Evco EV3 Basic Split User manual

EVCOS.p.A.|EV3BasicSplit|Instructionsheetver.1.0|Code1043BSE103|Page1of3|PT49/18
EV3 Basic Split Split-version controllers for refrigerated units
I ENGLISH
- controllers for normal and low temperature units
- power supply 115... 230 VAC or 230 VAC (according to the model)
- cabinet probe and evaporator probe (PTC/NTC)
- door switch and multi-purpose input (according to the model)
- compressor relay 16 A res. @ 250 VAC
- sealed relays compliant with the standard EN 60079-15
- management of Embraco and Secop variable capacity compressors (according to the
model)
- management of 0-10 V compressor and fans (according to the model)
- output 12 VDC max. 30 mA (according to the model)
- alarm buzzer
- TTL MODBUS slave port for EVJKEY programming key, EVconnect app, EPoCA remote
monitoring system or for BMS
- hot or cold mode regulation.
Purchasing
code
Number of re-
lays
Power supply
Management of
variable capacity
compressors
Output 12 VDC
max. 30 mA
EV3SB22N7 2 230 VAC no no
EV3SB24N7 4 230 VAC no no
EV3SB54N9 4 115... 230 VAC yes yes
1 MEASUREMENTS AND INSTALLATION | Measurements in mm (inches)
1.1 User interface
To be fitted to a panel, snap-in brackets provided.
N.B.
The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in).
1.2 Control module
To be installed on an electrical panel, on spacers (not provided).
N.B.
Any metal parts must be far enough away so as not to compromise safety distances.
INSTALLATION PRECAUTIONS
- ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section
- do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks
- in compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2 ELECTRICAL CONNECTION
N.B.
- use cables of an adequate section for the current running through them
- to reduce any electromagnetic interference, locate the power cables as far away as
possible from the signal cables.
PRECAUTIONS FOR ELECTRICAL CONNECTION
- if using an electrical or pneumatic screwdriver, adjust the tightening torque
- if the device is moved from a cold to a warm place, humidity may cause condensation
to form inside. Wait for about an hour before switching on the power
- make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS
- disconnect the power supply before carrying out any type of maintenance
- do not use the device as a safety device
- for repairs and for further information, contact the EVCO sales network.
3 FIRST-TIME USE
1. Carry out the installation following the instructions given in the section MEASUREMENTS
AND INSTALLATION.
2. Power up the device as set out in the section ELECTRICAL CONNECTION: an internal
test will start up.
The test normally takes a few seconds; when it is finished the display will switch off.
3. Configure the device as shown in the section Setting configuration parameters.
Recommended configuration parameters for first-time use:
PAR. DEF. PARAMETER MIN... MAX.
SP 0.0 setpoint r1... r2
P0 1 type of probe 0 = PTC 1 = NTC
P2 0 temperature measurement unit 0 = °C 1 = °F
d1
0
type of defrost
0 = electric 1 = hot gas
2 = compressor stopped
Then check that the remaining settings are appropriate; see the section CONFIGURA-
TION PARAMETERS.
4. Disconnect the device from the mains.
5. Make the electrical connection as shown in the section ELECTRICAL CONNECTION,
without powering up the device.
6. To use the device with the Evconnect app, connect the EVIF25TBX module. To use the
device with the EPoCA remote monitoring system, connect the EVIF25TWX module.
When connecting to an RS-485 network, connect the EVIF22TSX interface. To activate
real-time functions, connect the EVIF23TSX module.
If using EVIF22TSX or EVIF23TSX, set the bLE parameter to 0.
7. Power up the device.
4 USER INTERFACE AND MAIN FUNCTIONS
4.1 Switching the device on/off
1. If POF = 1 (default), touch the ON/STAND-BY key for 4 s.
If the device is switched on, the display will show the P5 value ("regulation temperature" de-
fault); if the display shows an alarm code, see the section ALARMS.
LED ON OFF FLASHING
compressor switched
on
compressor switched
off
- compressor protection in pro-
gress
- setpoint being set
defrost or pre-drip ac-
tive -
- defrosting delay in progress
- dripping active
evaporator fans on
evaporator fans off
evaporator fan stop in progress
HACCP
HACCP alarm saved in
EVlink -
-
energy saving active
-
-
compressor mainte-
nance request
-
- settings in progress
- access to additional functions in
progress
°C/°F
temperature display
-
overcooling or overheating active
AUX auxiliary load on
auxiliary load off
- auxiliary load on from digital in-
put
- auxiliary load delay in progress
device switched off
device switched on
device being switched on/off
When 30 s have elapsed without the keys being pressed, the display will show the “Loc" label
and the keypad will lock automatically.
4.2 Unlocking the keypad
Touch a key for 1 s: the display will show the label “UnL”.
