3 of 5 Document 52033 Rev. C 02/19/08
MS-9600, MS-9600LS & MS-9600UDLS
(Software Version 1.2 or Greater)
NFPA 72 Auxiliary Protective Signaling System
(AlarmSignalTransmission)
For connection of initiating devices and modules in this system, refer to the MS-9600 Installation Manual, Document 51335.
This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions.
IMPORTANT! Thisapplication,utilizinganMBT-1andanMS-9600FACP,isonlypossiblewhentheMS-9600has
SoftwareVersion1.2orGreaterinstalled.
Note:MS-9600LSandMS-9600UDLSFireAlarmControlPanelsareFMApproved.
TB3 TB8
+ -
MS-9600
- To next device
+ on SLC Loop
Braided-shield/Drain Wire
Alarm polarity shown!
EOLR-1
Power Supervision Relay
White Wire
Brown Wire
CMF-300*
Connect wires to two
red terminals on box
Gamewell Model M34-56
Local Energy Municipal Box
Note: 10 ohms maximum loop re-
sistance due to wiring from power
supply to Municipal Box.
The CMF-300 must be programmed as
'Silenceable' and 'General Alarm.'
Red Black
SLC LOOP B
24VDC, Nonresettable
(Contacts shown in
energized position)
+ -
MBT-1
-
+
-
+
+ -
Shield
B
* If the SLC device does not match the one in
this figure, refer to the SLC Manual (docu-
ment #51309) wiring conversion charts for
legacy and newer versions of the modules.