Type N551/N851 Packing Removal/Replacement
!
WARNING
Verify that the Emergency Shutoff Valve is Type N551,
and not the previous version Type N550, by conrming
that it is marked with “1” as shown in Figure 2 below.
Please refer to D450042T012 for Type N550/N850
packing removal/replacement Instruction Manual.
If the Type N551(1)’s operating handle closes slowly
or binds in a “no ow” condition, it could be from
binding in the packing gland area or from external
binding, such as a bent operating handle catching on
the latch block, etc. Check for some type of external
binding rst.
If the binding appears to be internal, it could be from
uneven or over-tightened gland bolts (key 33). Try
loosening these two bolts 1/2 turn each and tap the
shaft (key 15) lightly side to side to align the gland
and follower bearing. Snug the bolts down evenly,
only tight enough to prevent leakage. If this does not
free the handle, the packing must be removed and be
either cleaned or replaced.
Removal of Packing
Refer to Figure 25.
Note
Figure 1. Type N551 in a Closed Position.
Table 1. Replacement Parts to Order
DESCRIPTION KEY
RCN551T0012
2 washers 29
Packing stack* 30
O-ring 65
T12851T0012 Spring 28
T12841T0012 Follower 31
* Packing stack includes a black graphite female adaptor, a white Tetrauoroethylene
(TFE) packing ring and a white TFE male adaptor.