4.3 Setting the setpoint
Check that the keypad is not locked.
1. Touch the SET key.
2. Touch the UP or DOWN keys within 15 s to set the value within
the limits r1 and r2 (default "-40... 50”).
3. Touch the SET key (or take no action for 15 s).
4.4 Setting the evaporator fan speed (percentage of the maximum capacity; only
available for EV3SB54, if Ao1 = 3 and F30 = 0)
Check that the keypad is not locked.
1. Touch the SET key twice.
2. Touch the UP or DOWN keys within 15 s to set the value within
the limits F31 and F32 (default “50... 100”).
3. Touch the SET key (or take no action for 15 s).
4.5 Activating manual defrost (if r5 = 0, default)
Check that the keypad is not locked and that overcooling is not active.
1. Touch the UP key for 4 s.
If P3 = 1 (default), defrost is activated provided that the evaporator temperature is lower than
the d2 threshold.
4.6 Switching the cabinet light on/off (if u1c... u5c = 5)
1. Touch the ON/STAND-BY key.
4.7 Switching the load on/off using the key (if u1c... u5c = 10 or 11)
1. Touch the CABINET LIGHT key (for 2 s if u1c... u5c = 5).
If u1c... u5c = 6, the demisting heaters switch on for the u6 time.
4.8 Silencing the buzzer (if u9 = 1, default)
Touch a key.
If u1c... u5c = 11 and u4 = 1, the alarm output is deactivated.
5 ADDITIONAL FUNCTIONS
5.1 Activating/deactivating the overcooling, overheating and energy saving func-
tions in manual mode
Check that the keypad is not locked.
1. Touch the DOWN key.
FUNCTION CONDITION CONSEQUENCE
overcooling
r5 = 0, r8 = 1 and defrost-
ing not activated the setpoint becomes “setpoint -
r6”, for the r7 time
overheating
r5 and r8 = 1
the setpoint becomes “setpoint +
r6”, for the r7 time
energy saving
r5 = 0 and r8 = 2
the setpoint becomes “setpoint +
r4”, at maximum for the HE2 time
5.2 Activating the high or low humidity function (if F0 = 5)
Check that the keypad is not locked.
1. Touch the DOWN key for 1 s.
2. Touch the UP or DOWN key within 15 s to select the label “rH”.
3.
Touch the SET key for 2 s until the display shows the right label
for the function (only touch the key to see the function acti-
vated).
LAB. DESCRIPTION
rhL
low humidity function (evaporator fan with F17 and F18 if the compressor is
off, on if the compressor is on)
rhH high humidity function (evaporator fan on)
4. Touch the ON/STAND-BY key (or take no action for 60 s) to exit
the procedure.

EVCOS.p.A.|EV3BasicSplit|Instructionsheetver.1.0|Code1043BSE103|Page2of3|PT49/18
5.3 Displaying/deleting the compressor functioning hours
Check that the keypad is not locked.
1. Touch the DOWN key for 1 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
CH1 view compressor functioning hours (days)
CH2 view compressor 2 functioning hours (days) (if u1c... u5c = 1)
rCH delete compressor and compressor 2 functioning hours
3. Touch the SET key.
4. Touch the UP or DOWN key to set “149” (to select rCH).
5. Touch the SET key.
6. Touch the ON/STAND-BY key (or take no action for 60 s) to exit
the procedure.
5.4 Viewing the temperature detected by the probes
Check that the keypad is not locked.
1. Touch the DOWN key for 1 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
Pb1 cabinet temperature (if P4 = 0, 1, 2 or 4)
incoming air temperature (if P4 = 3)
Pb2 evaporator temperature (if P3 = 1 or 2)
Pb3 auxiliary temperature (if P4 = 1, 2, 3 or 4)
Pb4 calculated product temperature (CPT; if P4 = 3)
3. Touch the SET key.
4. Touch the ON/STAND-BY key (or take no action for 60 s) to exit
the procedure.
6 SETTINGS
6.1 Setting configuration parameters
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the PAS value (de-
fault “-19”).
4. Touch the SET key (or take no action for 15 s): the display will
show the label “SP”.
5. Touch the UP or DOWN key to select a parameter.
6. Touch the SET key.
7. Touch the UP or DOWN key within 15 s to set the value.
8. Touch the SET key (or take no action for 15 s).
9. Touch the SET key for 4 s (or take no action for 60 s) to exit the
procedure.
6.2 Setting the date, time and day of the week (if the EVIF25TBX, EVIF25TWX or
EVIF23TSX module is connected)
N.B.
- do not disconnect the device from the mains in the two minutes after setting the
date, time and day of the week
- if the device communicates with the EVconnect app or the EPoCA remote monitor-
ing system, the date, time and day of the week will be automatically set by the
smartphone or tablet.
