Fire-Lite FIRE-LITE 411UDAC Operating instructions

411UDAC
Fire Alarm Communicator
Installation, Programming, Troubleshooting
and Operating Instruction Manual
One Fire-Lite Place
Northford, CT 06472
Phone (203) 484-7161
FAX: (203) 484-7118 P/N 51073:D ECN 08-870
D
Document #51073
12/09/2008 Rev.

PrecauLarge.PMD 02/26/2007
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise follow-
ing the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These docu-
ments can be found at http:/www.systemsensor.com/html/
applicat.html. A study by the Federal Emergency Manage-
ment Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not providetimely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sens-
ing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flam-
ing fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently con-
sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or com-
prehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmis-
sion systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the require-
ments of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
FireAlarmSystemLimitations

PrecauLarge.PMD 02/26/2007
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and asso-
ciated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F and at a relative humidity of
93 ±2% RH (non-condensing) at 32 ±2°C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room tempera-
ture of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
Adherencetothefollowingwillaidinproblem-free
installationwithlong-termreliability:
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
CanadianRequirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications. This Class A
digital apparatus complies with Canadian ICES-003.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada. Cet
appareil numerique de la Classe A est conforme a la
norme NMB-003 du Canada.
FCC Warning
Installation Precautions

4411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Notes

411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 5
CHAPTER 1: Product Description ..................................................................................................................... 9
Product Features ............................................................................................................................................ 9
411UDAC Digital Communicator ..................................................................................................... 9
DP-2 Dress Panel ............................................................................................................................... 9
Specifications ................................................................................................................................................ 11
Circuits .......................................................................................................................................................... 12
Channels/Inputs ..................................................................................................................................... 12
Notification Appliance Circuit ............................................................................................................... 12
Output Circuits ....................................................................................................................................... 12
Auxiliary Relays .................................................................................................................................... 12
Earth Ground ......................................................................................................................................... 12
Controls and Indicators ................................................................................................................................. 13
411UDAC Controls and Indicators ................................................................................................... 13
Components and Accessories ........................................................................................................................ 14
Digital Communicator Operation .................................................................................................................. 14
Panel Configuration ...................................................................................................................................... 15
Operational Modes ........................................................................................................................................ 15
Normal Mode ......................................................................................................................................... 15
Real Time Clock Mode .......................................................................................................................... 15
Program Mode ....................................................................................................................................... 15
Troubleshoot Mode ................................................................................................................................15
Default Mode ......................................................................................................................................... 15
Telephone Requirements and Warnings ........................................................................................................ 16
Telephone Circuitry - PH1 & PH2 ......................................................................................................... 16
Digital Alarm Communicator: ............................................................................................................... 16
Telephone Company Rights and Warnings: ........................................................................................... 16
For Canadian Applications .................................................................................................................... 17
CHAPTER 2: Installation .................................................................................................................................... 18
Mounting Options ......................................................................................................................................... 18
Mounting ....................................................................................................................................................... 18
Transformer Mounting ...................................................................................................................... 18
Cabinet Dimensions and Knockout Locations ................................................................................... 19
411UDAC Backbox ........................................................................................................................... 20
Operating Power ........................................................................................................................................... 21
Operating Power Connections ........................................................................................................... 21
Battery Cable Connections ................................................................................................................ 22
Input Channels .............................................................................................................................................. 23
Wiring Initiating Device Circuits ...................................................................................................... 24
Typical Addressable FACP Connection to 411UDAC ...................................................................... 25
Output Circuits .............................................................................................................................................. 26
Notification Appliance Circuit Connections ...................................................................................... 26
Relay Installation ............................................................................................................................... 27
Programmable Relay ......................................................................................................................... 27
Telephone Circuits ........................................................................................................................................ 28
Wiring Phone Jacks ........................................................................................................................... 28
Optional Programmer .................................................................................................................................... 29
Programmer Connection to 411UDAC ............................................................................................. 29
UL Power-limited Wiring Requirements ...................................................................................................... 30
Typical UL Power-limited Wiring Diagram ...................................................................................... 30
CHAPTER 3: Modes of Operation ..................................................................................................................... 31
Normal Mode ................................................................................................................................................ 31
Programmer Key Functions ................................................................................................................... 32
Programmer Keypad .......................................................................................................................... 32
Programmer Display .............................................................................................................................. 33

