• FWD, Rev, plus 3 Digital inputs configurable for Source or Sink.
• 0-10VDC analog inputs.
• 4-20mA analog input.
• Transistor outputs.
• Form C contact relay
o (250VAC 0.3A, cosØ=0.3), (48VDC, .5A).
• 24VDC max 200mA DC output power.
• 10VDC output for potentiometer.
• 24 VDC 50mA power source
Other Control Terminal
• RJ-45 keypad connection port.
FRENIC-Mini (C2) Quick Reference Guide
ON level 0V 2V
ON level 22V 27V
Orange = Outputs, Yellow = Analog Inputs, Blue = Digital Inputs
Control Card Terminals FRENIC-Mini (C2)Control Wiring
Note 1:
When connecting a DC REACTOR (DCR) (option), remove the jumper
bar from across the terminals [P1] and [P (+)].
For single-phase 100V input series, DCR shall be connected to the
point that is shown below.
Note 2:
Install a recommended molded-case circuit breaker (MCCB) or an earth leakage circuit breaker (ELCB) (with an
overcurrent protection function) in the primary circuit of the inverter to protect wiring. At this time, ensure that the
circuit breaker capacity is equivalent to or lower than the recommended capacity.
Note 3:
Install a magnetic contactor (MC) recommended for each inverter to separate the inverter form the power supply,
apart from the MCCB or ELCB, when necessary. Connect a surge suppressor in parallel when installing a coil such
as the MC or solenoid near the inverter.
Note 4:
(THR) is available when one of terminal functions for X1 to X3, FWD, REV (function code E01 to E03, E98 or E99)
is set to the data “9”.
Note 5:
Frequency can be set by connecting a frequency setting device (external potentiometer) among the terminals 11, 12
and 13 instead of inputting voltage signal (0 to +10V DC, 0 to +5V DC or +1 to +5V DC) between the terminals 12
and 11.
Note 6:
For the control signal wires, use shielded or twisted wires. Ground shielded wires. To prevent malfunction due to
noise, keep the control circuit wiring away from the main circuit wiring as far as possible (recommended:
10cm(3.94inches) or more), and never set them in the same wire duct. ⓔ
When crossing the control circuit wiring with the main circuit wiring, set them at right angles.
Note 7:
Three –phase 4wire cable is recommended for motor wiring to reduce the noise emitted. Connect the motor
grounding wire to the inverter grounding terminal G
Y1 Y1E FMA C1 PLC X1 X2 X3
11 12 13 11 CM FWD REV CM
〜
( )
( ) ( )
()
( 1)
( )
()
( )
( )
+
−
( )
:
:
:
:
:
( )
( )
( )
( )
()
( )
‐
( )
( )
( )