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select the label “rtc”.
3. Touch the SET key: the display will show the label “yy” followed
by the last two figures of the year.
4. Touch the UP or DOWN key within 15 s to set the year.
5. Repeat actions 3 and 4 to set the next labels.
LAB. MEANING OF THE NUMBERS FOLLOWING THE LABEL
n month (01… 12)
d day (01… 31)
h hour (00… 23)
n minutes (00… 59)
6. Touch the SET key: the display will show the label for the day of
the week.
7. Touch the UP or DOWN key within 15 s to set the day of the
week.
LAB. DESCRIPTION
Mon Monday
tuE Tuesday
UEd Wednesday
thu Thursday
Fri Friday
Sat Saturday
Sun Sunday
8. Touch the SET key: the device will exit the procedure.
9. Touch the ON/STAND-BY key to exit the procedure beforehand.
6.3 Restoring factory (default) settings and saving customised settings
N.B.
- check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- saving customised settings overwrites the factory settings.
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the value.
VAL. MEANING
149 value for restoring the factory information (default)
161 value for saving customised settings
4.
Touch the SET key (or take no action for 15 s): the display will
show the label “dEF” (for setting the “149” value) or the label
“MAP” (for setting the “161” value).
5. Touch the SET key.
6. Touch the UP or DOWN key within 15 s to set “4”.
7.
Touch the SET key (or take no action for 15 s): the display will
show “- - -” flashing for 4 s, after which the device will exit the
procedure.
8. Disconnect the device from the power supply.
9. Touch the SET key for 2 s before action 6 to exit the procedure
beforehand.
7 CONFIGURATION PARAMETERS
N.B.
- parameters having column "PAR." in grey are not available for EV3SB22
- parameters having column "DEF." in grey are only available for EV3SB54.
NO.
PAR. DEF. SETPOINT MIN... MAX.
1 SP 0.0 setpoint r1... r2
NO.
PAR. DEF. ANALOGUE INPUTS MIN... MAX.
2
CA1
0.0
cabinet probe offset
-25... 25 °C/°F
if P4 = 3, incoming air probe
offset
3 CA2 0.0 evaporator probe offset -25... 25 °C/°F
4 CA3 0.0 auxiliary probe offset -25... 25 °C/°F
5 P0 1 type of probe 0 = PTC 1 = NTC
6 P1 1 enable decimal point °C 0 = no 1 = yes
7 P2 0 temperature measurement unit 0 = °C 1 = °F
8
P3
1
evaporator probe function
0 = disabled
1 = defrost + fans
2 = fans
3 = digital input
option 3 only available for
EV3SB22
9
P4
0
configurable input function
0 = digital input
1 = condenser probe
2 = critical temp. probe
3 = outgoing air probe
4 = evaporator probe 2
if P4 = 3, regulation tempera-
ture = product temperature
(CPT)
10
P5
0
value displayed
0 = regulation temperature
1 = setpoint
2 = evaporator temp.
3 = auxiliary temperature
4 = incoming air tempera-
ture
11
P7
50
incoming air effect to calculate
product temperature (CPT)
0... 100 %
CPT = {[(P7 x (incoming air)]
+ [(100 - P7) x
(outgoing air)] : 100}
12
P8 5 display refresh time 0... 250 s: 10
NO.
PAR. DEF. REGULATION MIN... MAX.
13
r0
2.0
setpoint differential
1... 15 °C/°F
if u1c... u5c 1, proportional
band
if Ao1 = 0... 3 or u5c = 0,
band compressor off (relative
to setpoint or setpoint - r0)
14
r1 -40 minimum setpoint -99 °C/°F... r2
15
r2 50.0
maximum setpoint r1... 199 °C/°F
16
r3 0 enable setpoint lock 0 = no 1 = yes
17
r4 0.0 setpoint offset in energy saving 0... 99 °C/°F
18
r5
0
hot or cold mode regulation
0 = cold mode
1 = hot mode
19
r6
0.0
setpoint offset in overcool-
ing/overheating 0... 99 °C/°F
20
r7 0 duration overcooling/overheating 0... 240 min
21
r8
2
DOWN key additional function
0 = disabled
1 = overcooling/overheating
2 = energy saving
22
r12
1
differential position r0
0 = asymmetrical
1 = symmetrical
23
r13
25.0
proportional band modulating
regulation (relative to setpoint)
0... 99 °C/°F
setpoint + r13
for Ao1 = 0... 3 or u5c = 0
24
r14
10
integral action time modulating
regulation 0... 99 min
25
r15
3
type of PWM compressor
1 = Embraco VEM
2 = Embraco VEG
3 = Embraco VNEK and
VNEU
4 = Secop VNL
5 = Secop 33... 133 Hz
not visible if r13 = 0
26
r16
0
percentage 0-10 V output for
compressor with minimum ca-
pacity
0 %... r17
27
r17
100
percentage 0-10 V output for
compressor with maximum ca-
pacity
r6... 100 %
not visible if r13 = 0
28
r18
0
maximum percentage modulating
regulation in energy saving
0... 100 %
0 = disabled
not visible if r13 = 0
NO.
