(Optional extra)
Mounting bracket.
Fix base to wall in 4 positions.
2. Fixing Details
25-5644 Iss A
Knockout or drill required cable gland holes, and fix required
1. Installation
Dimensions
Industrial Sounder/Beacon (230Vac)
Specification
5. Sounder Assembly
4. Sounder Settings
155mm
212mm
168mm
ASSERTA
2
4
3
1
Switch 1 bit 4 is to select voice (0)/ no voice (1). (Where fitted)
Minutes
(Stage 3 Tone is dependent on the setting of switch 2)
Turn dial clockwise to increase volume.
010X10110X
6
6
4. Switch 3 (Stage 2 tone selection)
3. Switch 2 (Stage1 tone selection)
OPEN
321 54
0 = Open
1 = Closed
OPEN
12345
See table overleaf.
See table overleaf.
101X
100X 20
15 001X
000X
2. Switch 1 (Time out setting)
(Nominal 20dB range)
1. Volume Control
OPEN
321 4 MinutesBIT 123X
111X 5011X
BIT 123X
30
40
∞
25
0°
90°
cable glands.
148mm
117
N
COM
L
Stage 3
Stage 1
Stage 2
N
L
N
L
L
N
Ensure that guide
ribs are aligned.
(Top & Bottom)
WARNING : On some tones the output level can exceed 120dB(A) @ 1m.
: Consult the relevant or appropriate health and safety regulations for guidelines.
Tones Table overleaf.
: Do not remove cover, refer servicing to qualified personnel.
: High voltage present within this equipment.
NOTE : Polar dispersion information available in the technical manual. (Ref:M03-003)
Ingress Protection
Termination
Specification
Current Consumption
Operating Temperature
Operation
Operating Voltage Range
Sound Output @ 1m
Construction
Tones
230Vac 110dB(A)
Continuous
230Vac 50/60Hz
0.28~2.5mm² cable
ABS /PC FR plastic
-25°C to +75°C
See table overleaf
39mA@230Vac
42 see table overleaf
IP66
230Vac 50/60Hz
42 see table overleaf
65mA@230Vac
See table overleaf
-25°C to +75°C
ABS /PC FR plastic
0.28~2.5mm² cable
IP66
Continuous
230Vac 120dB(A)
1. Plug the 5 way ribbon cable into the base header.
2. Plug the 2 way ribbon cable into the base header.
3. Ensure that the top indicator on the base is aligned with the top indicator on
the sounder, and push the sounder onto the base.
4. Secure the sounder to the base using the bolts provided.
230Vac 50/60HzOperating Voltage Range
Ingress Protection
Termination
Construction
Operating Temperature
Current Consumption
0.28~2.5mm² cable
IP66
15mA
-25°C to +75°C
ABS /PC FR plastic
Beacon 230Vac
Sounder
NOTE: Ensure that the IP integrity
is maintained during gland
fitting.Take care not to disturb the
electronics while drilling.Remove
PCB if required)
3. Connection
NOTE: A readily accessible
disconnect device must be
incorporated in the mains
supply wiring to this unit.
}
}
Beacon
Sounder
Fuse 80mA Antisurge, 20mm
Ensure that the mains switch is set to 230V.
Fuse 80mA Antisurge, 20mm 80mA Antisurge, 20mm
Rating 2 Joules
Hole positions for additional cable entries.
Knock outs for cable entries.
(Top & Bottom)