User’s Manual M40-T
FEMA ELECTRÓNICA - Page 8
The input menu selects the input signal range. Options avail-
able are Pt100/RTD 2 or 3 wires, and thermocouples J, K, T,
E, S, R, N, C, L and X.
Note - Thermocouple X is a linear signal at 10uV/ºC.
The temperature conguration menu sets the function param-
eters for Pt100/RTD and thermocouple sensors.
Degrees (DEG) - Value “ºC/ºF”. Select the temperature to be
displayed in celsius or fahrenheit degrees.
Pt100/RTD resolution (P.RES) - Value “1º/0.1º”. Resolution
for the Pt100/RTD. Select to display with degree or tenth of
degree resolution.
Offset (OFFS) - Value from “-9999” to “9999” counts. Offset
to be added to the reading. Both for Pt100/RTD and ther-
mocouples.
Thermocouple Cold Junction Compensation (T.CJC) -
Value “On/Off”. Select “On” for automatic CJC compensation
in the instrument. Select “Off” to disable the CJC compensa-
tion.
On break (ON.BK) - Value “to_h/to_l”. Select “To L” to make
the reading go to minimum, in case of probe broken. Select
“To H” to make the reading go to maximum in case of probe
broken.
Alpha (ALPH) - Value “385/390”. Select “385” or “390” ac-
cording to your Pt100/RTD sensor.
Hysteresis (HYSt) - Value from “0” to “9999”. Points of hyster-
esis. The hysteresis applies on the deactivation of the alarm.
Delay (DEL) - Value from “0.0” to “99.9” seconds. Delay to be
applied to the relay activation and deactivation. Relays are
activated and deactivated X seconds after the activation /
deactivation of the alarm. The delay affects only to the relays.
The delay does not affect to the front leds.
Setpoint2 (SET2) - Value from “-1999” to “9999”. Second
setpoint. The second setpoint allows for the creation of acti-
vation windows. If the alarm is congured as maximum with
setpoint 1000 and setpoint2 is congured at 1500, the alarm
will be activated between 1000 and 1500 and the alarm will
be deactivated when display is <1000 and >1500. Setpoint2
is affected on the same way as the setpoint with hysteresis
and delays.
Functions on this menu allow for conguration of the visu-
alization.
Steps (STEP) - Display changes on predened steps. Values
are 1, 2, 5, 10, 20 and 50. The display is made in steps of X
counts. For example, select a step of 20 will make the display
to change in steps of 20 (1420, 1440, 1460, ...).
Maximum (MAX) - Memory of maximum display. Indicates
the maximum value of display since the last reset of the
memory. Memory is reset on the following cases : manual
reset from the Conguration Menu (Maximum), change on
the input signal (Input), modication on the scaling (Scaling),
change on the decimal point (dP), modication of the linear-
ization segments, or instrument power-down.
Minimum (MIN) - Memory of minimum display. Indicates the
minimum value of display since the last reset of the memory.
Memory is reset on the following cases : manual reset from
the Conguration Menu (minimum), change on the input
signal (Input), modication on the scaling (Scaling), change
on the decimal point (dP), modication of the linearization
segments, or instrument power-down.
The instrument can manage up to 3 alarms. These alarms
control optional relays R1 (see section 2.1) which can be
installed at slots Opt1, Opt2 and Opt3. More alarms can be
achieved by installing special control modules R2, R4 and
R6. Conguration menus for special modules are not listed
in this document.
Active (ACT) - Value “ON/OFF”. Denes if the instrument
has to manage this alarm or not. Select “OFF” for alarm not
managed.
Type (TYPE) - Value “MAX/MIN”. Denes the behavior of
the alarm as maximum or minimum alarm. The alarms con-
gured as maximum are activated when the display value
is equal or higher than the setpoint. The alarms congured
as maximum are deactivated when the display is lower than
the setpoint. The alarms congured as minimum have the
inverse behavior.
Setpoint (SET) - Value from “9999” to “-1999”. Alarm set
point.
1.10.1 Input menu
1.10.3 Alarms
1.10.4 Display
Password (PASS) - Select a number to act as password. This
password will be requested when entering the Conguration
Menu. To deactivate the password select “Off”.
Factory Settings (FACT) - Factory default conguration.
Select “yES” to activate the factory default conguration.
Version (VER) - Firmware version installed.
Light (LIGH) - Luminosity. Select between 5 predened
levels of luminosity.
1.10.5 Tools
1.10.2 Temperature conguration