PAR. DEF. COMPRESSOR MIN... MAX.
29
CP0
0
85 Hz PWM compressor time
from power-on 0... 100 s x 10
not visible if r13 = 0
30
CP1
50
percentage 0-10 V compressor
from power-on 0... 100 %
not visible if r13 = 0
31
CP3
100
percentage 0-10 V compressor in
cabinet probe alarm 0... 100 %
not visible if r13 = 0
32
CP4
0
maximum 0-10 V compressor-on
time 0... 240 min
not visible if r13 = 0
33
C0
0
compressor-on delay from
power-on 0... 240 min
34
C1
5
delay between two compressor
switch-ons 0... 240 min
35
C2 3 minimum compressor-off time 0... 240 min
36
C3 0 minimum compressor-on time 0... 240 s
37
C4
10
compressor-off time in cabinet
probe alarm 0... 240 min
38
C5
10
compressor-on time in cabinet
probe alarm 0... 240 min
39
C6
80.0
high condensation signal thresh-
old 0... 199 °C/°F
differential = 2 °C/4 °F
40
C7
90.0
high condensation alarm thresh-
old 0... 199 °C/°F
41
C8 1 high condensation alarm delay 0... 15 min
42
C9
5
cabinet temperature consecutive
time within proportional band to
operate compressor at max.
power
0... 99 h
0 = disabled
until cabinet temperature <
setpoint
43
C10
0
compressor days for mainte-
nance 0... 999 days
0 = disabled
44
C11 10 compressor 2 on delay 0... 240 s
45
C12
2
compressor hour value effect to
balance hours and switch-ons
(BHC)
0... 10
BHC = {[C12 x (compressor
hours)] + [C13 x (compres-
sor switch-ons)]}
46
C13
1
compressor switch-ons value ef-
fect to balance hours and switch-
ons (BHC)
0... 10
BHC = {[C12 x (compressor
hours)] + [C13 x (compres-
sor switch-ons)]}
47
C14
1
constraint between compressors
0 = function of C11
1 = function of r0
2 = function of C12 and C13
NO.
PAR. DEF. DEFROSTING (if r5 = 0) MIN... MAX.
48
d00
0
enable “b” mode parameters on
setpoint threshold 0 = no 1 = yes
49
d01
1.0
setpoint threshold to activate “b”
mode parameters r1... r2
activated if setpoint > d01
50
d0
8
automatic defrost interval
0... 99 h
0 = manual only
if d8 = 3, maximum interval
51
d0b
6
automatic defrost interval “b”
mode like d0
52
d1
0
type of defrost
0 = electric
1 = hot gas (do not use with
regulation with 2 com-
pressors)
2 = compressor stopped
53
d1b 2 type of defrost “b” mode like d1
54
d2 2.0 defrost end threshold -99... 99 °C/°F
55
d2b 4.0 defrost end threshold “b” mode like d2
56
d3
30
defrost duration
0... 99 min
if P3 = 1, maximum duration
57
d3b 20 defrost duration “b” mode like d3
58
d4 0 enable defrost at power-on 0 = no 1 = yes
59
d5 0 defrost delay from power-on 0... 99 min
60
d6
1
value displayed when defrosting
0 = regulation temperature
1 = locked display
2 = label dEF
61
d7 2 dripping time 0... 15 min
62
d7b 0 dripping time “b” mode like d7
63
d8
0
defrost interval count mode
0 = hours device on
1 = hours compressor on
2 = hours evaporator tem-
perature < d9
3 = adaptive
4 = in real time
64
d9
0.0
evaporation threshold for auto-
matic defrost interval count -99... 99 °C/°F
65
d11 0 enable defrost timeout alarm 0 = no 1 = yes
66
d15
0
compressor-on consecutive time
for hot gas defrost
-20... 99 min
if values are negative, drip-
ping heaters on time
67
d16
0
pre-dripping time for hot gas de-
frost 0... 99 min
68
d18
40
adaptive defrost interval
0... 999 min
if compressor on + evapora-
tor temperature < d22
0 = manual only
69
d19
3.0
adaptive defrost threshold (rela-
tive to optimal evaporation tem-
perature)
0... 40 °C/°F
optimal evaporation tempera-
ture - d19
70
d20
180
compressor-on consecutive time
for defrost 0... 999 min
0 = disabled
71
d21
200
compressor-on consecutive time
for defrost from power-on and
from overcooling
0... 500 min
if (regulation temperature -
setpoint) > 10°C/20 °F
0 = disabled
72
d22
-2.0
evaporation threshold for adap-
tive defrost interval count (rela-
tive to optimal evaporation tem-
perature)
-10... 10 °C/°F
optimal evaporation tempera-
ture + d22
73
d25
0
enable outgoing air probe for de-
frost in evaporator probe alarm 0 = no 1 = yes
74
d26
6
defrost interval in evaporator
probe alarm
0... 99 h
0 = manual only
if d25 = 1
NO.