6411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Real Time Clock Mode ................................................................................................................................. 34
Program Mode .............................................................................................................................................. 35
DACT Programming .............................................................................................................................. 36
Ademco Contact ID Format - Primary .............................................................................................. 39
4+2 Standard and 4+2 Express Formats - Primary ............................................................................ 40
All 3+1, 4+1 and 4+2 Expanded Formats - Primary .......................................................................... 41
Ademco Contact ID Format - Secondary ........................................................................................... 44
4+2 Standard and 4+2 Express Formats - Secondary ........................................................................ 45
All 3+1, 4+1 and 4+2 Expanded Formats - Secondary ...................................................................... 46
411UDAC Operational Modes .......................................................................................................... 47
Verification Timing Diagram ............................................................................................................ 50
Restoral Methods ...............................................................................................................................51
Default Mode ................................................................................................................................................ 53
Troubleshoot Mode ....................................................................................................................................... 53
Handset/Speaker Connection ............................................................................................................. 54
CHAPTER 4: Central Station Communications ............................................................................................... 55
Format Selection Addresses ( 20 and 50) Programming ................................................................... 56
Format Selection Address Explanation .............................................................................................. 57
Transmittal Priorities .............................................................................................................................. 58
Ademco Contact ID Format Event Code Description ............................................................................ 59
Compatible UL Listed Receivers ....................................................................................................... 60
CHAPTER 5: Remote Site Upload/Download ................................................................................................... 61
General .......................................................................................................................................................... 61
Security Features .................................................................................................................................... 62
Downloading to the Communicator .............................................................................................................. 63
Uploading From the Communicator ............................................................................................................. 63
Simultaneous Data Transfers ......................................................................................................................... 64
CHAPTER 6: Battery Calculations .................................................................................................................... 65
Battery Calculations .......................................................................................................................... 65
411UDAC Power Supply .............................................................................................................................. 66
Load in Standby ................................................................................................................................. 66
Load in Alarm .................................................................................................................................... 66
Programming Sheets ...............................................................................................................................................67
Digital Communicator Options Program Sheets .............................................................................................. 67
Digital Communicator Options Program Sheet (Factory Defaults) ................................................................. 69
Event Codes/Transmission Format Programming Sheets ................................................................................. 71
4+2 Standard & 4+2 Express Formats Primary Central Station ...................................................................... 71
4+2 Standard & 4+2 Express Formats Secondary Central Station .................................................................. 71
4+2 Standard & 4+2 Express Formats Primary Central Station ...................................................................... 72
4+2 Standard & 4+2 Express Formats Secondary Central Station .................................................................. 72
All 3+1, All 4+1 and 4+2 Expanded Formats for Primary Central Station ...................................................... 73
All 3+1, All 4+1 and 4+2 Expanded Formats for Secondary Central Station .................................................. 73
All 3+1, All 4+1 and 4+2 Expanded Formats for Primary Central Station (Factory Defaults) ....................... 73
All 3+1, All 4+1 and 4+2 Expanded Formats for Secondary Central Station (Factory Defaults) .................. 73
Ademco Contact ID Format Primary Central Station ...................................................................................... 74
Ademco Contact ID Format Secondary Central Station .................................................................................. 74
Ademco Contact ID Format Primary Central Station (Factory Defaults) ........................................................ 75
Ademco Contact ID Format Secondary Central Station (Factory Defaults) .................................................... 75
Ademco Contact ID Format Event Code Description ........................................................................................ 76
Events and Default Event Codes .......................................................................................................................... 80
Operational Modes ................................................................................................................................................ 81
Canadian Applications .......................................................................................................................................... 82

