UL certification information
Product category code NRAQ/NRAQ7
File number E239998
Considered standards UL 61010-1, 3rd Edition, May 11, 2012, revised April 29, 2016
CAN/CSA-C22.2 No. 61010-1-12, 3rd Edition, revision dated April
29, 2016
UL 61010-2-201, 1st Edition, revised February 20, 2017
CSA-C22.2 No. 61010-2-201: 14, 1st Edition, issue date January
01, 2014
UL mark
Tab. 4 UL/CSA Certification Information
– Technical data and environmental conditions may be subject to change in order to comply with
Underwriters Laboratories Inc. (UL) certification requirements for the USA and Canada.
Observe deviations èTechnical data.
– The unit shall be supplied by a power source which fulfils the requirements on a limited-energy
circuit in accordance to IEC/EN/UL/CSA 61010-1 or on a Limited Power Source (LPS) in accord-
ance to IEC/EN/UL/CSA 60950-1 or IEC/EN/UL/CSA 62368-1 or a Class 2 circuit in accordance to
NEC or CEC.
2 Function
2.1 General
A digital output module provides digital outputs to connect electrical consumers. Valves, contactors or
display components, for example, can therefore be actuated with a voltage of 24VDC. Status and
error messages can be shown by LED indicators on the module. The module behaviour can be set
using parameters è 3 Parameterisation.
The power supply of the outputs is electronically protected from short circuit or overload. If this fuse is
tripped, the power supply of the output is switched off and the error is shown by an LED on the mod-
ule.
After the elimination of the short circuit or the overload, the power supply is not switched on again
until after the output is reset (default). This behaviour can be adjusted by parameters. The power sup-
ply of this output is then reactivated automatically without requiring reset of the output.
The electronic fuse of the module is slow-blowing. Electrical consumers with a temporarily higher cur-
rent requirement can therefore also be connected.
Function
6 Festo — CPX-E-...DO-... — 2020-01a