PAR. DEF. ALARMS MIN... MAX.
75
A0
0
select value for high/low tem-
perature alarms
0 = regulation temperature
1 = evap. temperature
2 = auxiliary temperature
76
A1 0.0 low temperature alarm threshold -99... 99 °C/°F
77
A2
0
type of low temperature alarm
0 = disabled
1 = relative to setpoint
2 = absolute
78
A4
0.0
high temperature alarm thresh-
old -99... 99 °C/°F
79
A5
0
type of high temperature alarm
0 = disabled
1 = relative to setpoint
2 = absolute
80
A6
120
high temperature alarm delay
from power-on 0... 240 min
81
A7
15
high/low temperature alarm de-
lay 0... 240 min
82
A8
15
high temperature alarm delay
post-defrosting 0... 240 min
83
A9
15
high temperature alarm delay
from door closure 0... 240 min
84
A10
10
duration of power failure for sav-
ing alarm 0... 240 min
0 = disabled
85
A11
2.0
high/low temperature alarm re-
set differential 1... 15 °C/°F
86
A12
1
type of power failure alarm signal
0 = LED HACCP
1 = LED HACCP + label PF +
buzzer
2 = LED HACCP + label PF +
buzzer (if duration >
A10)
NO.
PAR. DEF. FANS MIN... MAX.
87
F0
1
evaporator fan mode in normal
function
0 = off 1 = on
2 = on if compressor on
3 = thermoregulated (with
regulation temperature
+ F1)
4 = thermoregulated (with
regulation temperature
+ F1) if compressor on
5 = function of F6
6 = thermoregulated (with
F1)
7 = thermoregulated (with
F1) if compressor on
88
F0b
1
evaporator fan mode in normal
function “b” mode like F0
89
F1
-4.0
evaporator fans regulation
threshold -99... 99 °C/°F
default -1.0 for EV3SB22
90
F2
0
evaporator fan mode in defrost
and drip mode
0 = off 1 = on
2 = function of F0
default 1 for EV3SB22
91
F2b
0
evaporator fan mode in defrost
and drip mode like F2
92
F3
2
maximum time evaporator fans
off 0... 15 min
default 0 for EV3SB22
93
F3b
2
maximum time evaporator fans
off like F3
94
F4
30
time evaporator fans off in en-
ergy saving 0... 240 s x 10
if F0 ≠ 5
95
F5
30
time evaporator fans on in en-
ergy saving 0... 240 s x 10
if F0 ≠ 5
96
F6
0
function for high/low humidity
0 = for low humidity (with
F17 and F18 if compres-
sor off, on if compressor
on)
1 = for high humidity (on)
97
F7
5.0
evaporator fans on threshold
from dripping (relative to set-
point)
-99... 99 °C/°F
setpoint + F7
98
F8
2.0
evaporator fans regulation
threshold differential 1... 15 °C/°F

EVCOS.p.A.|EV3BasicSplit|Instructionsheetver.1.0|Code1043BSE103|Page3of3|PT49/18
99
F9
10
evaporator fans off delay from
compressor off 0... 240 s
if F0 = 2 or 5
100
F11 15.0 condenser fans on threshold 0... 99 °C/°F
101
F12
30
condenser fans off delay from
compressor off 0... 240 s
if P4 ≠ 1
102
F13
2
condenser fans regulation
threshold differential
1... 25 °C/°F
0-10 V condenser fans pro-
portional band if Ao1 = 2
(relative to F11, F11 + F13)
103
F14
10
100 % start-up time for 0-10 V
condenser fans 0... 240 s
104
F15
100
maximum percentage 0-10 V
condenser fans in energy saving 0... 100 %
105
F17
60
time evaporator fans off in low
humidity
0... 240 s
if u1c... u5c = 16, activates
speed 2 evaporator fans
106
F18
10
time evaporator fans on in low
humidity 0... 240 s
107
F19
0
interval activation reversible
condenser fans 0... 240 h
108
F20
0
reversible condenser fans on
time 0... 240 min
109
F30
0
setting percentage 0-10 V evapo-
rator fans in normal function
mode
0 = touch SET key twice
1 = with F33
2 = automatic with F1, F31,
F32 and F36
110
F31
50
percentage 0-10 V output for
evaporator fans with minimum
capacity
0... 100 %
if F31>F32, F32 is relevant
111
F32
100
percentage 0-10 V output for
evaporator fans with maximum
capacity
0... 100 %
if F32<F31, F31 is relevant
112
F33
100
percentage 0-10 V evaporator
fans in normal function F31... F32
113
F34
10
Start up time 0-10 V
evaporator fans at F35 0... 240 s
114
F35
100
percentage 0-10 V evaporator
fans from power-on 0... 100%
115
F36
10
0-10 V evaporator fans
proportional band (relative to F1)
1... 25 °C/°F
F1-F36
116
F37
0
maximum percentage 0-10 V
evaporator fans in energy saving
0... 100%
NO.