This digital communicator/transmitter has been designed to comply with standards set forth by the following
regulatory agencies:
• Underwriters Laboratories Standard
• NFPA 72 National Fire Alarm Code
• CAN/ULC - S527-M99 Standard for Control Units for Fire Alarm Systems
NFPA Standards
Central Station Signaling Systems Protected Premises Unit (Automatic, Manual and Waterflow)
Proprietary Fire Alarm Systems (Protected Premises Unit)
Remote Station Fire Alarm Systems
Automatic Fire Detectors
Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems
Inspection, Testing and Maintenance for Fire Alarm Systems
Underwriters Laboratories Documents:
UL 217 Smoke Detectors, Single and Multiple Station
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1635 Digital Alarm Communicator System Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems
This Class (A) digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL
864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the
approval of the local Authority Having Jurisdiction (AHJ).
Before proceeding, the installer should be familiar with the following documents.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 7

8411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
+
+
+
TB4
B+
NAC +12V POWER
+B- -
TB1
RELAY 2RELAY 1
NO NONC NCCC
Relay 2
(nonsupervised)
Common
NC Contact
NO Contact
Relay 1
(nonsupervised)
Common
NC Contact
NO Contact
NAC B+
NAC B-
+12 VDC Resettable
- Resettable (common)
Zone 1 B+
Zone 1 B-
Zone 2 B+
Zone 2 B-
Zone 3 B+
Zone 3 A+
Zone 3 A-
Zone 3 B-
Zone 4 B+
Zone 4 B- Phone Line 1
Phone Line 2
Relay K5 and K6
PRO-411
DACT
Programmer
Battery Connector
(supervised, nonpower-limited)
AC Power Connector
(supervised, nonpower-limited)
Earth
AC Neutral
AC Hot
411UDABD.CDR
411ANAC.CDR
411AREL.CDR
- +
HIGH VOLTAGE
CAUTION!
Transformer
JumperJ8must
be installed for
proper panel
operation
All Circuits on TB2 and TB4 are
supervised and power-limited
hinged cover must be
closed after wiring

411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 9
Product Description
CHAPTER 1 Product Description
The 411UDAC is a fire alarm communicator with four input/channels and dual telephone lines. The four inputs use
conventional input devices. The 411UDAC accepts waterflow devices, two-wire smoke detectors, four-wire smoke
detectors, pull stations and other normally-open contact devices. The unit also supervises AC voltage, telephone line
input voltage/current, battery level and battery charger operation.
Outputs include one supplementary NAC (Notification Appliance Circuit), two programmable Form-C relays and 12
VDC resettable special application power. The 411UDAC interfaces with the public switched telephone network and
is compatible with most central station receivers. A total of fifteen popular communications formats are supported,
including the industry standard Ademco Contact ID. The communicator also contains a unique DACT option that
eliminates 'dialer runaway'. It restricts the transmission of any intermittent nuisance fault to 10 attempts in a 24 hour
period.
Accessories include the Fire-Watch 411 Series DACT Programmer (Model PRO-411) as well as the PK-411UD
Windows®95 based remote site programming software. The 411UDAC is supplied with a compact metal cabinet.
The digital communicator can be programmed or interrogated off-site via the public switched telephone network.
Any IBM compatible personal computer with Windows®3.1 or greater, with a 1200 baud Hayes®compatible modem
and Upload/Download software P/N PK-411UD, may serve as a service terminal.
1.1 Product Features
• Four input/channels - three fixed Style B (Class B) and
one Style A (Class A) or Style B (Class B)
• Programmable input channels
2-wire smoke (Inputs 1 & 3 only)
pull station
normally-open contact
host panel trouble (Slave Mode)
supervisory
supervisory autoresettable
waterflow (silenceable)
waterflow (nonsilenceable)
• One Style Y (Class B) NAC (supplementary application)
• Dual telephone lines
Dual telephone line voltage detect
Alternating phone lines for 24 hour test messages
• 12 VDC operation
• 1.6 amps total system power
• Alarm Verification
• Signal Silence Inhibit
• Autosilence
• Trouble Reminder
• Trouble Resound - troubles will resound the buzzer every 24
hours at midnight until the trouble is cleared
• Optional DP-2 Dress Panel (required for Canadian
applications)
FIGURE 1-1:411UDAC Digital Communicator
411UDACV.CDR
DP411A.CDR
FIGURE 1-2:DP-2 Dress Panel

