manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. First Alert
  6. •
  7. Keypad
  8. •
  9. First Alert FA215KP User manual

First Alert FA215KP User manual

K3590-1V1 8/00
REMOTE KEYPADS
FA215KP, FA260KP, FA560KP
INSTALLATION GUIDE
Keypad Features FA215KP
Fixed-Word FA260KP
Fixed-Word FA560KP ✝
2-Line Alpha
Backlit Display NO YES (See Note 1) YES (See Note 1)
Dedicated Function Keys NO YES YES
Built-in Sounder Piezo Speaker Speaker
First Alert Pro Controls
FA110C* YES YES NO
FA120C* YES YES NO
FA142C* YES YES See Note 2
FA148C* YES YES See Note 2
FA162C* YES YES See Note 2
FA1220CV** YES YES See Note 2
FA1340C** YES YES See Note 2
FA1600C/CA/CB** NO NO See Note 3
FA2000C* YES YES See Note 2
✝The FA560KP must be used to program the FA142C, FA148C, FA162C, FA1220CV, FA1340C, FA1600C/CA/CB, & FA2000C controls.
* Use the non-addressable mode with these controls (set to address 31).
** Use the addressable mode with these controls (addresses 00-30).
Notes 1. Permanent display backlighting is an option on some controls (see the control's instructions for details).
2. The FA560KP is required for certain advanced user functions (see the control's instructions for details).
3. Use the FA560KP with the red color insert (provided for fire installations) as required by local authority having jurisdiction
GENERAL INFORMATION WIRING AND INSTALLATION
The FA215KP, FA260KP & FA560KP are addressable
Remote Keypads and are intended for use with the controls
listed in table above. Addresses are set via the keypad keys
(no DIP switches). See the table above for valid addresses.
The keys on the keypads are continuously backlit for
convenience except the FA215KP.
KEYPAD DISPLAYS AND LEDS
The keypads have the following features of the display:
Model Fixed
Word
Display
2-line
Alpha
Display
2-digit
Zone
Identifier
Custom Zone
Descriptors
FA215KP X X
FA260KP X X
FA560KP X X
The following table shows the LEDs and their functions:
LED Function
Red Lights when the system is armed in any mode
Green Lights when the system is "ready" to be armed.
SPECIAL FUNCTION KEYS
The keypads also feature function keys, see table below.
These keys may be programmed for panic alarms or other
special functions such as macros. See the control's
instructions for details. The FA215KP uses the key pairs
only. Function keys must be held down for at least 2
seconds to activate an alarm; key pairs activate
immediately.
FA260KP/FA560KP FA215KP
A ([1] & [*]) [1] & [*]
B ([*] & [#]) [*] & [#]
C ([3] & [#]) [3] & [#]
DNONE
The keypads can be surface mounted directly to a drywall, or to
a single- or double-gang electrical box.
1.
Remove the case back by pushing down two "snaps."
See diagram below.
2.
Route wiring from the control panel through the
opening in the case back.
3. Mount the case back to a wall or electrical box.
4.
Wire directly from the keypad’s terminal block to the
terminal block on the control board. Wire functions are
marked next to terminals. Labels are as follows: DI Data
In to Control Panel, - Ground, + Aux. Power Plus, DO Data
Out of Control Panel. See the control panel’s Installation
Instructions for more complete details.
5. Re-attach the keypad to its case back.
6. Remove the clear protective film from the LCD display.
Remove Case back by pushing in
the 2 "Snaps" along keypad's
bottom edge and pulling the case
apart
SETTING THE KEYPAD ADDRESS FUNCTION KEY LABELS
A set of adhesive-backed labels with some typical function
symbols (i.e., fire, police, personal emergency, etc.) is provided.
These labels can be placed on or next to the keys to identify
each key's function for the end user (as determined by the
control panel's capability and programming; see the control's
instructions).
SPECIFICATIONS
The keypad can either be set for an address of 00-30, or to
the non-addressable mode (31). The keypad's default
address is 31.
To change the keypad's address, do the following:
1. Enter address mode: Power up the keypad. Within 60
seconds of power-up, press and hold down the [1] and [3]
keys at the same time for 3 seconds. (If unable to enter
address mode, power up and try again.)
The current keypad address will be displayed, and the
cursor will be under the "tens" digit. If 10 seconds have
passed with no key entry, the keypad automatically
exits address mode. You must power down, power up
and start address mode again.
NOTE: The keypad will not enter address mode if the
panel to which it is connected is in programming mode.
2. Set the current address to "00": Press [0] to clear the
current "tens" digit. The cursor will move to the "ones"
digit position. Press [0] to clear the current "ones" digit.
The cursor will move back to the "tens" digit position.
3. Enter the keypad's address: Enter the proper "tens" digit
of the keypad's address. The cursor will move to the
"ones" digit position. Enter the proper "ones" digit of the
keypad's address. Note that address "31" sets the
keypad to non-addressable mode.
4. Exit address mode:
Press [
✱
] to save the displayed address and exit address
mode.
VIEWING THE KEYPAD ADDRESS
Press and hold down the [1] and [3] keys at the same time
for about 3 seconds. The current address is displayed. No
key entry is allowed. Press any key to exit or wait 10
seconds to exit viewing mode.
KEYPAD COLOR INSERTS
All three models include a cool gray color insert. An
additional RED label is provided with the FA560KP should
any local agency require it.
Physical:
FA215KP: 5-5/8"H x 4-3/8"W x 1-5/16"D
FA260KP: 6-5/8"H x 4-7/8"W x 1-5/16"D
FA560KP: 7-5/16"H x 5-3/8"W x 1-3/8"D
Wiring (all Keypads):
DI (Green): “Data In” to control panel
- (Black): Ground
+ (Red): +12VDC (Aux. Power)
DO (Yellow): “Data Out” from control panel.
Displays:
FA215KP, Fixed-Word LCD
FA260KP: Fixed-Word LCD (backlit).
FA560KP: 2 x 16 alpha-numeric supertwist LCD, backlit.
Sounder:
FA215KP: Piezo-electric (fire alarm is loud, pulsing single
tone; (all Keypads) burglary alarm is loud,
continuous, dual tone).
FA260KP, Speaker.
FA560KP: Speaker.
Current:
FA215KP: 55mA sounder on
35mA standby (alarm sounder off).
FA260KP: 150mA backlight and sounder on
75mA standby mode (backlight on).
FA560KP: 150mA backlight and sounder on
80mA standby mode (backlight on).
REFER TO INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED
FOR WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
175 Eileen Way, Syosset, New York 11791
Copyright 2000
¬.9Pl
K3590-1V1 8/00

