under a tamper condition but the tamper condition will still be signalled back to
the control panel. The control panel can then trigger the siren using the R– line.
Note: The siren will self-activate if the supply lines are cut in either mode.
T ME
R
LEDS
J1
J6
J2
J7
EN
G
HEALTHY
SAB
S
C
B
J4 J5
TONES
J8
H+
H
-
R
-
ST-
TS
TR
BAT+
BAT
-
3
J1
2
TONES (J4/J5)
3 41
J6
TIMER
LEDS
10m
3m
5s
J2 J7
15m ON
OFF
FLASH
OFF

Technical Support Line +44 (0)23 9269 6638 (Option 3) PAK200218 ss 05B Oct 2012 ©2012 ELMDENE NTERNAT ONAL LTD
C
ONNECTIONS
ENG Optional engineer input for quiet operation
during installation/ maintenance.
HEALTHY
(x2)
Volts free siren Healthy/Fault output - normally closed (Healthy)
H+ Permanent Positive Hold off Supply TS Tamper select. Connect to H- for single unit or last in line. Connect
to TR of next unit for multiple unit installation (see Figure 4.0)
H- Permanent Negative Hold off Supply TR Tamper return connection to control panel
R- Negative Siren Trigger BAT+ Positive connection to battery
ST- Negative strobe Trigger and Supply BAT- Negative battery connection. Connect black battery lead after
applying power.
Panel First /Only unit Last unit
(Furthest from panel)
0V Strobe
Trigger
Fault i/p
Fault i/p
+12V
0V
Tamper
Return
0V Siren
Trigger
Prog o/p
H+
H-
TS
TR
R-
ST-
ENG
Healthy
Healthy
H+
H-
TS
TR
R-
ST-
ENG
Healthy
Healthy
Figure 3: Multiple cascade siren connections
0V Strobe
Trigger
Fault i/p
Fault i/p
H+
H-
TS
TR
+12V
0V
Tamper
Return
0V Siren
Trigger
Prog o/p
R-
ST-
ENG
Healthy
Healthy
Figure 2: Single siren connections
Note 1:
Where the siren Trigger is not pulled up to > +8.5V by the
control panel when in standby mode, or is operated via
volt free contacts, it will be necessary to fit a pull up
resistor (1k0) as shown, at the control panel to enable
monitoring of the Trigger connection.
4
See Note 1
See Note 1

Technical Support Line +44 (0)23 9269 6638 (Option 3) PAK200218 ss 05B Oct 2012 ©2012 ELMDENE NTERNAT ONAL LTD
I
NSTALLATION AND
S
ET
-U
P
1. Remove cover, undo module fixing screw and swing electronics module away from backplate. Module will self support
when pivots are pushed back in their pivot slots
2. Offer backplate to desired position on mounting surface and drill holes to match chosen fixing centres and rear tamper
insert. A minimum of three fixings should be used.
3. Pierce cable grommet (supplied) to match diameter of control panel cable. Grommet must be used to prevent water
ingress via cable.
4. Fix grommet to backplate and pass control cable through grommet.
5. Fix backplate to mounting surface using appropriate fixings for the mounting
surface.
6.
Fix tamper insert to mounting surface using an appropriate fixing for the
mounting surface
7. Swing electronics module onto backplate and verify that rear tamper pin is
depressed when in contact with the tamper insert.
8. Set the required Cut-off Timer (J1 & J6), LED option (J2 & J7), Tone options
(J4 & J5) and SAB/SCB option (J8).
9. Connect ENG input to H+ or to a switched output of control panel set high.
10. Make remaining connections to control panel in the following order:
sounder activate, strobe activate, tamper return, negative power supply,
positive supply.
11. Connect the black battery lead to BAT-.
12. Disconnect ENG from H+.
13. Lower inner cover and fix using self tapping screw supplied.
14. Replace cover temporarily. Sounder should stop when cover completely replaced.
T
ESTING
1. Activate bell or ring output from control panel. Check sounder activates.
2. Activate strobe output from control panel. Check strobe flashes.
3. Ensure control panel bell and strobe outputs are switched off. Remove cover and check sounder operates due to top
tamper.
4. f a Tamper Return connection is made to the control panel, check that the panel detects a tamper active condition.
5. Temporarily replace cover. Check that sounder switches off. Check that the tamper active condition has cleared at the
control panel.
6. Unfasten inner cover fixing screw so that module sits away from wall mounting and rear tamper is activated. Temporarily
replace cover and check that sounder activates. Check that a tamper active condition is detected at the control panel.
7. Push cover and module into its fully seated position closing the rear tamper pin. Check that sounder switches off and that
the tamper condition is cleared at the control panel.
8. Securely fasten inner cover retaining screw.
9. Remove +ve sounder power supply connection at control panel. Check sounder activates and a tamper active condition is
detected at the control panel.
10. Replace +ve sounder power supply. Check tamper active condition is cleared at control panel.
11. Remove -ve sounder power supply connection at control panel. Check sounder activates and a tamper active condition is
detected at the control panel.
12. Replace -ve sounder power supply. Check tamper active condition is cleared at control panel.
13. Disconnect R- at control panel, check that the siren activates
14. Check correct operation of comfort LEDS.
15. Fasten cover to backplate using two fixing screws supplied. Fit screw covers.
16. Testing complete.
M
AINTENANCE
1. The sounder should be tested for correct operation on a periodic basis. A minimum of one check every 12 months is
recommended. The following features should be verified on each maintenance visit:
2. Correct operation of sounder and strobe from control panel signals
3. Correct operation of cover and rear tampers.
5
Figure 4: Tamper insert
mounting