Product Features
10 411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
• Industry first 20-digit central station and service terminal telephone numbers
• NAC coding per ANSI S-3.41 (Temporal Coding)
• Surface mount technology
• Separate external keypad and display
provides means of programming 411UDAC in program mode
provides means of testing input/output circuits (including telephone connections) in Troubleshoot Mode
• Compact in size 14.5" (36.83 cm) high X 12.5" (31.75 cm) wide X 2.875" (7.303 cm) deep metal cabinet
• Communicates vital status of monitored control panel (Slave Mode):
fire alarm
host control panel trouble
fire supervisory
AC (mains) power loss (programmable)
other
• Communicates vital status of 411UDAC:
digital communicator troubles
telephone Line 1 and 2 voltage fault
Primary Central Station number communication fault
Secondary Central Station number communication fault
system off-normal (local Program Mode entered)
24 Hour normal test
24 Hour abnormal test (24 hour test message with previously reported alarm or trouble still active)
• Individual LEDs for:
AC Power
System Trouble
Input Active
Supervisory
Communication Fail
Battery Trouble
Earth Fault
• Local piezo sounder with separate and distinct sounds for the various conditions
• Acknowledge/System Silence switch - 1st press silences local piezo sounder, 2nd press silences NAC
• Reset switch
• Real time clock
• Extensive transient protection
• Two Form-C relays, fully programmable to activate for the following conditions:
• Optional PK-411UD Remote Upload/Download Kit
• Industry-first, UL recognized 'dialer runaway' feature
• Industry-first user selectable restoral methods
fire alarm
host control panel trouble
fire supervisory (latching)
fire supervisory (autoresettable)
total communication failure
DACT trouble (factory default for relay)

411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 11
Specifications
1.2 Specifications
AC Power - TB3
120 VAC, 60 Hz, 0.3 amps
Wire size: minimum 14 AWG (2.00 mm2) with 600V insulation
Supervised, nonpower-limited
Battery (lead acid only) - J3
Maximum Charging Circuit: Normal flat charge - 13.7V @ 0.6 amps
Maximum Charger Capacity: 14 Amp Hour battery
Supervised, nonpower-limited
Channels/Inputs - TB2 Terminals 1 through 10
Programmable Channels 1 through 4
Power-limited circuitry
Fully supervised (monitored for opens, shorts and earth fault)
Normal Operating Voltage: 12.0 VDC (ripple = 100 mV maximum)
End-of-Line Resistor: 2.2K ohms, ½ watt (P/N 27070 UL listed)
Operation for each channel:
• Channel/Input 1, Style B (Class B) 2-wire smoke detector input and Channel/Input 3, Style B (Class B) 2-wire
smoke detectors or waterflows or Style D (Class A) waterflow input:
Note: Connecting 2-wire detectors on Channel/Input 3 requires NFPA Style B (Class B) only.
Alarm Current: 11 mA
Short Circuit Current: 24 mA maximum
Maximum Detector Current in Standby: 2 mA
Maximum Loop Resistance: 30 ohms
Detector Loop Current is sufficient to ensure operation of a minimum of one alarmed detector per
zone
Standby Current: 5.17 mA (including End-of-Line Resistor)
• Channel/Input 2 and Channel/Input 4 - Style B (Class B) contact closure input:
Short Circuit Current: 4.46 mA maximum
Maximum Loop Resistance: 100 ohms
Standby Current: 2.66 mA
Refer to Device Compatibility Document for listed compatible devices
Notification Appliance Circuit - TB4 Terminals 1(+) & 2(-)
The 411UDAC Notification Appliance Circuit may only be used to supplement host panel NACs
Style Y (Class B) power-limited and supervised circuit (monitored for opens, shorts and earth fault)
Maximum voltage drop in wiring: 2.0 VDC
Operating voltage nominal 13.8 VDC
Current for all external devices: 1.0 amp
End-of-line resistor: 2.2K ohms, ½ watt (P/N 27070)
Refer to Device Compatibility Document for listed compatible devices
Two Form-C Relays - TB1 Terminals 1 through 6
Operating voltage nominal 12 VDC
Contact rating: 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive)
Nonsupervised
12 VDC Resettable Special Application Power - TB4 Terminals 3(+) and 4(-)
Operating voltage nominal 12 volts Maximum ripple voltage: 10 mVRMS
Up to 200 mA is available for powering 4-wire smoke detectors
Power-limited and supervised circuitry. Recommended maximum standby current is 50 mA
Notes:
1. For power supply and battery calculations, refer to Chapter 6