PAR. DEF. DIGITAL INPUTS MIN... MAX.
117
i0
5
door switch input function
0 = disabled
1 = compressor + evapora-
tor fans off
2 = evaporator fans off
3 = cabinet light on
4 = compressor + evapora-
tor fans off, cabinet light
on
5 = evaporator fans off,
cabinet light on
118
i1
0
door switch input activation
0 = with contact closed
1 = with contact open
119
i2
30
door open alarm delay
-1... 120 min
-1 = disabled
120
i3
15
maximum time for inhibiting
regulation with door open -1... 120 min
-1 = until closed
121
i5
0
multi-purpose input function
0 = disabled
1 = energy saving
2 = alarm iA
3 = alarm iSd
4 = load 1 operated by on
key
5 = load 2 operated by on
key
6 = switches device on/off
7 = alarm LP
8 = alarm C1t
9 = alarm C2t
122
i6
0
multi-purpose input activation
0 = with contact closed
1 = with contact open
123
i7
0
multi-purpose input alarm delay
0... 120 min
if i5 = 3 or 7, compressor on
delay from alarm reset
124
i8
0
number of multi-purpose input
activations for high pressure
alarm
0... 15
0 = disabled
if i5 = 3
125
i9
240
counter reset time for high pres-
sure alarm 1... 999 min
126
i10
0
door closed consecutive time for
energy saving
0... 999 min
after cabinet temperature <
SP
0 = disabled
127
i13
180
number of door openings for de-
frost 0... 240
0 = disabled
128
i14
32
door open consecutive time for
defrost 0... 240 min
0 = disabled
NO.
PAR. DEF. DIGITAL OUTPUTS MIN... MAX.
129
u1c
0
K1 relay configuration
0 = compressor 1
1 = compressor 2
2 = evaporator fans
3 = condenser fans
4 = defrosting
5 = cabinet light
6 = demisting
7 = door heaters
8 = heaters for neutral zone
9 = dripping heaters
10= button-operated load 1
11= button-operated load 2
12= alarm
13= on/stand-by
14= evaporator fans 2
15= defrosting 2
16= speed 2 evaporator fans
17= reversible cond. fans
18= speed 2 cond. fans
130
u2c 2 K2 relay configuration like u1c
131
u3c 4 K3 relay configuration like u1c
132
u4c 5 K4 relay configuration like u1c
133
u5c
3
K5 relay configuration
0 = PWM compressor
1... 18 like u1c
134
u2
0
enable cabinet light and load in
stand-by using the key 0 = no 1 = yes
in manual mode
135
u3
0
alarm relay activation
0 = with alarm not active
1 = with alarm active
136
u4 1 enable silencing alarm output 0 = no 1 = yes
137
u5 -1.0 door heaters on threshold -99... 99 °C/°F
138
u5d
2.0
door heaters on threshold differ-
ential 1... 25 °C/°F
139
u6
5
duration demisting on
1... 120 min
1 = on/off by pressing key
140
u7
-5.0
neutral zone for heating thresh-
old (relative to setpoint)
-99... 99 °C/°F
differential = 2 °C/4 °F
setpoint + u7
141
u9 1 enable alarm buzzer 0 = no 1 = yes
NO.
PAR. DEF. ANALOGUE OUTPUTS MIN... MAX.
142
Ao1
5
analogue output configuration
0 = PWM compressor (r15)
1 = 0-10 V compressor
2 = 0-10 V cond. fans
3 = 0-10 V evap. fans
4 = disabled
5 = disabled
NO.
PAR. DEF. CLOCK MIN... MAX.
143
Hr0 0enable clock 0 = no 1 = yes
NO.
PAR. DEF. ENERGY SAVING (if r5 = 0) MIN... MAX.
144
HE2
0
maximum duration energy saving
0... 999 min
0 = until door opened
NO.
PAR.
DEF.
ENERGY SAVING IN REAL TIME
(if r5 = 0; visible if Hr0=1) MIN... MAX.