Technical Support Line +44 (0)23 9269 6638 (Option 3) PAK200218 ss 05B Oct 2012 ©2012 ELMDENE NTERNAT ONAL LTD
M
AINTENANCE
(C
ONT
.)
4. Remove the +ve power supply from the control panel and check internal battery voltage is greater than 4.5v dc. f the
battery voltage is less than this value, the battery must be replaced. See ‘Specifications’ section for replacement battery
details.
5. Check for signs of significant water or insect ingress. Clean as necessary.
D
IAGNOSTICS
NOTE: Commissioning Mode only activated when ENG is connected to 9-15vdc AND 5s Time-out selected
Commissioning
Tones Status Indicated Action
Single Click Tamper closing – front or rear Use to ensure that the rear tamper has been fully closed
or that the cover has been fully closed.
Double Click Tamper opening – front or rear Use to verify correct operation of tamper circuit
Continuous slow clicks Rear tamper not closed when cover tamper
is closed Check tamper insert is not detached from backplate
Continuous fast clicks Battery not connected or faulty when cover
tamper is closed
Open cover and check that battery is correctly
connected.
F
AULT
F
INDING
Sym tom Fault Action
Sounder activated in
non-alarm condition
and tamper at panel
Cover not closed correctly. Check cover closed and screw secure.
Rear tamper insert disengaged from backplate Check tamper insert is not detached from
backplate
Sounder activated in
non-alarm condition
and NO tamper at panel
R- not pulled up to +12V in standby mode Fit ‘pull up’ resistor to R- at control panel,
see Note 1 (Fig. 2 & Fig. 3)
Sounder stops after 5s ncorrect timer link setting Set correct timer jumper links.
Cannot SET control
panel
(due to sounder
tamper)
Tamper output open due to ENG input still connected
to H+
Disconnect ENG from H+ in sounder or set
control panel programmable output low.
Tamper Source (TS) not connected to H- for single
sounder or to Tamper Return (TR) for cascaded
sounders
Refer to connection diagrams for cascaded
sounders (Figure 3).
Cover or Rear tamper switch not closed. Check cover and rear tamper switches closed.
Total resistance of tamper circuit is too high for
multiple sounder installations
Reduce number of cascaded sounders on one
tamper loop
Fault output open
Battery not connected Check battery connections to terminal block.
Battery faulty or low voltage Replace battery.
Piezo fault
Return unit to manufacturer
Battery charger faulty
6