Circuits
12 411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
1.3 Circuits
The 411UDAC circuit board utilizes surface mount technology and contains a MicroController Unit (MCU), dual
modular phone line jacks, piezo sounder, two sockets for optional programmable relays and connectors for input, out-
put and power wiring. A piezo silence switch and reset switch are provided on the membrane panel which plugs into
connector J7 on the main circuit board.
1.3.1 Channels/Inputs
Four input channels are provided on the 411UDAC. The 411UDAC can be used to monitor a host FACP (Fire
Alarm Control Panel) in Slave Mode or as a stand-alone FAC (Fire Alarm Communicator). Each input can be
programmed to monitor the following conditions:
• fire alarm activation
• 2-wire smoke (channels 1 & 3 only)
• pull station
• normally open contact device
• waterflow
• trouble activation
• fire supervisory activation
1.3.2 Notification Appliance Circuit
One Style B NAC (Notification Appliance Circuit) requiring a 2.2K ohm End-of-Line resistor. This NAC can
only be used to supplement host panel NACs.
1.3.3 Output Circuits
• Modular jacks are used to interface the primary and secondary phone lines to the public telephone network.
Phone lines are fully supervised at all times (if communication is enabled).
• 12 volt resettable special application power output (200 mA)
• 12 volt battery charger will charge up to 14 AH batteries
1.3.4 Auxiliary Relays
Two dry Form-C relays (P/N: 411RK), with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30
VAC (resistive), are installed on the main circuit board. Each relay is programmable for:
Alarm
Fire supervisory - latching
Fire supervisory - autoresettable
Host panel trouble
DACT trouble
Total communications failure
1.3.5 Earth Ground
Connect a separate earth ground wire to ground stud in backbox for transient protection (refer to Figure 2-4 on
page 21 for location of stud).

411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 13
Controls and Indicators
1.4 Controls and Indicators
Front Panel Switch
• Reset Switch - to reset 411UDAC circuits
• Acknowledge/System Silence Switch
press once to acknowledge alarm or trouble (silence local 411UDAC piezo sounder and change all
flashing LEDs to steady on)
press a second time and hold for minimum of two seconds to perform a System Signal Silence (silence
Notification Appliance Circuit)
411UDAC Piezo Sounder
• The 411UDAC piezo sounder is used to locally annunciate DACT alarms and troubles. DACT troubles
include input channel open circuit, NAC fault, phone line 1 or 2 voltage fault, phone number 1 or 2
communication fault and total communication failure. Separate and distinct sounds are provided for the
following conditions:
alarm - steady On
trouble - 1 second On and 1 second Off
supervisory - ½ second On and ½ second Off
Front Panel Indicator
• AC Power - green LED
• Input Active - green LED
• Communication Fail - yellow LED
• System Trouble - yellow LED
• Supervisory - yellow LED
• Battery Trouble - yellow LED
Circuit Board Indicator
• Earth Fault - yellow LED (indicates zero impedance between panel and earth ground)
FIGURE 1-3:411UDAC Controls and Indicators
411ACDSP.CDR