145
H01 0 energy saving time 0... 23 h
146
H02 0 maximum duration energy saving
0... 24 h
NO.
PAR.
DEF.
SWITCHING ON/OFF IN REAL
TIME (visible if Hr0=1) MIN... MAX.
147
Hon
h-
time device switch-on
0... h-
h- = disabled
148
HoF
h-
time device switch-off
0... h-
h- = disabled
149
Hc1
h-
1st time reversible condenser
fans on
0... h-
h- = disabled
for time F20
150
Hc2
h-
2nd time reversible condenser
fans on
0... h-
h- = disabled
for time F20
NO.
PAR.
DEF.
DEFROSTING IN REAL TIME (if
d8 = 4; visible if Hr0=1) MIN... MAX.
151
Hd1
h-
1st daily defrosting time
0... h-
h- = disabled
152
Hd2
h-
2nd daily defrosting time
0... h-
h- = disabled
153
Hd3
h-
3rd daily defrosting time
0... h-
h- = disabled
154
Hd4
h-
4th daily defrosting time
0... h-
h- = disabled
155
Hd5
h-
5th daily defrosting time
0... h-
h- = disabled
156
Hd6
h-
6th daily defrosting time
0... h-
h- = disabled
NO.
PAR. DEF. SECURITY MIN... MAX.
157
POF 1 enable ON/STAND-BY key 0 = no 1 = yes
158
Loc 1 enable keypad lock 0 = no 1 = yes
159
PAS -19 password -99... 999
160
PA1 426 1st level password -99... 999
161
PA2 824 2nd level password -99... 999
NO.
PAR.
DEF.
EVLINK DATA-LOGGING (visible
if Hr0=1) MIN... MAX.
162
rE0 15 data logger sampling interval 0... 240 min
163
rE1
1
select temperature for data log-
ger
0 = none 1 = cabinet
2 = evaporator
3 = auxiliary
4 = cabinet and evaporator
5 = all
NO.
PAR. DEF. MODBUS MIN... MAX.
164
LA 247 MODBUS address 1... 247
165
Lb
2
MODBUS baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
166
LP
2
MODBUS parity
0 = none 1 = odd
2 = even
NO.
PAR. DEF. EVLINK MIN... MAX.
167
bLE
1
activate EVlink
0 = no 1 = yes
> 1 = reserved
8 ALARMS
CODE
MEANING RESET TO CORRECT
Pr1 cabinet probe alarm automatic - check P0
Pr2 evaporator probe alarm automatic - check the integrity of the probe
Pr3 auxiliary probe alarm automatic - check electrical connection
rtc clock alarm manual set date, time and day of the week
AL low temperature alarm automatic check A0, A1 and A2
AH high temperature alarm automatic check A4 and A5
id door open alarm automatic check i0 and i1
PF
power failure alarm
manual
- touch a key
- check electrical connection
COH high condensation signal automatic check C6
CSd
high condensation alarm
manual
- switch the device off and on
- check C7
iA multi-purpose input alarm automatic check i5 and i6
iSd
high pressure alarm
manual
- switch the device off and on
- check i5, i6, i8, i9
LP low pressure alarm automatic check i5 and i6
C1t
compressor thermal switch
alarm automatic
check i5 and i6
C2t
compressor 2 thermal
switch alarm automatic
check i5 and i6
dFd
defrost timeout alarm
manual
- touch a key
- check d2, d3 and d11
9 TECHNICAL SPECIFICATIONS
Purpose of the control device: function controller.
Construction of the control device: built-in electronic device.
Housing:
user interface: black, self-extinguishing control module: open frame board.
Category of heat and fire resistance: D.
Measurements:
user interface: 75.0 x 33.0 x 39.5 mm
(2 15/16 x 1 5/16 x 1 9/16 in) control module: 66.5 x 107.5 x 31.0 mm (2
5/8 x 4 1/4 x 1 1/4 in).
Mounting methods for the control device:
user interface: to be fitted to a panel, snap-in
brackets provided control module: to be installed on an electri-
cal panel, on spacers (not provided).
Degree of protection provided by the casing:
user interface: IP65 (front) control module: IP00.
Connection method:
user interface: plug-in screw terminal blocks
for wires up to 2.5 mm²
control module:
- fixed screw terminal blocks for wires up to
2.5 mm²
- Pico-Blade connector.
Maximum permitted length for connection cables:
user-interface-control module: 10 m (32.8 ft) power supply: 10 m (32.8 ft)
analogue inputs: 10 m (32.8 ft) digital inputs: 10 m (32.8 ft)
analogue outputs: 3 m (9.84 ft) digital outputs: 10 m (32.8 ft).
