
MTA7912 Service Manual
When WARMING a patient in MODERATE or GRADUAL modes,
water temperatue is limited to a maximum of 41.0°C and a
minimum which is determined by the current CONTROL OPTION
selected (15°C below the patient temperature in MODERATE
mode an 10°C below the patient temperature in GRADUAL
mode).
When using AUTO MODERATE and AUTO GRADUAL for patient
warming, NO MANUAL INTERVENTION is required once the
patient set point temperature has been selected for warming.
If the patient temperature deviates from the warming rate
specied by the CONTROL OPTION selected (MODERATE or
GRADUAL only) by 1.0°C, the following will occur:
• the PATIENT temperature will ash;
• the ALERT led will ash; and;
• the audible alarm will toggle
Once thepatient temperature returns to within 1.0°C of the
warming rate specied by the CONTROL OPTION selected,
the PATIENT temerature and ALERT light will stop ashing
and the audible alarm will silence.
NOTE: If the control MODE or SETPOINT is changed
while this alarm is occuring, the alarm will be reset.
NOTE: If the control MODE or SET POINT is changed
while in Auto-Gradual or Auto-Moderate control
mode, this may impact the overall time period of
the therapy depending on when in the hourly cycle
the mode is interrupted. The therapy time duration is
also dependent on the patient’s temperature at the time
the Auto Moderate or Auto Gradual control modes are
re-selected.
For water temperature control, the main microcontroller control
system outputs a pulse train to each solenoid valve. The pulse
train to the hot solenoid (and also heater) is the complement
of the pulse train to the cold solenoid. The pulse train duty
cycle depends on the magnitude and sense of the control
signal calculated by the main microcontroller. That is, while the
solenoids are each either on or off, the ratio of on time to off time
is proportional to the calculated control signal amplitude. For large
differences between set point and probe temperatures, the output
to each solenoid valve will be either on or off. For differences
approaching zero, the outputs to the solenoid valves (and heater)
will switch on and off, with the on and off times automatically
adjusted to maintain a probe temperature equal to the set point.
The circulating pump is energized whenever the unit is in
PATIENT CONTROL or BLANKET CONTROL modes.
The control latch U51 on the control/display board is the interface
between the main microcontroller (via the data bus at address
0FF7FH) and the peripheral drivers on the power supply board.
Interface circuitry on the power supply board consists of U1, U2,
U7, U8, Q3, Q4, Q8, Q9, and associated components. U1, U2,
U7, and U8 are optically coupled triac drivers used to control
their respective triacs (Q3, Q4, Q8, and Q9); these combinations
provide electrical isolation between the low voltage main
microcontroller control circuits and the line voltage circuits.
The heater, pump, hot solenoid valve, and cold solenoid valve
are individually controlled by the main microcontroller through
latch U51 on the control/display board. A high signal on the data
line from the main microcontroller causes a low signal on the
appropriate output line of U51 which then sinks current from the
power supply board to activate the peripheral devices.
Pin 11 of U51 on the control/display board and U8 and Q9 of the
power supply board control the cold solenoid valve while pin 9
of U51 on the control/display board and U7 and Q8 of the power
supply board control the hot solenoid valve. Pin 8 of U51 on the
control/display board and U2 and Q4 of the power supply board
control the circulating pump. Pin 7 of U51 on the control/display
board and U1 and Q3 of the power supply board control power to
the heater.
6.4.6 Cold Water Reservoir Temperature Control
The control latch U51 on the control/display board is the interface
between the main microcontroller (via the data bus at address
0FF7FH) and the refrigeration compressor relay driver on the
power supply board. A high signal on the appropriate data line
causes a low signal at pin 6 of U51 on the control/display board,
which then activates Q12 on the power supply board. Q12 on the
power supply board is the interface between the control/display
board and the coil of the power relay K1 located in the machine
base. The main microcontroller switches power through the relay
to the refrigeration compressor at cut-out and cut-in temperatures
of 3.3°C and 5.8°C. These temperatures are sensed by the cold
water reservoir probe RTl located in the water reservoir. (See
gure 16, p. 55.) Control of the cold water reservoir temperature
takes place whenever the machine is on.
6.4.7 Backup Water Temperature Limiting
Water temperature limiting is provided by two systems; Backup
System I and Backup System II.
Backup System I consists of a PIC microcontroller residing on the
alarm/backup board, the over-temperature probe RT3 located in
the base, and one of the REMOVE FROM USE NOW latching
circuits on the power supply board.
Backup System II consists of two REMOVE FROM USE NOW
latching circuits and two xed non-adjustable temperature limit
thermostats, S1 and S2 located in the base.
6.4.7.1 REMOVE FROM USE NOW Latching Circuits
The power supply board includes two REMOVE FROM USE
NOW latching circuits made up of U3, U4, U5, U6, U9, U10, D2,
D3, Q1, Q2, and their interconnecting components. Under normal
circumstances, Q1 and Q2 are kept turned on by the action of R7,
C10, and D4 and R5, C15, and D5 to complete the conduction
path for the heater and pump.
6.4.7.2 Backup System I
The PIC microcontroller has its own power supply on the alarm/
backup board which is independent of the main microcontroller’s
Theory of Operation
14