Components and Accessories
14 411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
1.5 Components and Accessories
Main Circuit Board
The main circuit board contains the system’s MCU (microcontroller unit), power supply, other primary
components and wiring interface connectors. The main circuit board is shipped in the same carton as the cabinet
but is not mounted in the cabinet. The circuit board should be installed only after the cabinet is mounted to the
wall and the area is clean and free of potential contaminants.
Cabinet
The cabinet is red and measures 14.5" (36.83 cm) high X 12.5" (31.75 cm) wide X 2.875" (7.303 cm) deep. It
provides space for up to two 7 Amp Hour batteries which must be ordered separately. A dress panel, which
mounts inside the cabinet, is also available. A supplied bezel must be installed in the door opening.
Dress Panel
An optional dress panel (P/N: DP-2) is available (required for Canadian installations). The dress panel restricts
access to the system wiring while allowing access to the membrane switch panel. See Figure 1-2 on page 9.
Transformer Assembly
One transformer is shipped in the same carton as the cabinet and main circuit board but not mounted in the
cabinet. The transformer should be installed before the cabinet is mounted to the wall.
Fire•Watch 411 Series DACT Programmer (Model PRO-411)
The PRO-411 is an optional DACT programmer which can be used to troubleshoot and program the 411UDAC,
as well as access the various modes of operation. The PRO-411 must be ordered separately.
PK-411UD Upload/Download Software Kit
The optional PK-411UD Kit consists of the PK-411UD Upload/Download software on 3½” disk and the
PK-411UD Program Manual. The PK-411UD enables a user to program the 411UDAC off site via the public
switched telephone network using any personal computer with Windows®3.1 or greater or Windows®95 and a
1200 baud Hayes®compatible modem.
1.6 Digital Communicator Operation
The 411UDAC has been designed to be compatible with a wide variety of fire alarm, nonfire and combination control
panels (Slave Mode operation). Numerous formats are also available for communication to a central station. Two
modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the Pri-
mary and Secondary phone lines. The digital communicator provides the following functions:
• Line Seizure- takes control phone lines, disconnecting any premise phones which may be using the same lines
• Off/On-Hook - perform on and off-hook status to phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) phone number - default is Touch-Tone®, programmable to rotary
• Discern proper Central Station 'ACK' and 'Kiss-off' tone(s)
• Transmit data to the Central Station(s)
• Verify data has been accepted by the Central Station(s)
• Hang-up and release phone lines
• Communicate in a variety of formats (Refer to Table 4-1, “Format Selection Addresses ( 20 and 50) Program-
ming,” on page 56).

411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 15
Panel Configuration
1.7 Panel Configuration
The 411UDAC can be configured, through programming, for the following modes of operation:
• Stand-alone Mode With Communicator Enabled - the 411UDAC functions as a latching digital alarm com-
municator in which all input circuit activations latch (except those programmed as autoresettable) and are
restored only by pressing the local reset switch. The onboard communicator will attempt to transmit events to
a Central Station
• Slave Mode With Communicator Enabled - the 411UDAC functions as a nonlatching slave to a host control
panel and the onboard digital alarm communicator will attempt to transmit events to a Central Station
• Slave Mode With Communicator Disabled - the 411UDAC functions only as a nonlatching slave to a host
control panel. The digital alarm communicator will not transmit to a Central Station
1.8 Operational Modes
1.8.1 Normal Mode
Normal Mode is the standard mode of operation in which the 411UDAC monitors the channel/input circuits as well
as telephone line voltage and other internal circuits. In addition to locally annunciating system trouble, active chan-
nel/input and communication fail, the onboard communicator transmits system status information to UL listed central
station receivers if programmed to do so. Transmitted data includes fire alarm, fire alarm trouble, supervisory alarm
and AC loss information. Specific digital communicator troubles are also transmitted.
1.8.2 Real Time Clock Mode
Real Time Clock Mode allows the user to change the digital alarm communicator’s internal 24 hour clock. Connect-
ing an external Programmer allows access to the various Modes of operation. While the 411UDAC is in Real Time
Clock Mode, it does not monitor channel inputs.
1.8.3 Program Mode
Program Mode is used to change the programmed functions of the 411UDAC. While the 411UDAC is in Program
Mode, it does not monitor channel inputs. In addition, some program items will be locked, which will prevent editing
while the communicator is active (dialing, transmitting, etc.).
1.8.4 Troubleshoot Mode
Troubleshoot Mode may be used to sample and display status for all channel/input circuits, Notification Appliance
Circuit, AC power, battery, charger and 12 volt resettable power. In addition, Troubleshoot Mode may be used for
testing the telephone line interconnect wiring. Connection from the 411UDAC’s modular jacks, through the RJ31X
jacks and into the telephone network may be easily checked. In this mode, the Programmer keypad acts similar to a
telephone touchpad. While the 411UDAC is in Troubleshoot Mode, it does not monitor channel inputs.
1.8.5 Default Mode
Default Mode may be used to return all 411UDAC programming back to the factory default settings and to reset the
Real-Time Clock to ‘00:01’ midnight. See “Default Mode” on page 53.