Operating temperature: from 0 to 60 °C (from 32 to 140 °F)
Storage temperature: from -25 to 70 °C (from -13 to 158 °F).
Operating humidity:
relative humidity without condensate from
10 to 90%.
Pollution status of the control device: 2.
Compliance:
RoHS 2011/65/EC
WEEE 2012/19/EU
REACH (EC) Regulation no.
1907/2006
EMC 2014/30/EU LVD 2014/35/EU.
Power supply:
user interface: powered by the control mod-
ule
control module:
- 230 VAC (+10% -15%), 50/60 Hz (±3
Hz), max. 2 VA insulated in EV3SB22N7
and EV3SB24N7
- 115... 230 VAC (+10 % -15%), 50/60 Hz
(±3 Hz), max. 3.2 VA insulated in
EV3SB54N9.
Earthing methods for the control device: none.
Rated impulse-withstand voltage:
- 4 KV in EV3SB22N7 and EV3SB24N7
- 2.5 KV in EV3SB54N9.
Over-voltage category:
- III in EV3SB22N7 and EV3SB24N7
- II in EV3SB54N9.
Software class and structure: A.
Analogue inputs:
- 1 for PTC or NTC probes (cabinet probe) in
EV3SB22
- 2 for PTC or NTC probes (cabinet probe
and evaporator probe) in EV3SB24 and
EV3SB54
PTC probes: Type of sensor: KTY 81-121 (990 @ 25 °C, 77 °F)
Measurement field: from -50 to 150 °C (from -58 to 302 °F)
Resolution: 0.1 °C (1 °F).
NTC probes: Type of sensor: ß3435 (10 K@ 25 °C, 77 °F)
Measurement field: from -40 to 105 °C (from -40 to 221 °F)
Resolution: 0.1 °C (1 °F).
Digital inputs:
1 dry contact (door switch); not available for
EV3SB22.
Other inputs:
- 1 input can be configured for analogue in-
put (evaporator probe) or digital input
(door switch, dry contact) for EV3SB22
- 1 input can be configured for analogue in-
put (auxiliary probe) or digital input
(multi-purpose, dry contact) for EV3SB24
and EV3SB54
Contact Type of contact: 5 VDC, 1.5 mA
dry: Power supply: none
Protection: none.
Analogue outputs:
1 for PWM or 0-10 V signal (compressor in-
verter; only available for EV3SB54).
Other outputs:
1 for 12 VDC max. 30 mA (only available for
EV3SB54).
Signal Power supply: 12 VDC (+16 % -25 %), 20 mA max.
PWM: Frequency: 0... 150 Hz
Protection: none.
0-10 V
Signal: Minimum applicable imped-
ance: 1 K
Resolution: 0.01 V
Digital outputs:
- 2 with sealed electro-mechanical relay in
compliance with the EN 60079-15 stan-
dard in EV3SB22
- 4 with sealed electro-mechanical relay in
compliance with the EN 60079-15 stan-
dard in EV3SB24 and EV3SB54.
K1 relay: SPST, 16 A res. @ 250 VAC.
K2 relay:
SPST, 5 A res. @ 250 VAC (not available for
EV3SB22).
K3 relay:
SPDT, 8 A res. @ 250 VAC (not available for
EV3SB22).
K4 relay: SPDT, 16 A res. @ 250 VAC.
Type 1 or Type 2 actions: type 1.
Additional features of Type 1 or Type 2 ac-
tions: C.
Displays: custom display, 3 digit, with function icons.
Alarm buzzer: built-in.
Communications ports:
1 TTL MODBUS slave port for EVJKEY pro-
gramming key, EVconnect app, EPoCA re-
mote monitoring system or for BMS.
N.B.
The device must be disposed of according to local regulations governing the collection
of electrical and electronic equipment.
This document and the solutions contained therein are the intellectual property of EVCO and thus pro-
tected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the full
or partial reproduction and disclosure of the content other than with the express approval of EVCO. The
customer (manufacturer, installer or end user) assumes all responsibility for the configuration of the de-
vice.
EVCO accepts no liability for any possible errors in this document and reserves the right to make any
changes, at any time without prejudice to the essential functional and safety features of the equipment.
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
Tel. +39 0437/8422 | Fax +39 0437/83648
Other Evco Controllers manuals

Evco
Evco EVJ 200 Series User manual

Evco
Evco Vcolor 338 L User guide

Evco
Evco RICS 4.30 User manual

Evco
Evco c-pro 3 micro AHU Instructions for use

Evco
Evco EV3B71 User manual

Evco
Evco EVJ 500 Series User manual

Evco
Evco EV3B23 User manual

Evco
Evco Vcolor 539 Series User guide

Evco
Evco c-pro 3 NODE kilo User manual

Evco
Evco C-PRO NANO User manual