This manual suits for next models

2

Other First Alert Keypad manuals

First Alert FA260RF User manual

First Alert

First Alert FA260RF User manual

First Alert FA570RF User manual

First Alert

First Alert FA570RF User manual

First Alert FA570CR Assembly instructions

First Alert

First Alert FA570CR Assembly instructions

First Alert FA560VKP User manual

First Alert

First Alert FA560VKP User manual

First Alert FA570RF User manual

First Alert

First Alert FA570RF User manual

First Alert TouchCenter FA701CKP User manual

First Alert

First Alert TouchCenter FA701CKP User manual

First Alert FA260KP-OM User manual

First Alert

First Alert FA260KP-OM User manual

First Alert FA270RF User manual

First Alert

First Alert FA270RF User manual

First Alert FA560VKP Assembly instructions

First Alert

First Alert FA560VKP Assembly instructions

First Alert FA220KP Assembly instructions

First Alert

First Alert FA220KP Assembly instructions

First Alert FA270RF Assembly instructions

First Alert

First Alert FA270RF Assembly instructions

First Alert FA270VKP Assembly instructions

First Alert

First Alert FA270VKP Assembly instructions

First Alert FA6150RF Assembly instructions

First Alert

First Alert FA6150RF Assembly instructions

First Alert TouchCenter FA701CVKP Assembly instructions

First Alert

First Alert TouchCenter FA701CVKP Assembly instructions

First Alert FA270VKP User manual

First Alert

First Alert FA270VKP User manual

First Alert 1220CV User manual

First Alert

First Alert 1220CV User manual

First Alert FA210RF User manual

First Alert

First Alert FA210RF User manual

Popular Keypad manuals by other brands

Gecko k-35-in Series Quick reference card

Gecko

Gecko k-35-in Series Quick reference card

Digital Monitoring Products XR5 user guide

Digital Monitoring Products

Digital Monitoring Products XR5 user guide

LEGRAND AU7010 Series installation instructions

LEGRAND

LEGRAND AU7010 Series installation instructions

X-keys XK-24-USB-R product manual

X-keys

X-keys XK-24-USB-R product manual

SEA ROCK quick start guide

SEA

SEA ROCK quick start guide

Russound KP4-KP6 instruction manual

Russound

Russound KP4-KP6 instruction manual

GTO F320 user guide

GTO

GTO F320 user guide

jablotron JA-60F manual

jablotron

jablotron JA-60F manual

Eldes EKB3W user manual

Eldes

Eldes EKB3W user manual

RemoteLock 2500 Series manual

RemoteLock

RemoteLock 2500 Series manual

APO DK-9826 MK-II Programming & installation manual

APO

APO DK-9826 MK-II Programming & installation manual

LEGRAND AU5009WH quick start guide

LEGRAND

LEGRAND AU5009WH quick start guide

Ketra X 2 installation guide

Ketra

Ketra X 2 installation guide

Velleman HAA2890 Programming & installation manual

Velleman

Velleman HAA2890 Programming & installation manual

Mottura XDIGIT 99.779 quick start guide

Mottura

Mottura XDIGIT 99.779 quick start guide

Gianni Industries DG-600H Specifications

Gianni Industries

Gianni Industries DG-600H Specifications

SECO-LARM Enforcer SK-1123-FDQ manual

SECO-LARM

SECO-LARM Enforcer SK-1123-FDQ manual

custom alarm Vista Quick reference guide

custom alarm

custom alarm Vista Quick reference guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.