Technical Support Line +44 (0)23 9269 6638 (Option 3) PAK200218 ss 05B Oct 2012 ©2012 ELMDENE NTERNAT ONAL LTD
SAB
B
ATTERY
R
EMOVAL
The SAB battery may be removed for disposal at end of product life or if it is detected faulty by the sounder self test.
To remove battery:
1. Ensure H+ power is disconnected from product.
2. Remove all field wiring.
3. Unclip battery from moulding
4. Remove battery leads from BAT+ and BAT-
To fit a new battery:
1. Clip replacement battery into position on backplate.
2. Route battery cables to electronics module connect positive (RED) lead to BAT+ and negative (BLACK) lead to BAT-.
MPORTANT: Ensure correct polarity of connections and that exposed battery leads DO NOT accidentally touch.
Dispose of used batteries in accordance with all national and local regulations
D
ISPOSAL OF
P
RODUCT AT
E
ND OF
L
IFE
This product falls within the scope of EU Directives 2002/96/EC Waste Electrical and Electronic Equipment (WEEE) and
2006/66/CE (Battery). At the end of life, the product must be separated from the domestic waste stream and disposed of via
an appropriate approved WEEE disposal route in accordance with all national and local regulations.
Before disposal of the product, the SAB battery must be removed and disposed of separately via an appropriate approved
battery disposal route in accordance with all national and local regulations. Package used batteries safely for onward transport
to your supplier, collection point or disposal facility.
Caution ris of fire or explosion
if bare battery wires are allowed to touch.
See Specification for battery type information. The battery is marked with the crossed out wheelie bin symbol, which may
include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg).
For more information see: www.recyclethis.info
7

Technical Support Line +44 (0)23 9269 6638 (Option 3) PAK200218 ss 05B Oct 2012 ©2012 ELMDENE NTERNAT ONAL LTD
S
PECIFICATION
Sound Output 105dB(A) peak @ 1m Modulated tone.
Power Supply 9.0 – 15.0Vdc, 13.8Vdc nominal
Current Consumption 20 mA max (quiescent)
Sounding 175 mA max
Strobing 140 mA max.
Cut-off Timer Selectable [5s, 5, 10, 15] minutes or no cut-off
Battery 6V 300mAh NiMH - Battery recharge in less than 24 hours
(Following 2 x 15 minute sounding)
Strobe LED, 1Hz flash rate reducing to 0.5Hz after 15 minutes
Tamper Cover and Rear
Tamper Output Volt free contact, maximum 16Ω resistance
Max 100mA current rating
Sound Trigger nput R- < 3.5Vdc = sound ON R- > 8.5Vdc = sound OFF
12mA max
Strobe Trigger nput ST- < 6.5Vdc = strobe flash ON ST- > 6.6Vdc = strobe OFF
5mA max
Fixings No 10 (M5) self tapping screws (4-off)
Cover Material Polycarbonate
Backplate Material Polycarbonate
Lens Material Polycarbonate
Operating Temperature - 25
o
C to +60
o
C
Storage Temperature - 25
o
C to +70
o
C
C
OMPLIANCE
This product meets the essential requirements of the following EU Directives:
EMC: 2004/108/EC
RoHS: 2002/95/EC
WEEE: 2002/96/EC
Battery: 2006/66/EC
EN50131-4:2009 Security Grade 3
Environmental Class V
This product is suitable for use in systems designed to comply with PD6662:2010 at:
Grade 3 and Environmental Class IV.
.
The packaging supplied with this product may be recycled.
Please dispose of packaging accordingly.
8
Table of contents
Other Elmdene Marine Equipment manuals
Popular Marine Equipment manuals by other brands

New Age
New Age PRM 402 Workshop manual

Onwa
Onwa KEC-30 Operator's manual

Furuno
Furuno FA-30 Setup, installation and troubleshooting tips

Furuno
Furuno FMD-3200-BB instruction manual

Pfannenberg
Pfannenberg DS10-SIL Instruction Manual/Safety Manual

Marina
Marina BU3050 Installation, maintenance and operation manual