Telephone Requirements and Warnings
16 411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
1.9 Telephone Requirements and Warnings
1.9.1 Telephone Circuitry - PH1 & PH2
AC Ringer Equivalence Number (REN) = 1.2B
DC Ringer Equivalence Number (REN) = 0.0B
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all
areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be con-
nected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN
for the calling area.
1.9.2 Digital Alarm Communicator:
Before connecting the 411UDAC to the public switched telephone network, the installation of two RJ31X jacks is
necessary. The following information is provided if required by the local telephone company:
Manufacturer: Fire•Lite Alarms Inc./Notifier
One Fire-Lite Place
Northford, CT 06472
Product Model Number: 411UDAC
FCC Registration Number: OAAUSA-25431-AL-E
AC Ringer Equivalence: 1.2B
DC Ringer Equivalence: 0.0B
Note: FCC ID label is located on the inside cover.
Important! The DACT must not be used to dial a phone number that is call-forwarded per requirements of UL 864
9th Edition.
1.9.3 Telephone Company Rights and Warnings:
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in
its facilities, services, equipment or procedures which may affect the operation of this digital communicator. How-
ever, the telephone company is required to give advance notice of such changes or interruptions. If the digital com-
municator causes harm to the telephone network, the telephone company reserves the right to temporarily
discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In
such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems
and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
When the digital communicator activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The digital communicator must be connected to the public switched telephone network upstream of any private tele-
phone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to
the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.

411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 17
Telephone Requirements and Warnings
1.9.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
“NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equip-
ment meets certain telecommunications network protective, operational and safety requirements as prescribed in the
appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the
equipment will operate to the user’s satisfaction.”
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be installed using an acceptable method of connection. The
customer should be aware that compliance with the above conditions may not prevent degradation of service in some
situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the
supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the
telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone
lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly
important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection
authority, or electrician.
“The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum
number of terminals allowed to be connected to a telephone interface. The termination of an interface may consist of
any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
Representative: NOTIFIER/FIRE•LITE, CANADA
10 Whitmore Rd.
Woodbridge, Ontario L4L 7Z4
IC Certificate Number:
Ringer Equivalence Number (REN): 0.4B

