5.4 Connecting components
Port [X0], [X1], … Signal
0Input 0, 2, 4, …
1Input 1, 3, 5, …
2+24 V DC input 0, 2, 4, …
3+24 V DC input 1, 3, 5, …
40 V DC input 0, 2, 4, …
50 V DC input 1, 3, 5, …
Fig. 6
6 Conveying and storage
Observe specifications for the environmental and storage conditions
è13 Technical data.
7 Mounting
Mount the module as outlined in the “Instructions for using system CPX-E”
è1.1 Further applicable documents.
8 Installation
1. Make sure that the power supply is switched off.
2. Connect the lines to the terminal strips as outlined in the “Instructions for using
system CPX-E” è1.1 Further applicable documents.
9 Commissioning
You can find information on commissioning system CPX-E in the
“Instructions for using system CPX-E”. Information on the parameters can
be found in the “Description of system CPX-E” and the descriptions of the
modules being used è1.1 Further applicable documents.
Behaviour of the display components after error-free commissioning
[P] (red)1)
Off
1) Flashes once briefly at the initialisation of system CPX-E
Fig. 7
Information on troubleshooting in the event of incorrect behaviour can be
found in the “Description of system CPX-E” and the descriptions of the
modules being used è1.1 Further applicable documents.
10 Diagnostics and fault clearance
10.1 Diagnostics options
Various options are available for diagnosing errors:
– Internal system diagnostics
– LED indicators on the product
10.2 Internal system diagnostics
The internal system diagnostics process is described in the “Description
ofsystem CPX-E” and the module descriptions
è1.1 Further applicable documents.
10.3 LED indicators
Module error [P]1)
LED (red) Significance Remedy
Lights up
Short circuit/overload on sensor
supply or module defective
1. Eliminate short circuit/overload,
check connected sensors.
2. Switch the power supply UEL/SEN
off and on again.2)
Off
Normal operating status –
1) Flashes once briefly at the initialisation of system CPX-E
2) The need to perform this step depends on the setting of the “Behaviour after SCO” parameter
èDescription of the digital input modules CPX-E-…DI-…
Fig. 8
Status of input [X0.0], [X0.1], [X1.0], …
LED (green) Significance Remedy
Lights up
Input active (logic 1)
1-signal at the input
–
Off
Input inactive (logic 0)
0-signal at the input
–
Fig. 9
11 Maintenance
Note
Accumulation of heat due to reduced air supply to electronics.
Keep the ventilation slots free and regularly remove contamination.
12 Disposal
Dispose of the packaging and the product at the end of its useful life through
environmentally friendly recycling in accordance with applicable specifications.
13 Technical data
General
Key feature Specification/value
CPX-E-16DI CPX-E-16DI-P
General technical data of system CPX-E Description of system CPX-E
è1.1 Further applicable documents
Dimensions (length x width x height) [mm] 124.3 x 18.9 x 76.6
Product weight1) [g] 102
Mounting position Vertical/horizontal
Ambient temperature [°C] –5 … +60 (–5 … +50)2)
Storage temperature [°C] –20 … +70
Air humidity (non-condensing) [%] 0 … 95
Assigned address space (inputs/outputs) [bit] 16/–
Module code (CPX-E-specific) 29 33
Module identification E-16DI E-16DI-P
Degree of protection in accordance with
EN60529
IP20
Protection against electric shock
(protection against direct and indirect contact
to IEC 60204-1)
Through the use of PELV circuits
(protective extra-low voltage)
Electromagnetic compatibility To
EN 61000-6-2/-4
To
EN 61000-6-2/-4
and NE 21
1) Including linking
2) With horizontal mounting position
Fig. 10
Power supply
Key feature Specification/value
Operating voltage supply UEL/SEN [V DC] 24 ± 25 %
Intrinsic current consumption at nominal
operating voltage 24 V from UEL/SEN
[mA] Typically 15
Fig. 11
Digital inputs1)
Key feature Specification/value
CPX-E-16DI CPX-E-16DI-P
Number of inputs 16
Max. cable length [m] 30 –
Version [V DC] 0 … 30, positive logic (PNP)
Logic level (logic 0/1) [V DC] 5/11
Switch-on delay Can be parameterised
Signal extension Can be parameterised
Electrical isolation between the channels None
Sensor supply
Sensor supply voltage [V DC] 24 ± 25 %
Short-circuit protection Electronic
Trigger level [A] ,1.8
Characteristic Slow-blow
Behaviour after end of overload Can be parameterised
Voltage drop on short-circuit protection
(reduction of sensor supply voltage)
[V DC] 1
Reverse polarity protection 24 V USEN
against 0 V USEN
Yes
Potential difference between 0 V external
sensor supply and 0 V internal sensor
supply
Not permissible
1) Type 3, 24 V DC according to IEC 61131-2
Fig. 12