The PCU control system is a thermostat able to command of a three-
speed fan unit, the solenoid valves 230V on / off and a damper of 230V
bypass on / off.
It 'also equipped with an internal clock with the ability to program two time
slots on / off and setting the set point for three different time periods:
Weekly Monday-Friday (days 1 to 5), Saturday (day 6) and Sunday (day
7).
Two external temperature probes NTC 10k must be connected with the
PCU control unit for the management of the bypass damper.
Added the display internal probe, you will have a total of three displayed
temperature values.
The operation of the ventilation is adjusted manually with a special ven-
tilation button (3) or automatically when selected auto mode, in which
case the speed will grow to estrange the detected temperature from the
set point.
The heating / cooling valves are activated, depending on the operating
mode, as a function of the difference between the set point and the selec-
ted control probe, which can be the local probe on the control or one of
the two external probes.
During normal operation, the display area indicated by the number (7) the
written ROOM, and the temperature value displayed is that of the local
probe on the unit, if you press and hold the up arrow key, the display
changes to the temperature measured by the probe 1 (instead of the
clock appears NTC1 words), releasing and pressing arrow up, you have
the view of the probe 2 (NTC 2 words).
The display returns to the default value after about 5/2 of the lack of keys
pressure.
If you briefly press the Mode / Menu button switches between heating /
cooling mode and vice versa.
The bypass output drive takes place in a different way depending on the
mode of operation:
- During heating operation it has the bypass activated if the value mea-
sured by sensor 1 is below the set point and if the value detected by the
sensor S2 is greater than the set point
- During the cooling operation you will have the bypass activation if the
value measured by sensor 1 is greater than the set point and if the value
detected by the sensor S2 is below the set point
To make more selective the bypass action you can set a value in the
manufacturer menu in which the temperature probe must be higher /
lower than the set point of the value and no higher / lower simply (see
paragraph installer parameters).
Pressing and holding the Mode / Menu key switches in succession to the
following features:
- Night mode
- Manual mode or time slots (to be selected with the arrow keys)
- Programming clock (minutes, hours, current day)
- Programming time slots
The transition from one to the next function is highlighted by the different
symbols that start flashing on the display.
To change the parameters of its programming using the arrow keys while
the symbol of the function concerned flashes.
The parameter set is automatically stored at exit from the programming
that occurs automatically to the lack of the buttons pressed for about
5 seconds.