Installation
18 411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
CHAPTER 2 Installation
2.1 Mounting Options
The cabinet may be either semi-flush or surface mounted. The door is removable during the installation period by
opening and lifting it off the hinges. The cabinet mounts using two key slots and two additional 0.25" diameter holes
located in the backbox. The keyslots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area
where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily
install and maintain the panel. Locate the top of the cabinet approximately five feet above the floor with the hinge
mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knock-
outs are provided for wiring convenience. Select the appropriate knockout(s) and pull the required conductors into
the box. Note that there are no knockouts on the left (hinged) side of the cabinet. All wiring should be in accordance
with the National and/or Local codes for fire alarm systems.
2.2 Mounting
Backbox Mounting
• Open the door and lift the door off the pin hinges
• Mark and predrill holes for the top two keyhole mount-
ing bolts using the dimensions shown in Figure 2-2 on
page 19
• Install two upper fasteners in the wall with the screw
heads protruding
• Using the upper 'keyholes', temporarily mount the
backbox over the two screws
• Mark the lower two holes, remove the backbox from
the wall and drill the lower two holes in the wall
• Before mounting the backbox to the wall, install the
supplied transformer in the backbox by sliding the bot-
tom transformer flange into the lower transformer
mounting slot. Position the hole in the top transformer
flange over the transformer mounting stud. Refer to
Figure 2-1 for the location of the slot and stud
• Secure the transformer with the supplied nut and
attached washer
• Mount the backbox to the keyhole mounting bolts, install and tighten the remaining fasteners
Main Circuit Board Mounting
• When the location is clean and free of construction dust or other contaminants, install the main PC board by
installing the four supplied standoffs on the four main circuit board mounting studs located in the backbox.
Refer to Figure 2-2, “Cabinet Dimensions and Knockout Locations,” on page 19
• Position the main circuit board’s four corner mounting holes over the four standoffs just installed. Be certain
to observe the proper ESD (Electro Static Discharge) precautions to prevent damage to the static sensitive
circuits. This includes, but is not limited to, use of a wrist strap
• Secure the main circuit board to the standoffs with the four supplied screws and attached washers
• Plug the transformer connector into the main circuit board connector J4. The connector is keyed and can only
be plugged-in one way. Refer to Figure 2-4 on page 21 and Figure 2-13 on page 30 for transformer connector
location and AC power connections
• When wiring is completed, install the door on the backbox pin hinges and the window bezel in the door
FIGURE 2-1:Transformer Mounting
Transformer
flange
Transformer
mounting slot
Transformer
mounting stud
Top of backbox
411XFRMT.CDR
Ground
Stud

411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 19
Mounting
12.625"
(32.068 cm)
14.625“ (37.148 cm)
16.625" (42.228 cm)
17.625"
(44.768 cm)
2.875“
(7.303 cm)
1.25“
(3.175 cm)
1.25“
(3.175 cm)
1.125“
(2.858 cm) 0.875“
(2.223 cm)
14.5“
(36.83 cm)
3.25“
(8.255 cm)
1.75“
(4.445 cm)
3.5“
(8.89 cm)
12.5“ (31.75 cm)
4.12“ (10.47 cm)
6.12“ (15.55 cm)
8.12“ (20.63 cm)
10.12“ (25.75 cm)
1.1“ (2.794 cm)
6.5“ (16.51 cm)
(7.62 cm)
3.0“
FIGURE 2-2:Cabinet Dimensions and Knockout Locations
5024JRBB.CDR
Main Circuit Board
Mounting Studs
Transformer
Mounting
Stud
Ground
Stud
Single
Transformer
Mounting
Slot
Double
Transformer
Mounting
Slot
Knockouts
Top (back)
Top (front)
TR-3-R Trim Ring

Mounting
20 411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Top
Bottom
Right Side
Door=12.714“ (32.294 cm)
Backbox=12.5“ (31.75 cm)
Door=14.714“ (37.374 cm)
Backbox=14.5“ (36.83 cm)
Depth=2.875“ (7.303 cm)
Depth=3“
(7.62 cm)
FIGURE 2-3:411UDAC Backbox
411ACABB.CDR
This manual suits for next models
1
Table of contents
Other Fire-Lite Security System manuals

Fire-Lite
Fire-Lite BG-12LA User manual

Fire-Lite
Fire-Lite Fire-Lite Alarms BB-17F Technical manual

Fire-Lite
Fire-Lite BG-12LAO User manual

Fire-Lite
Fire-Lite BG-12LO User manual

Fire-Lite
Fire-Lite ACM-16ATF User manual

Fire-Lite
Fire-Lite DACT-UD User manual

Fire-Lite
Fire-Lite Fire-Lite Alarms BB-26 User manual

Fire-Lite
Fire-Lite BG-12 Series User manual

Fire-Lite
Fire-Lite BG-12LR User manual

Fire-Lite
Fire-Lite Device User manual